9-3-6. Only the Indoor Fan does not Operate

< Check procedure >

Shut off the power supply once.

Turn the power supply.

Does the fan

NO

 

 

 

 

 

 

stop in no operating

Control PC board is defective.

 

 

 

Replace the PC board.

 

 

 

 

 

 

 

status?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Start the operation with low fan setting in cool operation.

Does the fan rotate?

YES

 

Is the voltage

 

Shut off the power supply,

 

measured DC35V

 

NO

NO

and turn it on after

between 1 (red lead wire, +)

disconnecting the motor

 

and 2 (black lead wire, –)

 

 

 

connector (CN10)* from

 

of the motor connector

 

 

(CN10) ?

 

the PC board.

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

Shut off the power supply.

Change the setting of

 

 

 

 

 

Does the cross

 

 

 

cooling to high fan.

 

NO

 

 

 

flow fan rotate

 

 

 

 

 

 

 

 

 

 

 

 

normally?

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn on the power supply.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Does the fan speed NO

Operation

 

 

 

 

become higher?

 

stops

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

Is the rotation signal

 

 

 

 

 

 

(DC+5V-0V) output between 4

 

 

 

(blue lead wire) and 2

(black

 

 

 

lead wire) of the motor connector

 

 

 

(CN10) when rotating the cross

 

 

 

flow fan by hand in no operating

 

 

 

status ? (2 pulses/one turn)

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Repair the bearing of the drain fan.

Is the voltage of DC35V measured

between 1 (red lead wire, +) NO and 2 (black lead wire, –) of

the motor connector (CN10) ?

YES

NO

Replace the PC board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace the control

 

 

 

Replace the

 

 

Normal

 

 

 

 

 

 

 

 

 

 

 

PC board.

 

 

 

fan motor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of damage of the motor.

– 42 –

Image 42
Contents R C O Contents Troubleshooting Flowcharts What to be Prechecked FirstPrimary Judgement of Trouble Sources Specifications RAS-10SK-E/10SA-E RAS-10SKX/10SAX CoolingCondition JIS C9612-1994 Temperature Cooling Construction Views Indoor UnitOutdoor Unit RAS-10SA-E RAS-10SAXWiring Diagram Main P.C. BoardSpecifications of Electrical Parts Parts name Type SpecificationsRefrigerant Cycle Diagram RAS-10SK-E / RAS-10SA-E RAS-10SKX / RAS-10SAXMICRO-COMPUTER Block Diagram AUTO, COOL, DRY, FAN onlyCool Operation Operation DescriptionsFAN only Operation M3/hDRY Operation Louver ControlAuto Operation Temporary AutoECONO. Mode Low-Temperature Limit Control Cooling OperationCooling How to Set the Auto Restart Auto Restart FunctionHow to Cancel the Auto Restart Case of Power Failure during the Timer OperationInstallation Procedure Safety Cautions For general public useUK Plugs and Sockets etc Safety Regulations SI Number Installation Diagram of Indoor and Outdoor Units AttachInstallation Installation PartsOptional Parts Remote control Installation placeCutting a Hole and Mounting Installation Plate Mounting the installation plateWhen the installation plate is directly mounted on the wall Electrical WorkHow to open the screw cap Wiring ConnectionHow to remove the front cabinet Taking out the power cordStripping length of connecting cable How to install the front cabinet on the indoor unitCase of downward piping Piping and Drain Hose InstallationCase of rightward piping Left-hand connection with pipingIndoor Unit Installation DrainageStrong wind Flaring Refrigerant Piping ConnectionVacuum Pumping Tightening connectionPacked Valve Handling Precautions A5 mm hexagon wrench is requiredOthers Auto Restart SettingHow to set the Auto Restart Gas Leak TestWhat to be Prechecked First Troubleshooting ChartPower Supply Voltage Incorrect Cable Connection between Indoor and Outdoor UnitsMisleading but Good Operations Program Controlled Operation Operation of air-conditioner DescriptionPrimary Judgement of Trouble Sources Role of Indoor Unit ControllerBlock display Self-diagnosis with remote control Selecting ordinary modeSelf-diagnosis by check codes Operating key Indication after operationCondition Code Status Troubleshooting Flowcharts Power can not be Turned on No Operation at AllPreliminary checks Power can not be Turned on after Replacing Indoor PC Board Checking ProcedureOutdoor Unit does not Operate Only Compressor does not Operate Only Outdoor Fan does not Operate Check procedure Only the Indoor Fan does not OperateThere is no beep from Inspection procedures How to Check the PC BoardOperating precautions Main PC board partProcedure Check Point Symptom Causes PC Board Layout Top View Bottom ViewHow to Reduce the Operation Time of the Anti-Restart Timer SensorPart Replacement Indoor Unit RAS-10SK-E, RAS-10SKXPart name Procedure Remarks Microcomputer RAS-10SK-E, RAS-10SKX Outdoor Unit RAS-10SA-E, RAS-10SAX OFF Exploded Views and Parts List Part DescriptionIndoor Unit Capillary Tube