Toshiba RAS-10YAV-E, RAS-13YKV-E Refrigerant R410A, Safety During Installation/Servicing

Page 6

2. REFRIGERANT R410A

This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.

The working pressure of the new refrigerant R410A is 1,6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refrigerat- ing oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.

The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.

2-1. Safety During Installation/Servicing

As R410A’s pressure is about 1,6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materi- als exclusive for R410A, it is necessary to carry out installation/servicing safely while taking the following precautions into consideration.

(1)Never use refrigerant other than R410A in an air conditioner which is designed to operate with R410A.

If other refrigerant than R410A is mixed, pres- sure in the refrigeration cycle becomes abnor- mally high, and it may cause personal injury, etc. by a rupture.

(2)Confirm the used refrigerant name, and use tools and materials exclusive for the refrigerant R410A.

The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air condi- tioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22.

(3)If a refrigeration gas leakage occurs during installation/servicing, be sure to ventilate fully.

If the refrigerant gas comes into contact with fire, a poisonous gas may occur.

(4)When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture or personal injury may be caused.

(5)After completion of installation work, check to make sure that there is no refrigeration gas leakage.

If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.

(6)When an air conditioning system charged with a large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level.

If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.

(7)Be sure to carry out installation or removal according to the installation manual.

Improper installation may cause refrigeration trouble, water leakage, electric shock, fire, etc.

(8)Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.

Improper repair’s may result in water leakage, electric shock and fire, etc.

2-2. Refrigerant Piping Installation

2-2-1. Piping Materials and Joints Used

For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.

(1)Copper Pipes

It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discol- ored portion (especially on the interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants.

As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials.

Thicknesses of copper pipes used with R410A are as shown in Table 2-2-1. Never use copper pipes thinner than 0,8 mm even when it is available on the market.

– 6 –

Image 6
Contents AIR-CONDITIONER Contents Specifications SpecificationsRAS-10YKV-E/RAS-10YAV-E RAS-13YKV-E/RAS-13YAV-E RAS-13YKV-ECooling Heating Operation Characteristic CurveCapacity Variation Ratio According to Temperature CoolingRefrigerant R410A Safety During Installation/ServicingRefrigerant Piping Installation Piping Materials and Joints UsedOuter diameter mm R410A R22 Processing of Piping Materials1 Thicknesses of annealed copper pipes Thickness mm Nominal diameter5 Flare and flare nut dimensions for R410A 3 Dimensions related to flare processing for R410A Outer4 Dimensions related to flare processing for R22 Outer Outer Thickness Dimension mmNm kgfcm Wrenches available on the marketRequired Tools R410A air conditioner Conventional air InstallationTools General tools Conventional tools can be used1 Configuration of refrigerant charging Recharging of RefrigerantBrazing of Pipes Materials for BrazingFlux Brazing Never use gas other than Nitrogen gasConstruction Views Indoor UnitRAS-10YKV-E, RAS-13YKV-E Outdoor Unit RAS-10YAV-E RAS-13YAV-EWiring Diagram 1 Simple check points for diagnosing faultsCheck items Diagnosis result RAS-10YAV-E, RAS-13YAV-E V. Pulse Modulating ValveSpecifications of Electrical Parts Parts name Type SpecificationsParts name Model name Rating Refrigerant Cycle Diagram Refrigerant Cycle DiagramRAS-10YKV-E/RAS-10YAV-E RAS-13YKV-E/RAS-13YAV-E Operation Data CoolingHeating Control Block Diagram Remote ControllerAssembly RASMCC808 P.C.B Operation Description Outline of Air Conditioner ControlCurrent Release Control Power Factor Improvement ControlCapacity Control 1 Compressor revolution rangeLouver Control Prevent-Freezing Control5. P. M. V. Pulse Modulating Valve Indoor Fan Control DC Fan MotorCOOL, DRY Description of Operation CircuitOutdoor Fan Control DC Fan Motor HeatOutdoor temperature release control Prevent-freezing controlCurrent release control Rps Louver control5 Setting of air flow ECONO. operation controlStarting and in stability Heating OperationBasic control Cold draft preventing controlDefrost control Temporary Auto Operation Temporary OperationAutomatic Operation Temporary Cooling OperationHow to Set the Auto Restart Auto Restart FunctionOperation Motion How to Cancel the Auto Restart Case of Power Failure during the Timer OperationName of Indications on Remote Controller Remote ControllerParts Name of Remote Controller START/STOP buttonInstallation Procedure Safety CautionsRemark per EMC Directive 89/336/EEC Optional Installation Parts Indoor UnitElectrical Work Outdoor Unit Refrigerant Piping ConnectionConfirmation of Power Voltage HOW to Diagnose the TroubleConfirmation of Power Supply First ConfirmationPrimary Judgment Operation Which is not a Trouble Program OperationOperation of air conditioner Description Judgment by Flashing LED of Indoor Unit Check Block display Description for self-diagnosis CodeSelf-Diagnosis Self-Diagnosis by Remote Controller Check CodeOperation Control by Rated Frequency in Service Mode ButtonBlock distinction Check outdoor heat exchanger temp Confirmation procedure Judgment of Trouble by Every SymptomIndoor Unit Including Remote Controller Power is not turned on Does not operate entirelyOnly the indoor fan does not operate YESCause How to examine whether remote controller is good or bad Wiring Failure Interconnecting and Serial Signal Wire Check procedure Select phenomena described belowOutdoor unit does not operate Check Code 1C Miswiring in indoor/outdoor units and 1E Check procedureHow to Diagnose Trouble in Outdoor Unit Summarized Inner Diagnosis of Inverter AssemblyDiagnosis/Process flowchart Contents Summary Operating precautions How to Check Simply the Main PartsHow to Check the P.C. Board Indoor Unit Inspection proceduresCheck procedures Procedure Check point Symptom CausesSensor characteristic table 10-8-2. P.C. Board LayoutBottom View Outdoor Unit Part name Checking procedureIndoor Unit Other Parts Position Resistance valueChecking Method for Each Part Case that product is goodHow to Simply Judge Whether Outdoor Fan Motor is Good or Bad Symptom11-1 Indoor Unit HOW to Replace the Main PartsPart name Procedure Remarks To assemble the front panelRemoving Louver motor Microcomputer Board layoutNo. Part name Procedure Remarks DetachmentAttachment Bundled Be careful to check the inverter becauseHigh-voltage circuit is incorporated in it PartLead wires Propeller Flange nut is loosened by turning clockwise Check that coil at B room side Red Pulse modulating valve has a roomSide and B room side. After mounting it Perform work on a corrugated cardboardPart name Procedure Remarks Parts name Qty RemarksMCC-808 Exploded Views and Parts List Part DescriptionLocation Part Description 222 43T49023 Holder of Plate of EVA-SEAL 11, 13 12 24, 25 26, 27 12-3. P.C. Board Layout Toshiba Carrier Corporation Turn 208 10YKV-E 221 Cushion, Rubber Valve, 4-way To Sensor Ø6