9. TROUBLESHOOTING CHART

TROUBLESHOOTING PROCEDURES :

Following details of “What to be pre-checked first”, make sure of the basic items.

When there is no trouble corresponding to above, check in detail the faulty parts following “How to judge faulty parts by symptoms” later.

9-1. What to be Prechecked First

9-1-1. Power Supply Voltage

The line voltage must be AC 220/230/240V. If the line voltage is not within this range, this air conditioner may not work normally.

9-1-2. Incorrect Cable Connection between Indoor and Outdoor Units

The indoor unit is connected to the outdoor unit with 3 cables. Make certain that the indoor and outdoor units have been connected properly, with terminals assigned the same numbers wired to each other. If the connec- tors are not connected as specified, the outdoor unit will not operate normally.

– 32 –

Image 32
Contents R C O Contents Primary Judgement of Trouble Sources Troubleshooting FlowchartsWhat to be Prechecked First Specifications RAS-10SK-E/10SA-E RAS-10SKX/10SAX CoolingCondition JIS C9612-1994 Temperature Cooling Construction Views Indoor UnitOutdoor Unit RAS-10SA-E RAS-10SAXWiring Diagram Main P.C. BoardSpecifications of Electrical Parts Parts name Type SpecificationsRefrigerant Cycle Diagram RAS-10SK-E / RAS-10SA-E RAS-10SKX / RAS-10SAXMICRO-COMPUTER Block Diagram AUTO, COOL, DRY, FAN onlyOperation Descriptions FAN only OperationCool Operation M3/hDRY Operation Louver ControlAuto Operation Temporary AutoCooling ECONO. ModeLow-Temperature Limit Control Cooling Operation How to Set the Auto Restart Auto Restart FunctionHow to Cancel the Auto Restart Case of Power Failure during the Timer OperationInstallation Procedure Safety Cautions For general public useUK Plugs and Sockets etc Safety Regulations SI Number Installation Diagram of Indoor and Outdoor Units AttachOptional Parts InstallationInstallation Parts Installation place Cutting a Hole and Mounting Installation PlateRemote control Mounting the installation plateWhen the installation plate is directly mounted on the wall Electrical WorkWiring Connection How to remove the front cabinetHow to open the screw cap Taking out the power cordStripping length of connecting cable How to install the front cabinet on the indoor unitPiping and Drain Hose Installation Case of rightward pipingCase of downward piping Left-hand connection with pipingIndoor Unit Installation DrainageStrong wind Refrigerant Piping Connection Vacuum PumpingFlaring Tightening connectionPacked Valve Handling Precautions A5 mm hexagon wrench is requiredAuto Restart Setting How to set the Auto RestartOthers Gas Leak TestTroubleshooting Chart Power Supply VoltageWhat to be Prechecked First Incorrect Cable Connection between Indoor and Outdoor UnitsMisleading but Good Operations Program Controlled Operation Operation of air-conditioner DescriptionBlock display Primary Judgement of Trouble SourcesRole of Indoor Unit Controller Self-diagnosis with remote control Selecting ordinary modeSelf-diagnosis by check codes Operating key Indication after operationCondition Code Status Preliminary checks Troubleshooting FlowchartsPower can not be Turned on No Operation at All Outdoor Unit does not Operate Power can not be Turned on after Replacing Indoor PC BoardChecking Procedure Only Compressor does not Operate Only Outdoor Fan does not Operate Check procedure Only the Indoor Fan does not OperateThere is no beep from How to Check the PC Board Operating precautionsInspection procedures Main PC board partProcedure Check Point Symptom Causes PC Board Layout Top View Bottom ViewHow to Reduce the Operation Time of the Anti-Restart Timer SensorPart Replacement Indoor Unit RAS-10SK-E, RAS-10SKXPart name Procedure Remarks Microcomputer RAS-10SK-E, RAS-10SKX Outdoor Unit RAS-10SA-E, RAS-10SAX OFF Exploded Views and Parts List Part DescriptionIndoor Unit Capillary Tube