Roberts Gorden UHD[X][S][R] 125, UHD[X][S][R] 75 service manual Troubleshooting 13.1 General

Page 37

SECTION 13: TROUBLESHOOTING

SECTION 13: TROUBLESHOOTING 13.1 General

WARNING

Explosion Hazard

Installation, service and annual inspection must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.

START

Are gas & electrical

No

supplies on?

 

Yes

 

Is ignition control showing a

Yes

"4 flashes" LED code?

No

Turn on supplies.

UHD 75: Press in reset

button on manual reset limit switch. UHD 100 - 125: Wait

10 - 15 minutes for limit Yes switch to cool. Does fan

stop running?

No

Replace temperature limit

switch.

Turn off gas and electrical supplies before performing service or maintenance.

Failure to follow these instructions can result in death, injury or property damage.

Fan and limit switch are operating normally.

Is ignition control showing a

Yes

Burner has locked out due

to ignition failure. Use

"2 flashes" LED code?

 

Troubleshooting for Automatic

 

 

 

 

Ignition Burner Systems

 

 

section to test burner.

No

 

 

Does the flue blower run?

No

Use Troubleshooting for

Flue Blower section to test

 

 

 

fan.

Yess

 

 

With external controls (i.e.

No

Has burner “Locked Out”? No

thermostat) on, does the

burner continue through the

 

 

heating cycle?

 

 

 

 

Yes

 

 

Use Troubleshooting for

 

 

Automatic Ignition Burner

 

 

Systems section to test burner.

Yes

 

 

Heater Operating

 

If problems persist, contact

No

Roberts-Gordon, LLC at

TROUBLESHOOT ENDS.

www.rg-inc.com

 

The limit switch has

tripped. See Manual Reset No Replace limit switch. Limit Switch Figure.

Yes

Ensure air flow through the

heat exchanger is

appropriate per the rating

plate.

31

Image 37
Contents Combat Page Roberts-Gordon LLC Page Table of Figures Page Manpower Requirements Heater SafetyCorrosive Chemicals Installer ResponsibilityNational Standards and Applicable Codes Wall TagCritical Considerations 3.1 Basic Information Minimum Required Installation ClearancesManufactured Units Clearances to CombustiblesElectrical Supply VentilationGas Supply VentNational Standards and Applicable Codes High Altitude Temperature Rise and Pressure Drop Ranges Duct Heater Installation 5.1 GeneralAir Flow and Temperature Rise Ranges Minimum Inlet Duct LengthWall Mounting Shelf Mounting and SuspensionShelf-Mounting Methods Venting Vent InstallationChanging Vent and Air Intake Orientation United States RequirementsSeparated Combustion Heaters Models Uhdxsr 75 Standard Vented Heaters Models Uhdxr 75Unvented Operation Horizontal VentingVent Material Maximum Vent LengthsReplacing an Existing Heater in a Venting System Vent and Roof Detail Standard Vented Heater Common Vertical Vent Termination Concentric Vent Box UHVK1 Unvented Installation Separated Combustion InstallationAIR Supply Building VentilationConnections GAS PipingLow Voltage Thermostat with One Heater WiringPositioning Thermostats L2 L1 Internal Wiring DiagramFlue Blower Transformer GAS Valve Flame Sensor Electrode Ladder Wiring DiagramElectrical Connection to the Heater Begin Start-Up Before Operating the Heater Operation and MaintenancePre-Start-Up Checks Electrical ChecksEND View Check Gas Rate Pressure SwitchTurning Off the Heater External ControlsUser Instructions User InstructionsHeater Operation Lighting Instructions 11.4.1 To Turn On HeaterSimple Troubleshooting Burner Faults Simple TroubleshootingTo Turn Heater Off Servicing Vicinity of the Heater Maintenance ChecklistVehicles and Other ObjectsGas Line and Shut-off When installed DuctworkValves Burner ObservationTroubleshooting 13.1 General Conduct start-up procedure as shown on Page 23, Section Troubleshooting For Automatic Ignition Burner SystemsTroubleshooting for Flame Supervision System Troubleshooting for Flue Blower Troubleshooting for Gas ValvesBurner Components Replacement PartsBurner Injectors Burner CompartmentIgnition Electrode and Flame Probe Top, remove the blower and mounting plate as above Flue Blower Vertical InstallationIgnition Control Limit Switches Removal and ReplacementTOP View Specifications 15.1 Dimension DataTechnical Data Table General Technical Data TablePage Roberts Gordon will not PAY for Warranty is Void ifRoberts-Gordon Limitations on Authority RepresentativesPage Owner Warranty Registration Card Page Page Clearances to Combustibles