Toshiba RAS-10SAX Refrigerant Piping Connection, Vacuum Pumping, Flaring, Tightening connection

Page 29

8-5-1. Refrigerant Piping Connection

<Flaring>

(1) Cut the pipe with a pipe cutter.

90˚

Obliquity Roughness

Warp

Fig. 8-5-2

(2) Insert a flare nut into the pipe, and flare the pipe.

 

 

A

Outer

A (mm)

 

 

 

 

 

diam.

Imperial Rigid

 

 

 

 

 

 

 

 

 

 

6.35 mm 1.3 mm 0.7 mm

Die

Pipe

 

9.52 mm 1.6 mm 1.0 mm

Fig. 8-5-3

<Tightening connection>

Align the centers of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.

CAUTION

Do not apply excess torque. Otherwise, the nut may crack depending on the installation conditions.

(Unit : N·m)

Outer diam.

Tightening torque

Additional

tightening torque

 

 

 

 

 

6.35 mm

15.7 (1.6 kgf·m)

19.6 (2.0 kgf·m)

 

 

 

9.52 mm

29.4 (3.0 kgf·m)

34.3 (3.5 kgf·m)

8-5-2. Vacuum Pumping

AIR PURGE

Evacuate the air in the connecting pipes and in the indoor unit using vacuum pump.

Do not use the refrigerant in the outdoor unit.

For details, see the manual of vacuum pump.

<Use of vacuum pump>

(1)Connect the charge hose (A) from the manifold valve to the charge inlet of the gas side packed valve.

(2)Connect the charge hose (B) to the port of vacuum pump.

(3)Open fully the low pressure side handle of the manifold valve.

(4)Operate the vacuum pump.

(5)Close the low pressure side handle of manifold valve after vacuumizing and stop the vacuum pump.

Continue vacuumizing more than 15 minutes and check the pressure gauge indicates –76 cmHg (–1.013×105Pa).

(6)Open the stems of packed valves A and B all the way.

(7)Securely tighten the stem cap to each of the packed valve stems.

 

Manifold valve

Pressure gage

High pressure

side handle

 

Low pressure side handle

 

Charge hose (A)

Lo Hi

Outdoor unit

Half union or packed valve

Flare nut

Externally

Internally

threaded

threaded

side

side

Use a wrench

Use a torque wrench

to secure.

to tighten.

Indoor unit

 

Gas

 

 

(ø9.52)

 

C

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid

 

 

(ø6.35 )

Charge

hose (B)

Service port

VP

Packed valve

Fig. 8-5-4

Fig. 8-5-5

– 29 –

Image 29
Contents R C O Contents Primary Judgement of Trouble Sources Troubleshooting FlowchartsWhat to be Prechecked First RAS-10SK-E/10SA-E RAS-10SKX/10SAX Cooling SpecificationsCondition JIS C9612-1994 Temperature Cooling Indoor Unit Construction ViewsRAS-10SA-E RAS-10SAX Outdoor UnitMain P.C. Board Wiring DiagramParts name Type Specifications Specifications of Electrical PartsRAS-10SK-E / RAS-10SA-E RAS-10SKX / RAS-10SAX Refrigerant Cycle DiagramAUTO, COOL, DRY, FAN only MICRO-COMPUTER Block DiagramFAN only Operation Operation DescriptionsCool Operation M3/hLouver Control DRY OperationTemporary Auto Auto OperationCooling ECONO. ModeLow-Temperature Limit Control Cooling Operation Auto Restart Function How to Set the Auto RestartCase of Power Failure during the Timer Operation How to Cancel the Auto RestartSafety Cautions For general public use Installation ProcedureUK Plugs and Sockets etc Safety Regulations SI Number Attach Installation Diagram of Indoor and Outdoor UnitsOptional Parts InstallationInstallation Parts Cutting a Hole and Mounting Installation Plate Installation placeRemote control Mounting the installation plateElectrical Work When the installation plate is directly mounted on the wallHow to remove the front cabinet Wiring ConnectionHow to open the screw cap Taking out the power cordHow to install the front cabinet on the indoor unit Stripping length of connecting cableCase of rightward piping Piping and Drain Hose InstallationCase of downward piping Left-hand connection with pipingDrainage Indoor Unit InstallationStrong wind Vacuum Pumping Refrigerant Piping ConnectionFlaring Tightening connectionA5 mm hexagon wrench is required Packed Valve Handling PrecautionsHow to set the Auto Restart Auto Restart SettingOthers Gas Leak TestPower Supply Voltage Troubleshooting ChartWhat to be Prechecked First Incorrect Cable Connection between Indoor and Outdoor UnitsOperation of air-conditioner Description Misleading but Good Operations Program Controlled OperationBlock display Primary Judgement of Trouble SourcesRole of Indoor Unit Controller Selecting ordinary mode Self-diagnosis with remote controlOperating key Indication after operation Self-diagnosis by check codesCondition Code Status Preliminary checks Troubleshooting FlowchartsPower can not be Turned on No Operation at All Outdoor Unit does not Operate Power can not be Turned on after Replacing Indoor PC BoardChecking Procedure Only Compressor does not Operate Only Outdoor Fan does not Operate Only the Indoor Fan does not Operate Check procedureThere is no beep from Operating precautions How to Check the PC BoardInspection procedures Main PC board partProcedure Check Point Symptom Causes Top View Bottom View PC Board LayoutSensor How to Reduce the Operation Time of the Anti-Restart TimerIndoor Unit RAS-10SK-E, RAS-10SKX Part ReplacementPart name Procedure Remarks Microcomputer RAS-10SK-E, RAS-10SKX Outdoor Unit RAS-10SA-E, RAS-10SAX OFF Part Description Exploded Views and Parts ListIndoor Unit Capillary Tube