| Table |
|
|
|
Block level |
| Diagnosis function |
|
|
| ||
Check |
| Check |
| Air |
|
| Judgment and action |
Block | Symptom | Conditioner | Condition |
|
| ||
code | code |
|
| ||||
|
| status |
|
|
| ||
|
|
|
|
|
|
| |
| Indoor PC |
| Thermo sensor | Continued | Indicated when | 1. Check thermo sensor. | |
| board |
| short/break. | operation | detected abnormal | 2. | If it is OK, check PC board. |
|
|
| Heat exchanger | Continued | Indicated when | 1. | Check heat exchanger |
|
|
| sensor short/break. | operation | detected abnormal |
| sensor. |
|
|
|
|
|
| 2. | If it is OK, check PC board. |
|
|
| Indoor fan lock, | All off | Indicated when | 1. | Disconnect the power plug |
|
|
| abnormality of |
| detected abnormal |
| from AC outlet, and pull out |
|
|
| indoor fan. |
|
|
| the connector (CN10) for the |
|
|
|
|
|
|
| motor, then connect the plug |
|
|
|
|
|
|
| of AC power cord again and |
|
|
|
|
|
|
| turn the power on. |
|
|
|
|
|
| 2. Check the voltage between | |
|
|
|
|
|
|
| pin 1 and 2 of the connector |
|
|
|
|
|
|
| (CN10). |
|
|
|
|
|
| 3. | If the output voltage is 35V, |
|
|
|
|
|
|
| PC board is OK, check |
|
|
|
|
|
|
| motor. |
|
|
| Abnormality of | All off | Indicated when | Replace PC board. | |
|
|
| other indoor unit PC |
| detected abnormal |
|
|
|
|
| board. |
|
|
|
|
| Refrigerant |
| 1) Gas shortage. | All off | Indicated when | 1. | Check gas quantity. |
| system |
| (gas leak) |
| detected abnormal |
| (check gas leakage) |
|
|
|
|
|
|
| |
|
|
| 2) Other refrigerant |
|
| 2. | If it is OK, check heat |
|
|
| cycle trouble. |
|
| ||
|
|
|
|
|
| exchanger sensor. | |
|
|
|
|
|
|
| |
|
|
| 3) Heat exchanger |
|
| 3. | If heat exchenger sensor is |
|
|
| sensor off/break/ |
|
| ||
|
|
|
|
|
| OK. check overload relay and | |
|
|
| short. |
|
|
| |
|
|
|
|
|
| thermostat for compressor. | |
|
|
|
|
|
|
| |
|
|
| 4) Overload relay |
|
| 4. | If overload relay is OK, check |
|
|
|
|
|
| ||
|
|
|
|
|
|
| refrigerant cycle. |
|
|
|
|
|
| 5. | If refrigerant cycle is OK, |
|
|
|
|
|
|
| check PC board. |
Contents detected by the check codes “ ” to “ ” are stored in memory of the microcomputer even if the power supply is turned off. Therefore, contents of operations in the past are all displayed.