Feature | Specification |
|
|
Rack type | HP POD rack |
Max number of racks | 10 |
Max U space per rack | 50U |
Max U space per HP POD 20c | 500U |
Server capacity | 288 kW power capacity |
Average capacity per rack | 28.8 kW |
Peak capacity per rack | 69 kW |
Voltage to rack | |
Rack configuration | |
| capabilities |
Total number of PDU's | 20 (two per rack) |
Max power per PDU | 30 A = 17 kW; 60 A = 34 kW |
Max load (Chilled POD cooling mode)* | 288 kW |
Airflow per rack (Chiller POD cooling | 1,700 CFM |
mode) |
|
*Dependent on configuration |
|
HP POD 20c lighting
The HP POD 20c includes six LED lights. Three lights are located in the cold aisle and three lights are located in the hot aisle.
The main light switch is located on the ECS control panel door. For more information on the light switch location, see "Life safety component identification (on page 9)."
Two of the six lights are connected to battery backup power, keeping the interior of the HP POD 20c illuminated during a power outage or emergency.
For more information on lighting, see the HP Performance Optimized Datacenter 20c Maintenance and Service Guide.
Power, electrical, and controls 33