Configuring the chilled water supply pressure alarm parameters
The current chilled water return pressure alarm parameters appear on the related buttons. To configure the chilled water return pressure low alarm parameters:
1.Select Chilled Water Return Pressure Low Alarm. A keypad appears.
2.Enter a chilled water return pressure alarm parameter.
3.Select Save to store the new parameters in the system configuration file.
To configure the chilled water return pressure high alarm parameters:
1.Select Chilled Water Return Pressure High Alarm. A keypad appears.
2.Enter a chilled water return pressure alarm parameter.
3.Select Save to store the new parameters in the system configuration file.
Configuring the humidity alarm parameters
The current relative humidity parameters appear on the related buttons.
To configure the low humidity parameters:
1.Select the Humidity Low Alarm. A keypad appears.
2.Enter a humidity alarm parameter.
3.Select Save to store the new parameters in the system configuration file.
To configure the high humidity parameters:
1.Select the Humidity High Alarm. A keypad appears.
2.Enter a humidity alarm parameter.
3.Select Save to store the new parameters in the system configuration file.
Configuring the cold aisle temperature alarm parameters
The current temperature parameters appear on the related buttons.
To configure the cold aisle low temperature alarm parameters:
1.Select Cold Aisle Low Alarm Temperature. A keypad appears.
2.Enter a temperature alarm parameter.
3.Select Save to store the new parameters in the system configuration file.
To configure the cold aisle high temperature alarm parameters:
1.Select Cold Aisle High Alarm Temperature. A keypad appears.
2.Enter a temperature alarm parameter.
3.Select Save to store the new parameters in the system configuration file.