6-2. Operation Data
<Cooling>
Temperature condition (°C)
Indoor Outdoor
27/19 | 35/– |
| Standard | Heat exchanger |
| ||
| pipe temp. | Indoor fan | |||
Model name | pressure | ||||
|
| mode | |||
| P (MPa) | T1 (°C) | T2 (°C) | ||
|
| ||||
|
|
| |||
|
|
|
|
| |
0,8 to 1,0 | 9 to 11 | 42 to 44 | High | ||
|
|
|
|
| |
0,8 to 1,0 | 8 to 10 | 46 to 48 | High | ||
|
|
|
|
|
Outdoor fan | Compressor | |
revolution | ||
mode | ||
(rps) | ||
| ||
High | 56 | |
|
| |
High | 85 | |
|
|
<Heating>
Temperature condition (°C)
Indoor | Outdoor | |
|
| |
20/– | 7/6 | |
|
|
| Standard | Heat exchanger |
|
| ||
| pipe temp. | Indoor fan | Outdoor fan | |||
Model name | pressure | |||||
|
| mode | mode | |||
| P (MPa) | T1 (°C) | T2 (°C) | |||
|
|
| ||||
|
|
|
| |||
|
|
|
|
|
| |
3,5 to 3,7 | 42 to 44 | 2 to 4 | High | High | ||
|
|
|
|
|
| |
2,5 to 2,7 | 50 to 52 | 0 to 3 | High | High | ||
|
|
|
|
|
|
Compressor
revolution
(rps)
70
97
NOTES :
(1)Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent. (Thermistor themometer)
(2)Connecting piping condition : 5 m
– 20 –