HP Performance Optimized Data Center (POD) 20cp manual Power down procedure

Page 73

3.Wait five minutes to allow the system to stabilize.

The HP POD 20c is now fully operational and the control system automatically controls the fans and the flow control valve position.

Power down procedure

1.Power down all IT equipment.

2.Open all POD power drop box breakers.

3.Monitor the system parameters and allow the POD to cool to an acceptable temperature. Be sure that the cold aisle temperature does not fall below 10°C (50°F.)

4.Close the POD return chilled water isolation valve.

5.Close the POD supply chilled water isolation valve.

6.Open the POD main power feed breakers.

7.Unlock the POD house power and critical IT power cabinets.

8.Open all breakers in the POD power cabinets A and B.

9.Unlock the POD main power feed cabinet.

10.Open all breakers in the POD main power feed cabinet.

The HP POD 20c is now powered down and all breakers are ready for standard or cold weather power up.

Power up procedure 73

Image 73
Contents Part Number March Edition AbstractPage Contents Networking Connection portals Demarcation box Fire box Fire protection system Humidifier Controlled accessBefore you contact HP HP contact information Periodic maintenance Sample HP POD 20c maintenance scheduleComponent safety Operator safetyOverview Before you beginEnvironmental considerations Fire detection and suppressionStructural component identification Component identificationParts and part number identification Internal life safety components Life safety component identificationEnd view shown Component Description Page Front view shown Component Description Electrical power component identificationMain breaker locations Component identification Front view shown Electrical safety label Description Electrical safety label Description Control cabinet component identification Component Description HP POD 20c racksLife safety overview Life safety systemsEPO system ECS touchscreen and EPO indicators Component Indicator Color Description Battery backup during an EPO eventEPO modes EPO accidental activationOptional Fire protection system Vesda air sampling smoke detection systemManual fire button Fire suppression system Fire alarm indicatorsFire system operator panel Fire suppression sequence of operations Emergency egress Power safety Power, electrical, and controlsSite electrical system GroundingLightning protection Feature Specification Power feedersCapacities Electrical and mechanical cooling capacitiesPower distribution electrical busway system Arc flash safetyElectrical panels Front view shown Feature Specification Wire color codeWiring system-Critical IT power feeds and main power feeds Panel schedulesElectrical busways Wire color Label DescriptionDrop boxes Rack power Power configurationsHP POD 20c lighting Environmental control system Using the ECSEnvironmental control system overview Humidity sensors SensorsPressure sensors Temperature sensors Environmental control system Facility connections to ECS Connecting to the ECSFacility chilled water sensors Managing the ECS from the HP POD 20c Configuring the ECSEnvironmental control system Logging in remotely to the ECS Locating the ECS IP addresses Enter ipconfigNavigating the ECS interface Password protectionButton Description Logging in to the ECS touchscreenOverview screen Enter your ECS password Click OKInformation Description Status Overview screen Basic System Configuration screenCurrent temperature parameters appear on the related buttons Environmental control system Configuring the cold aisle temperature alarm parameters Configuring the humidity alarm parametersConfiguring the differential pressure alarm parameters Configuring the hot aisle temperature alarm parametersSetting the humidifier control Advanced System Configuration screenSetting the fan controls for each fan control zone Setting the start-up alarm reset delay Calibrating the flowmeter Setting the logging configurationCalibrating the differential pressure sensors Setting the switchboard serial number Controller Settings screenSetting the HP POD 20c serial number Loading default settingsPI parameter Fan failure ECS alarmsAlarm Meaning Solution Safety and access control alarmsCooling system Water supply temperatureHP POD 20c cooling system theory of operation Water quality requirements and specifications Cooling system components Fans Drains Condensation managementCold aisle drains Hot aisle drainsLeak detection Networking IT networking and communicationsConnection portals Demarcation boxFire box Optional components Controlled accessFire protection system HumidifierStandard HP POD 20c power up procedure Power up procedurePower up checklist Standard power up procedure Cold weather HP POD 20c power up procedureCold weather power up checklist POD heating procedure Power down procedure General HP POD 20c specifications SpecificationsElectrical specifications Features SpecificationsEnvironmental specifications Rack specificationsWater specifications Standard HP POD 20c racks AT978A Feature SpecificationFeature Specification Periodic maintenance MaintenanceSample HP POD 20c maintenance schedule Before you contact HP Contacting HPHP contact information Regulatory information Safety and IEC complianceHP POD 20c regulatory compliance Warranty information Safety and regulatory complianceGlossary Programmable logic controller Power distribution unitPersonal protective equipment Uninterruptible power system Enclosure of sufficient size to enable entry of personnelRack units Documentation feedback Index Environmental specifications EPO accidental activationEPO panel Vesda