The Controller Settings screen displays the control setpoints for each major system component.
You can set the following configuration options:
•PI settings temperature
•PI settings pressure
You must select Save to store the parameter changes in the system configuration file. If you do not save your changes, the old parameters stored in the configuration file reload when the system starts.
Item | Description |
|
|
Temperature setpoint (hot | Sets the temperature setpoint for the hot aisle |
aisle) |
|
Pressure setpoint | Sets the pressure setpoint |
PI parameter P | Proportion gains influence the rate of change in the position of the flow control |
| valve or the fan speed in order to reach the |
|
|
PI parameter I | Integral gains influence the rate of change in the position of the flow control valve |
| or the fan speed in order to reach the |
PI integration time | Used by the low pass filter to even the measurement values out |
|
|