agent countdown to 10 seconds. The fire suppression agent is released when the countdown is exhausted and the horn progresses to the
Personnel can press and hold the fire suppression abort button to stop the original
Manual initiation
Manual initiation causes the fire strobe lights to illuminate, the horn goes to the
The fire suppression abort button is inactive if a manual fire pull was activated and the release of the fire suppression agent is imminent. All personnel should immediately evacuate.
Emergency egress
The HP POD 20c includes the following features for life safety egress on all access doors:
•Panic bar
•Door strikes
o Standard
o Optional
Each personnel door includes a standard panic bar to ensure safe exit. The optional egress hardware included in the HP POD 20c (including electric panic bars, electric strikes, and magnetic locks) are tied to the fire alarm to enable uninhibited egress in the event of an emergency.
Life safety systems 24