HP Performance Optimized Data Center (POD) 20cp manual Environmental control system, Using the ECS

Page 34

Environmental control system

Environmental control system overview

The ECS developed for the HP water-cooled POD is a stand-alone control system that requires no external connections with an external site system, BMS, public or private Internet sites, cloud, or wireless system to properly control the POD operation.

The ECS includes Modbus TCP/IP connections through which a variety of data can be retrieved. These capabilities enable you to connect, at your expense, with the stand-alone ECS system to monitor the operating parameters of the POD. It is your responsibility (or your representative's or agent's responsibility) to integrate this communication capability into any existing BMS or monitoring system.

CAUTION: To ensure that alarm conditions can be identified and resolved, HP recommends that you remotely monitor all alarm conditions. Failure to monitor the alarm conditions can cause delays in appropriate action during an alarm condition.

Using the ECS

HP recommends connecting the HP POD 20c to your facility BMS and establishing communication through the Ethernet cable connected to the external communications box. For more information, see "Configuring the ECS (on page 39)."

The HP POD 20c ECS is a Windows-based system with the following features:

Intel Core Duo processor

15-inch touchscreen

512 MB RAM

80 GB hard drive

24 V DC power supply

One serial port

Four USB ports

1x10/100 BASE-T and 1x10/100/1000 BASE-T Ethernet connectors

The standard ECS protocol, Modbus TCP/IP, is a data communication protocol for building automation and control networks. Connecting across different protocols might require additional engineering labor and coordination between your in-house control manufacturer and HP. It is your responsibility to make the connection between the HP POD 20c and a BMS system.

The ECS provides the following:

A supported communication interface that can monitor and control certain HP POD 20c components remotely

Immediate notification of all supported alarm messages

Environmental control system 34

Image 34
Contents Abstract Part Number March EditionPage Contents Fire protection system Humidifier Controlled access Networking Connection portals Demarcation box Fire boxPeriodic maintenance Sample HP POD 20c maintenance schedule Before you contact HP HP contact informationOverview Operator safetyComponent safety Before you beginFire detection and suppression Environmental considerationsStructural component identification Component identificationParts and part number identification Life safety component identification Internal life safety componentsEnd view shown Component Description Page Front view shown Component Description Electrical power component identificationMain breaker locations Component identification Front view shown Electrical safety label Description Electrical safety label Description Control cabinet component identification HP POD 20c racks Component DescriptionLife safety overview Life safety systemsEPO system ECS touchscreen and EPO indicators EPO modes Battery backup during an EPO eventComponent Indicator Color Description EPO accidental activationOptional Fire protection system Vesda air sampling smoke detection systemManual fire button Fire suppression system Fire alarm indicatorsFire system operator panel Fire suppression sequence of operations Emergency egress Site electrical system Power, electrical, and controlsPower safety GroundingLightning protection Capacities Power feedersFeature Specification Electrical and mechanical cooling capacitiesPower distribution electrical busway system Arc flash safetyElectrical panels Wiring system-Critical IT power feeds and main power feeds Wire color codeFront view shown Feature Specification Panel schedulesWire color Label Description Electrical busways Drop boxes Power configurations Rack powerHP POD 20c lighting Environmental control system Using the ECSEnvironmental control system overview Humidity sensors SensorsPressure sensors Temperature sensors Environmental control system Facility connections to ECS Connecting to the ECSFacility chilled water sensors Configuring the ECS Managing the ECS from the HP POD 20cEnvironmental control system Logging in remotely to the ECS Enter ipconfig Locating the ECS IP addressesPassword protection Navigating the ECS interfaceLogging in to the ECS touchscreen Button DescriptionEnter your ECS password Click OK Overview screenInformation Description Basic System Configuration screen Status Overview screenCurrent temperature parameters appear on the related buttons Environmental control system Configuring the humidity alarm parameters Configuring the cold aisle temperature alarm parametersConfiguring the hot aisle temperature alarm parameters Configuring the differential pressure alarm parametersSetting the humidifier control Advanced System Configuration screenSetting the fan controls for each fan control zone Setting the start-up alarm reset delay Calibrating the flowmeter Setting the logging configurationCalibrating the differential pressure sensors Setting the HP POD 20c serial number Controller Settings screenSetting the switchboard serial number Loading default settingsPI parameter ECS alarms Fan failureSafety and access control alarms Alarm Meaning SolutionCooling system Water supply temperatureHP POD 20c cooling system theory of operation Water quality requirements and specifications Cooling system components Fans Condensation management DrainsHot aisle drains Cold aisle drainsLeak detection Connection portals IT networking and communicationsNetworking Demarcation boxFire box Fire protection system Controlled accessOptional components HumidifierStandard HP POD 20c power up procedure Power up procedurePower up checklist Cold weather HP POD 20c power up procedure Standard power up procedureCold weather power up checklist POD heating procedure Power down procedure Electrical specifications SpecificationsGeneral HP POD 20c specifications Features SpecificationsWater specifications Rack specificationsEnvironmental specifications Standard HP POD 20c racks AT978A Feature SpecificationFeature Specification Periodic maintenance MaintenanceSample HP POD 20c maintenance schedule Before you contact HP Contacting HPHP contact information Regulatory information Safety and IEC complianceHP POD 20c regulatory compliance Safety and regulatory compliance Warranty informationGlossary Programmable logic controller Power distribution unitPersonal protective equipment Uninterruptible power system Enclosure of sufficient size to enable entry of personnelRack units Documentation feedback Index Environmental specifications EPO accidental activationEPO panel Vesda
Related manuals
Manual 22 pages 15.98 Kb Manual 81 pages 57.33 Kb Manual 37 pages 24.34 Kb Manual 38 pages 28.4 Kb