HP Performance Optimized Data Center (POD) 20cp manual Cold weather power up checklist

Page 71

This process helps to ensure personnel safety during the electrical start up of the HP POD 20c.

WARNING: To avoid risk of personal injury or loss of life, do not open an energized POD electrical cabinet without an energized work permit and appropriate PPE.

Cold weather power up checklist

Site electrical

Open (verify open) all site POD feeder supply breakers.

Site mechanical

Verify that the POD supply and return isolation valves are closed.

POD mechanical

Open (verify open) POD chilled water return butterfly isolation valve.

POD electrical

Hot aisle—Verify that all IT power drop box breakers on the power tap boxes are open.

Cold aisle:

a.Close all breakers and fuses within the control cabinet.

b.Close and latch the ECS cabinet.

c.Position the EPO system (on page 18) to Armed (White) or Bypass (Green).

d.Verify that all EPO activation buttons are in the reset position (not depressed).

e.Position the 24V DC power switch to On.

Main power feed cabinet:

a.Close main power feed breakers A and B.

b.Verify power surge fuses are installed.

House power and critical IT power cabinets:

a.Close all fuses in the house power and critical IT power cabinets.

b.Close all non-spare breakers in the house power and critical IT power cabinets.

c.Close and lock both house power and transformer cabinet doors.

Standard power up procedure

Perform the following procedures in the exact order in which they are listed.

Site electrical

Close all POD site power feeder breakers and monitor for any effects that are not standard.

ECS and EPO

Verify the following using the ECS touchscreen and EPO indicators:

The ECS panel is operational and displays the user interface.

POD lighting is operational.

Power up procedure 71

Image 71
Contents Part Number March Edition AbstractPage Contents Networking Connection portals Demarcation box Fire box Fire protection system Humidifier Controlled accessBefore you contact HP HP contact information Periodic maintenance Sample HP POD 20c maintenance scheduleBefore you begin Operator safetyComponent safety OverviewEnvironmental considerations Fire detection and suppressionParts and part number identification Component identificationStructural component identification Internal life safety components Life safety component identificationEnd view shown Component Description Page Main breaker locations Electrical power component identificationFront view shown Component Description Component identification Front view shown Electrical safety label Description Electrical safety label Description Control cabinet component identification Component Description HP POD 20c racksEPO system Life safety systemsLife safety overview ECS touchscreen and EPO indicators EPO accidental activation Battery backup during an EPO eventComponent Indicator Color Description EPO modesManual fire button Vesda air sampling smoke detection systemOptional Fire protection system Fire system operator panel Fire alarm indicatorsFire suppression system Fire suppression sequence of operations Emergency egress Grounding Power, electrical, and controlsPower safety Site electrical systemLightning protection Electrical and mechanical cooling capacities Power feedersFeature Specification CapacitiesElectrical panels Arc flash safetyPower distribution electrical busway system Panel schedules Wire color codeFront view shown Feature Specification Wiring system-Critical IT power feeds and main power feedsElectrical busways Wire color Label DescriptionDrop boxes Rack power Power configurationsHP POD 20c lighting Environmental control system overview Using the ECSEnvironmental control system Pressure sensors SensorsHumidity sensors Temperature sensors Environmental control system Facility chilled water sensors Connecting to the ECSFacility connections to ECS Managing the ECS from the HP POD 20c Configuring the ECSEnvironmental control system Logging in remotely to the ECS Locating the ECS IP addresses Enter ipconfigNavigating the ECS interface Password protectionButton Description Logging in to the ECS touchscreenOverview screen Enter your ECS password Click OKInformation Description Status Overview screen Basic System Configuration screenCurrent temperature parameters appear on the related buttons Environmental control system Configuring the cold aisle temperature alarm parameters Configuring the humidity alarm parametersConfiguring the differential pressure alarm parameters Configuring the hot aisle temperature alarm parametersSetting the fan controls for each fan control zone Advanced System Configuration screenSetting the humidifier control Setting the start-up alarm reset delay Calibrating the differential pressure sensors Setting the logging configurationCalibrating the flowmeter Loading default settings Controller Settings screenSetting the switchboard serial number Setting the HP POD 20c serial numberPI parameter Fan failure ECS alarmsAlarm Meaning Solution Safety and access control alarmsHP POD 20c cooling system theory of operation Water supply temperatureCooling system Water quality requirements and specifications Cooling system components Fans Drains Condensation managementCold aisle drains Hot aisle drainsLeak detection Demarcation box IT networking and communicationsNetworking Connection portalsFire box Humidifier Controlled accessOptional components Fire protection systemPower up checklist Power up procedureStandard HP POD 20c power up procedure Standard power up procedure Cold weather HP POD 20c power up procedureCold weather power up checklist POD heating procedure Power down procedure Features Specifications SpecificationsGeneral HP POD 20c specifications Electrical specificationsStandard HP POD 20c racks AT978A Feature Specification Rack specificationsEnvironmental specifications Water specificationsFeature Specification Sample HP POD 20c maintenance schedule MaintenancePeriodic maintenance HP contact information Contacting HPBefore you contact HP HP POD 20c regulatory compliance Safety and IEC complianceRegulatory information Warranty information Safety and regulatory complianceGlossary Personal protective equipment Power distribution unitProgrammable logic controller Rack units Enclosure of sufficient size to enable entry of personnelUninterruptible power system Documentation feedback EPO panel Environmental specifications EPO accidental activationIndex Vesda