Roberts Gorden UHD[X][S][R] 75, UHD[X][S][R] 125 Shelf Mounting and Suspension, Wall Mounting

Page 14

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL

5.2 Shelf Mounting and Suspension

WARNING

Crush Hazard

Use 3/8" threaded rod minimum.

Failure to follow these instructions can result in death, injury or property damage.

Four suspension points (3/8" nuts) are located on the top of the heater. Drop rods must be 3/8" diameter mild steel.

When handling or supporting the heater from below, ensure that the weight is taken at the support points. For typical suspension, See Page 8, Figure 3.

For typical shelf mounting on existing shelf, See Page 9, Figure 4.

The gas or electrical supply lines must not be used to support the heater.

Figure 3: Suspension Methods

Do not locate the gas or electrical supply lines directly over the path of the flue products from the heater.

The heater must be installed in a location that is readily accessible for servicing.

The heater must be installed in accordance with clearances to combustibles as indicated on the wall tag and in this manual.

5.3 Wall Mounting

For typical suspension, See Page 9, Figure 5. Wall mounted heaters blowing parallel to the wall can only be installed with the service door away from the wall.

The wall mounting brackets must be attached to a suitable wall using all mounting holes. Screw sizes less than 3/8" may not be used. In order for the wall mounting brackets to adequately carry the weight of the heater, it must be installed according to best building practices.

Unistrut Channel

Nut

Washer

Nut

3/8"

Threaded Rod

3/8" Threaded Rod

Nut

Washer

Riv

Nut

Ensure all suspension hardware is torqued to a minimum of 20 ft lbs.

NOTE: Duct supports not shown. Duct supports and duct are not provided by manufacturer.

Cone Point

Set Pin

Window

Clamp

Unistrut

Support Points

8

Image 14
Contents Combat Page Roberts-Gordon LLC Page Table of Figures Page Heater Safety Manpower RequirementsNational Standards and Applicable Codes Installer ResponsibilityCorrosive Chemicals Wall TagManufactured Units Minimum Required Installation ClearancesCritical Considerations 3.1 Basic Information Clearances to CombustiblesGas Supply VentilationElectrical Supply VentNational Standards and Applicable Codes High Altitude Air Flow and Temperature Rise Ranges Duct Heater Installation 5.1 GeneralTemperature Rise and Pressure Drop Ranges Minimum Inlet Duct LengthShelf Mounting and Suspension Wall MountingShelf-Mounting Methods Changing Vent and Air Intake Orientation Vent InstallationVenting United States RequirementsUnvented Operation Standard Vented Heaters Models Uhdxr 75Separated Combustion Heaters Models Uhdxsr 75 Horizontal VentingReplacing an Existing Heater in a Venting System Maximum Vent LengthsVent Material Vent and Roof Detail Standard Vented Heater Common Vertical Vent Termination Concentric Vent Box UHVK1 AIR Supply Separated Combustion InstallationUnvented Installation Building VentilationGAS Piping ConnectionsPositioning Thermostats WiringLow Voltage Thermostat with One Heater Internal Wiring Diagram L2 L1Ladder Wiring Diagram Flue Blower Transformer GAS Valve Flame Sensor ElectrodeElectrical Connection to the Heater Pre-Start-Up Checks Operation and MaintenanceBegin Start-Up Before Operating the Heater Electrical ChecksEND View Turning Off the Heater Pressure SwitchCheck Gas Rate External ControlsHeater Operation User InstructionsUser Instructions Lighting Instructions 11.4.1 To Turn On HeaterTo Turn Heater Off Simple TroubleshootingSimple Troubleshooting Burner Faults Servicing Vehicles and Other Maintenance ChecklistVicinity of the Heater ObjectsValves When installed DuctworkGas Line and Shut-off Burner ObservationTroubleshooting 13.1 General Troubleshooting For Automatic Ignition Burner Systems Conduct start-up procedure as shown on Page 23, SectionTroubleshooting for Flame Supervision System Troubleshooting for Gas Valves Troubleshooting for Flue BlowerReplacement Parts Burner ComponentsBurner Compartment Burner InjectorsIgnition Electrode and Flame Probe Flue Blower Vertical Installation Top, remove the blower and mounting plate as aboveLimit Switches Removal and Replacement Ignition ControlSpecifications 15.1 Dimension Data TOP ViewGeneral Technical Data Table Technical Data TablePage Roberts-Gordon Warranty is Void ifRoberts Gordon will not PAY for Limitations on Authority RepresentativesPage Owner Warranty Registration Card Page Page Clearances to Combustibles