HP Performance Optimized Data Center (POD) 20cp Specifications, General HP POD 20c specifications

Page 74

Specifications

General HP POD 20c specifications

Features

Specifications

 

 

Overall dimensions

Height—3.05 m (10 ft)

 

Length—6.10 m (20 ft)

 

Width—2.43 m (7.97 ft)

 

 

Weight1

Empty—7,711 kg (17,000 lb)

 

Maximum fully loaded—22,680 kg (50,000 lb)

 

 

Maximum power2

288 kW

Power input voltage

380-415 V, 3-phase, 4-wire

Power input current

2 x 320 A electrical busways 3-phase, 4-wire feeders

Maximum rack quantity

10 racks

Rack Units (RU) per rack

50 RU

Rack Units (RU) total

500 RU

Average capacity per rack (kW)

30 kW

Peak rack capacity

69 kW

 

 

Voltage to rack

200-240 VAC

Minimum quantity of PDUs per HP POD 20c

10 (one per rack)

Maximum quantity of PDUs per HP POD 20c

20 (two per rack)

Maximum power per PDU

30A = 17 kW; 60A = 34 kW

Network supported

Bulk cable pass-through-fiber

 

Bulk cable pass-through-copper

 

External rated DEMARC box

 

 

1The empty weight includes the HP POD 20c structure, empty racks, PDUs, and drop boxes. It does not include IT equipment.

2The maximum power depends on the exact installation and power configuration in your POD. The HP POD 20c is electrically limited to 288 kW.

Electrical specifications

Electrical busway system information

Feature

Specification

 

 

Number of busways

2

Frequency

50-60 Hz

Amps (per busway)

200 A

Voltage (per busway)

380-415 VAC Wye

Grounding

Copper

Busway configuration

3-phase + neutral + equipment ground

Specifications 74

Image 74
Contents Abstract Part Number March EditionPage Contents Fire protection system Humidifier Controlled access Networking Connection portals Demarcation box Fire boxPeriodic maintenance Sample HP POD 20c maintenance schedule Before you contact HP HP contact informationOverview Operator safetyComponent safety Before you beginFire detection and suppression Environmental considerationsParts and part number identification Component identificationStructural component identification Life safety component identification Internal life safety componentsEnd view shown Component Description Page Main breaker locations Electrical power component identificationFront view shown Component Description Component identification Front view shown Electrical safety label Description Electrical safety label Description Control cabinet component identification HP POD 20c racks Component DescriptionEPO system Life safety systemsLife safety overview ECS touchscreen and EPO indicators EPO modes Battery backup during an EPO eventComponent Indicator Color Description EPO accidental activationManual fire button Vesda air sampling smoke detection systemOptional Fire protection system Fire system operator panel Fire alarm indicatorsFire suppression system Fire suppression sequence of operations Emergency egress Site electrical system Power, electrical, and controlsPower safety GroundingLightning protection Capacities Power feedersFeature Specification Electrical and mechanical cooling capacitiesElectrical panels Arc flash safetyPower distribution electrical busway system Wiring system-Critical IT power feeds and main power feeds Wire color codeFront view shown Feature Specification Panel schedulesWire color Label Description Electrical buswaysDrop boxes Power configurations Rack powerHP POD 20c lighting Environmental control system overview Using the ECSEnvironmental control system Pressure sensors SensorsHumidity sensors Temperature sensors Environmental control system Facility chilled water sensors Connecting to the ECSFacility connections to ECS Configuring the ECS Managing the ECS from the HP POD 20cEnvironmental control system Logging in remotely to the ECS Enter ipconfig Locating the ECS IP addressesPassword protection Navigating the ECS interfaceLogging in to the ECS touchscreen Button DescriptionEnter your ECS password Click OK Overview screenInformation Description Basic System Configuration screen Status Overview screenCurrent temperature parameters appear on the related buttons Environmental control system Configuring the humidity alarm parameters Configuring the cold aisle temperature alarm parametersConfiguring the hot aisle temperature alarm parameters Configuring the differential pressure alarm parametersSetting the fan controls for each fan control zone Advanced System Configuration screenSetting the humidifier control Setting the start-up alarm reset delay Calibrating the differential pressure sensors Setting the logging configurationCalibrating the flowmeter Setting the HP POD 20c serial number Controller Settings screenSetting the switchboard serial number Loading default settingsPI parameter ECS alarms Fan failureSafety and access control alarms Alarm Meaning SolutionHP POD 20c cooling system theory of operation Water supply temperatureCooling system Water quality requirements and specifications Cooling system components Fans Condensation management DrainsHot aisle drains Cold aisle drainsLeak detection Connection portals IT networking and communicationsNetworking Demarcation boxFire box Fire protection system Controlled accessOptional components HumidifierPower up checklist Power up procedureStandard HP POD 20c power up procedure Cold weather HP POD 20c power up procedure Standard power up procedureCold weather power up checklist POD heating procedure Power down procedure Electrical specifications SpecificationsGeneral HP POD 20c specifications Features SpecificationsWater specifications Rack specificationsEnvironmental specifications Standard HP POD 20c racks AT978A Feature SpecificationFeature Specification Sample HP POD 20c maintenance schedule MaintenancePeriodic maintenance HP contact information Contacting HPBefore you contact HP HP POD 20c regulatory compliance Safety and IEC complianceRegulatory information Safety and regulatory compliance Warranty informationGlossary Personal protective equipment Power distribution unitProgrammable logic controller Rack units Enclosure of sufficient size to enable entry of personnelUninterruptible power system Documentation feedback EPO panel Environmental specifications EPO accidental activationIndex Vesda