Fire alarm panel connections
The electrical layout of the fire alarm system is as described in the schematic drawing supplied with the HP POD 20c.
Water specifications
The following table describes the chilled water system specifications for the HP POD 20c.
Feature | Specification |
|
|
Facility input temperature to the HP POD | 12º to 24ºC (55º to 75ºF) |
20c |
|
Max design pressure | 1,034 kPa (150 psi) |
HP POD 20c pressure drop | 172.4 kPa (25 psi) |
HP POD 20c water flow rate | 454 lpm (120 gpm*) |
Chilled water supply and return | Two DIN PN16 DN80 flanges |
connections |
|
*Measurement is in US gallons per minute.
Rack specifications
Standard HP POD 20c racks (AT978A)
Feature | Specification |
|
|
U height | 50U |
Width | 54.6 cm (21.5 in) |
Depth | 99 cm (39 in)* |
Maximum load weight | 1,360.7 kg (3,000 lb) |
*This specification indicates the maximum clearance for the cold aisle. Equipment cannot exceed this measurement.
Thermal and air flow performance
Maximum thermal and air flow | HP POD 20c specification |
performance parameters |
|
|
|
Air | Dependent on IT configuration and |
chilled water inlet temperature | |
Chilled water temperature | 12°C to 24°C (55°F to 75°F) |
Total | Variable as required to maintain hot |
flow | aisle setpoint temperature and |
| dependent on IT configuration |
|
|
Heat rejection capacity | 300 kW |
Environmental specifications
Feature | Specification |
|
|
Operating temperature |
Specifications 75