HP Performance Optimized Data Center (POD) 20cp Fire alarm indicators, Fire suppression system

Page 22

Triggers a fire alarm signal to the BMS in the fire box (on page 67) and activates a 30-second delay before releasing the fire suppression agent

IMPORTANT: The fire suppression abort button does not delay the release of the fire suppression agent if a manual fire button is initiated. The release of the fire suppression agent is imminent and all personnel should evacuate immediately.

Fire alarm indicators

Upon activation of a fire alarm within the HP POD 20c, the following alarms alert personnel:

Strobe light—The HP POD 20c includes two fire strobe lights. One is located in the cold aisle and one is located on the POD exterior.

Audible horn—The HP POD 20c includes two audible horns. One is located in the cold aisle and one is located on the POD exterior.

Alarm within the ECS—The ECS system notifies you of a fire alarm condition with an alarm alert on the ECS screen.

Fire suppression system

WARNING: Fire suppression agents include a pre-discharge warning and evacuating system. In the event of a fire, all protected space must be evacuated as soon as possible.

CAUTION: The POD fire suppression system is manufacturer designed, engineered, and installed to comply with national standards. However, HP does not certify that the installed fire suppression system meets all local jurisdictional requirements. Compliance with local codes is your responsibility, and includes specific local requirements for initial and periodic inspections, certifications, and maintenance.

Any additional local requirements are not covered as part of the option price or basic installation and deployment services, unless specifically included in an executed Statement of Work.

IMPORTANT: The fire suppression abort buttons that are located on the ECS panel and next to the fire suppression cylinders can be pressed to interrupt the 60-second fire suppression agent release delay of the VESDA system. Pressing either of these buttons resets the fire suppression agent release delay to 10 seconds. Pressing and holding either of the fire suppression abort buttons stops the agent release. Releasing the fire suppression abort button that is being held gives personnel 10 seconds to evacuate before agent release. The fire suppression abort buttons do not operate if a manual fire button is activated.

The fire suppression system contains conventional fire alarm control circuits and includes features required for single or dual-hazard suppression release applications, including a low-toxicity agent. In the event of fire suppression release, the suppression tanks must be refilled by a certified technician.

Fire system operator panel

The panel is configured by the manufacturer in accordance with the local fire marshal and fire code requirements.

The operator panel includes the following:

Alarm status LED

Life safety systems 22

Image 22
Contents Abstract Part Number March EditionPage Contents Fire protection system Humidifier Controlled access Networking Connection portals Demarcation box Fire boxPeriodic maintenance Sample HP POD 20c maintenance schedule Before you contact HP HP contact informationOverview Operator safetyComponent safety Before you beginFire detection and suppression Environmental considerationsStructural component identification Component identificationParts and part number identification Life safety component identification Internal life safety componentsEnd view shown Component Description Page Front view shown Component Description Electrical power component identificationMain breaker locations Component identification Front view shown Electrical safety label Description Electrical safety label Description Control cabinet component identification HP POD 20c racks Component DescriptionLife safety overview Life safety systemsEPO system ECS touchscreen and EPO indicators EPO modes Battery backup during an EPO eventComponent Indicator Color Description EPO accidental activationOptional Fire protection system Vesda air sampling smoke detection systemManual fire button Fire suppression system Fire alarm indicatorsFire system operator panel Fire suppression sequence of operations Emergency egress Site electrical system Power, electrical, and controlsPower safety GroundingLightning protection Capacities Power feedersFeature Specification Electrical and mechanical cooling capacitiesPower distribution electrical busway system Arc flash safetyElectrical panels Wiring system-Critical IT power feeds and main power feeds Wire color codeFront view shown Feature Specification Panel schedulesWire color Label Description Electrical buswaysDrop boxes Power configurations Rack powerHP POD 20c lighting Environmental control system Using the ECSEnvironmental control system overview Humidity sensors SensorsPressure sensors Temperature sensors Environmental control system Facility connections to ECS Connecting to the ECSFacility chilled water sensors Configuring the ECS Managing the ECS from the HP POD 20cEnvironmental control system Logging in remotely to the ECS Enter ipconfig Locating the ECS IP addressesPassword protection Navigating the ECS interfaceLogging in to the ECS touchscreen Button DescriptionEnter your ECS password Click OK Overview screenInformation Description Basic System Configuration screen Status Overview screenCurrent temperature parameters appear on the related buttons Environmental control system Configuring the humidity alarm parameters Configuring the cold aisle temperature alarm parametersConfiguring the hot aisle temperature alarm parameters Configuring the differential pressure alarm parametersSetting the humidifier control Advanced System Configuration screenSetting the fan controls for each fan control zone Setting the start-up alarm reset delay Calibrating the flowmeter Setting the logging configurationCalibrating the differential pressure sensors Setting the HP POD 20c serial number Controller Settings screenSetting the switchboard serial number Loading default settingsPI parameter ECS alarms Fan failureSafety and access control alarms Alarm Meaning SolutionCooling system Water supply temperatureHP POD 20c cooling system theory of operation Water quality requirements and specifications Cooling system components Fans Condensation management DrainsHot aisle drains Cold aisle drainsLeak detection Connection portals IT networking and communicationsNetworking Demarcation boxFire box Fire protection system Controlled accessOptional components HumidifierStandard HP POD 20c power up procedure Power up procedurePower up checklist Cold weather HP POD 20c power up procedure Standard power up procedureCold weather power up checklist POD heating procedure Power down procedure Electrical specifications SpecificationsGeneral HP POD 20c specifications Features SpecificationsWater specifications Rack specificationsEnvironmental specifications Standard HP POD 20c racks AT978A Feature SpecificationFeature Specification Periodic maintenance MaintenanceSample HP POD 20c maintenance schedule Before you contact HP Contacting HPHP contact information Regulatory information Safety and IEC complianceHP POD 20c regulatory compliance Safety and regulatory compliance Warranty informationGlossary Programmable logic controller Power distribution unitPersonal protective equipment Uninterruptible power system Enclosure of sufficient size to enable entry of personnelRack units Documentation feedback Index Environmental specifications EPO accidental activationEPO panel Vesda