Toshiba RAS-10SA-E, RAS-10SKX, RAS-10SAX, RAS-10SK-E Indoor Unit Installation, Drainage

Page 27

8-4-5. Indoor Unit Installation

(1)Pass the pipe through the hole in the wall, and hook the indoor unit on the installation plate at the upper hooks.

(2)Swing the indoor unit to right and left to confirm that it is firmly hooked up on the installation plate.

(3)While pressing the indoor unit onto the wall by the lower part, hook it up on the installation plate by the lower part. Pull the indoor unit toward you by the lower part to confirm that it is firmly hooked up on the installation plate.

(1)

Hook here

1 Installation plate

(2)

Push

Hook

 

Fig. 8-4-15

For detaching the indoor unit from the installation plate pull the indoor unit toward you while pushing its bottom up by the specified parts.

8-4-6. Drainage

(1) Run the drain hose sloping downwards.

NOTE :

Hole should be made at a slight downward slant to the outdoor side.

Do not rise the drain hose.

Do not form the drain hose

 

into the wared shape.

50mm or more

Do not put the

Do not put the drain

drain hose end

hose end in the

into water.

drainage ditch.

Fig. 8-4-17

(2)Put water in the drain pan and make sure that the water is drained outdoors.

(3)When connecting extension drain hose, insulate the connecting part of extension drain hose with

5 shield pipe.

5 Shield pipe

Drain hose Inside the room

 

 

 

Extension drain hose

 

 

Fig. 8-4-18

Push Push

Fig. 8-4-16

CAUTION

Arrange the drain pipe for proper drainage from the unit.

Improper drainage can result in damage to property.

This air conditioner has the structure designed to drain water collected from dew, which forms on the back of the indoor unit, to the drain pan.

Therefore, do not store the power cord and other parts at a height above the drain guide.

Wall

Drain guide

Space for pipes

Fig. 8-4-19

– 27 –

Image 27
Contents R C O Contents Troubleshooting Flowcharts What to be Prechecked FirstPrimary Judgement of Trouble Sources RAS-10SK-E/10SA-E RAS-10SKX/10SAX Cooling SpecificationsCondition JIS C9612-1994 Temperature Cooling Indoor Unit Construction ViewsRAS-10SA-E RAS-10SAX Outdoor UnitMain P.C. Board Wiring DiagramParts name Type Specifications Specifications of Electrical PartsRAS-10SK-E / RAS-10SA-E RAS-10SKX / RAS-10SAX Refrigerant Cycle DiagramAUTO, COOL, DRY, FAN only MICRO-COMPUTER Block DiagramM3/h Operation DescriptionsFAN only Operation Cool OperationLouver Control DRY OperationTemporary Auto Auto OperationECONO. Mode Low-Temperature Limit Control Cooling OperationCooling Auto Restart Function How to Set the Auto RestartCase of Power Failure during the Timer Operation How to Cancel the Auto RestartSafety Cautions For general public use Installation ProcedureUK Plugs and Sockets etc Safety Regulations SI Number Attach Installation Diagram of Indoor and Outdoor UnitsInstallation Installation PartsOptional Parts Mounting the installation plate Installation placeCutting a Hole and Mounting Installation Plate Remote controlElectrical Work When the installation plate is directly mounted on the wallTaking out the power cord Wiring ConnectionHow to remove the front cabinet How to open the screw capHow to install the front cabinet on the indoor unit Stripping length of connecting cableLeft-hand connection with piping Piping and Drain Hose InstallationCase of rightward piping Case of downward pipingDrainage Indoor Unit InstallationStrong wind Tightening connection Refrigerant Piping ConnectionVacuum Pumping FlaringA5 mm hexagon wrench is required Packed Valve Handling PrecautionsGas Leak Test Auto Restart SettingHow to set the Auto Restart OthersIncorrect Cable Connection between Indoor and Outdoor Units Troubleshooting ChartPower Supply Voltage What to be Prechecked FirstOperation of air-conditioner Description Misleading but Good Operations Program Controlled OperationPrimary Judgement of Trouble Sources Role of Indoor Unit ControllerBlock display Selecting ordinary mode Self-diagnosis with remote controlOperating key Indication after operation Self-diagnosis by check codesCondition Code Status Troubleshooting Flowcharts Power can not be Turned on No Operation at AllPreliminary checks Power can not be Turned on after Replacing Indoor PC Board Checking ProcedureOutdoor Unit does not Operate Only Compressor does not Operate Only Outdoor Fan does not Operate Only the Indoor Fan does not Operate Check procedureThere is no beep from Main PC board part How to Check the PC BoardOperating precautions Inspection proceduresProcedure Check Point Symptom Causes Top View Bottom View PC Board LayoutSensor How to Reduce the Operation Time of the Anti-Restart TimerIndoor Unit RAS-10SK-E, RAS-10SKX Part ReplacementPart name Procedure Remarks Microcomputer RAS-10SK-E, RAS-10SKX Outdoor Unit RAS-10SA-E, RAS-10SAX OFF Part Description Exploded Views and Parts ListIndoor Unit Capillary Tube