HP Performance Optimized Data Center (POD) 20cp Electrical busways, Wire color Label Description

Page 30

Wire color

Label

Description

 

 

 

Brown

L1

A Phase

 

 

 

Black

L2

B Phase

Grey

L3

C Phase

Blue

N

Neutral

Green and yellow

PE

Equipment grounding conductor

 

 

Bonding conductor

 

 

Earth ground

 

 

 

 

Electrical busways

The electrical busway is a modular, overhead electrical distribution system that supplies power to the HP POD 20c IT loads. The HP POD 20c has a total of two busways, and each bus can support 200 A.

Top view shown

The HP POD 20c electrical busways can be configured for non-redundant power or redundant power. The HP POD 20c can be installed as a single source 1N load by providing all required feeders from one common power source and from common switchboards and transformers. A 2N redundancy installation is configured by feeding the parallel power paths from independent power sources, switchboards, and transformers.

Power, electrical, and controls 30

Image 30
Contents Abstract Part Number March EditionPage Contents Fire protection system Humidifier Controlled access Networking Connection portals Demarcation box Fire boxPeriodic maintenance Sample HP POD 20c maintenance schedule Before you contact HP HP contact informationOverview Operator safetyComponent safety Before you beginFire detection and suppression Environmental considerationsComponent identification Structural component identificationParts and part number identification Life safety component identification Internal life safety componentsEnd view shown Component Description Page Electrical power component identification Front view shown Component DescriptionMain breaker locations Component identification Front view shown Electrical safety label Description Electrical safety label Description Control cabinet component identification HP POD 20c racks Component DescriptionLife safety systems Life safety overviewEPO system ECS touchscreen and EPO indicators EPO modes Battery backup during an EPO eventComponent Indicator Color Description EPO accidental activationVesda air sampling smoke detection system Optional Fire protection systemManual fire button Fire alarm indicators Fire suppression systemFire system operator panel Fire suppression sequence of operations Emergency egress Site electrical system Power, electrical, and controlsPower safety GroundingLightning protection Capacities Power feedersFeature Specification Electrical and mechanical cooling capacitiesArc flash safety Power distribution electrical busway systemElectrical panels Wiring system-Critical IT power feeds and main power feeds Wire color codeFront view shown Feature Specification Panel schedulesWire color Label Description Electrical buswaysDrop boxes Power configurations Rack powerHP POD 20c lighting Using the ECS Environmental control systemEnvironmental control system overview Sensors Humidity sensorsPressure sensors Temperature sensors Environmental control system Connecting to the ECS Facility connections to ECSFacility chilled water sensors Configuring the ECS Managing the ECS from the HP POD 20cEnvironmental control system Logging in remotely to the ECS Enter ipconfig Locating the ECS IP addressesPassword protection Navigating the ECS interfaceLogging in to the ECS touchscreen Button DescriptionEnter your ECS password Click OK Overview screenInformation Description Basic System Configuration screen Status Overview screenCurrent temperature parameters appear on the related buttons Environmental control system Configuring the humidity alarm parameters Configuring the cold aisle temperature alarm parametersConfiguring the hot aisle temperature alarm parameters Configuring the differential pressure alarm parametersAdvanced System Configuration screen Setting the humidifier controlSetting the fan controls for each fan control zone Setting the start-up alarm reset delay Setting the logging configuration Calibrating the flowmeterCalibrating the differential pressure sensors Setting the HP POD 20c serial number Controller Settings screenSetting the switchboard serial number Loading default settingsPI parameter ECS alarms Fan failureSafety and access control alarms Alarm Meaning SolutionWater supply temperature Cooling systemHP POD 20c cooling system theory of operation Water quality requirements and specifications Cooling system components Fans Condensation management DrainsHot aisle drains Cold aisle drainsLeak detection Connection portals IT networking and communicationsNetworking Demarcation boxFire box Fire protection system Controlled accessOptional components HumidifierPower up procedure Standard HP POD 20c power up procedurePower up checklist Cold weather HP POD 20c power up procedure Standard power up procedureCold weather power up checklist POD heating procedure Power down procedure Electrical specifications SpecificationsGeneral HP POD 20c specifications Features SpecificationsWater specifications Rack specificationsEnvironmental specifications Standard HP POD 20c racks AT978A Feature SpecificationFeature Specification Maintenance Periodic maintenanceSample HP POD 20c maintenance schedule Contacting HP Before you contact HPHP contact information Safety and IEC compliance Regulatory informationHP POD 20c regulatory compliance Safety and regulatory compliance Warranty informationGlossary Power distribution unit Programmable logic controllerPersonal protective equipment Enclosure of sufficient size to enable entry of personnel Uninterruptible power systemRack units Documentation feedback Environmental specifications EPO accidental activation IndexEPO panel Vesda
Related manuals
Manual 22 pages 15.98 Kb Manual 81 pages 57.33 Kb Manual 37 pages 24.34 Kb Manual 38 pages 28.4 Kb