Toshiba RAS-13YKV-E, RAS-10YKV-E, RAS-10YAV-E, RAS-13YAV-E service manual Rps, Louver control

Page 28

(5)Limit for maximum compressor motor speed by indoor fan speed

When outdoor temperature sensor detected 32°C or lower, and indoor heat exchanger sensor detected 17°C or lower, the maximum compressor motor speed is limited by the indoor fan speed.

For example, the compressor motor speed is limited as described in the table below.

Table 8-2-1

Air flow rate

RAS-10YKV-E

RAS-13YKV-E

(rps)

(rps)

 

 

 

 

HIGH

56

85

 

 

 

M+

49

71

 

 

 

MED.

43

57

 

 

 

L–, L

36

44

 

 

 

UL, SUL

30

30

 

 

 

(6)Louver control

The vertical air flow louvers are automatically set to horizontal or cool memory position.

When temperature of indoor heat exchanger becomes 5°C or lower by the prevent-freezing control and the compressor is turned off, the vertical air flow louvers close once and then return to the position of previous time.

(7)Discharge temperature control

(Common control to cooling and heating)

The discharge temperature of refrigerant gas from the compressor is detected by the dis- charge temperature sensor, and controls operat- ing compressor motor speed.

1)Control 1 (A zone) : Normal operation zone

When TD detect value is 98°C or lower, the operation is performed with operating motor speed instructed by the serial signal.

2)Control 2 (B zone) : Slow-up zone of motor speed

When TD detect value is 98°C or higher, operating motor speed is slowly up.

3)Control 3 (C zone) : Keep zone

When TD detect value is 105°C or higher, operating motor speed is not changed if raising operation speed.

4)Control 4 (D zone) : Slow down zone of motor speed

When TD detect value is 108°C or higher, operating motor speed is slowly down.

5)Control 5 (E zone) : Normal down of motor speed

When TD detect value is 112°C or higher, operating motor speed is down.

6)Control 6 (F zone) : Operation stop zone

If TD detect value exceeds 117°C during operation, stop the operation immediately.

Then, restart the operation when TD detect value becomes 105°C or lower.

TD (˚C)

117

112

108

105

98

Zone

 

F

Operation stop zone

 

 

E

Normal down zone of motor speed

 

Release of motor speed

 

D

Slow down of motor speed

 

 

C

Keep zone : Motor speed is not changed.

 

 

B

Slow-up zone of motor speed

A

Normal operation zone

Fig. 8-2-3 Compressor motor speed control

– 28 –

Image 28
Contents AIR-CONDITIONER Contents Specifications SpecificationsRAS-10YKV-E/RAS-10YAV-E RAS-13YKV-E/RAS-13YAV-E RAS-13YKV-EOperation Characteristic Curve Capacity Variation Ratio According to TemperatureCooling Heating CoolingSafety During Installation/Servicing Refrigerant Piping InstallationRefrigerant R410A Piping Materials and Joints UsedProcessing of Piping Materials 1 Thicknesses of annealed copper pipes Thickness mmOuter diameter mm R410A R22 Nominal diameter3 Dimensions related to flare processing for R410A Outer 4 Dimensions related to flare processing for R22 Outer5 Flare and flare nut dimensions for R410A Outer Thickness Dimension mmNm kgfcm Wrenches available on the marketR410A air conditioner Conventional air Installation ToolsRequired Tools General tools Conventional tools can be used1 Configuration of refrigerant charging Recharging of RefrigerantMaterials for Brazing Brazing of PipesFlux Brazing Never use gas other than Nitrogen gasIndoor Unit Construction ViewsRAS-10YKV-E, RAS-13YKV-E Outdoor Unit RAS-10YAV-E RAS-13YAV-E1 Simple check points for diagnosing faults Wiring DiagramCheck items Diagnosis result RAS-10YAV-E, RAS-13YAV-E V. Pulse Modulating ValveParts name Type Specifications Specifications of Electrical PartsParts name Model name Rating Refrigerant Cycle Diagram Refrigerant Cycle DiagramRAS-10YKV-E/RAS-10YAV-E RAS-13YKV-E/RAS-13YAV-E Cooling Operation DataHeating Control Block Diagram Remote ControllerRAS AssemblyMCC808 P.C.B Operation Description Outline of Air Conditioner ControlPower Factor Improvement Control Capacity ControlCurrent Release Control 1 Compressor revolution rangePrevent-Freezing Control 5. P. M. V. Pulse Modulating ValveLouver Control Indoor Fan Control DC Fan MotorDescription of Operation Circuit Outdoor Fan Control DC Fan MotorCOOL, DRY HeatPrevent-freezing control Outdoor temperature release controlCurrent release control Rps Louver control5 Setting of air flow ECONO. operation controlHeating Operation Basic controlStarting and in stability Cold draft preventing controlDefrost control Temporary Operation Automatic OperationTemporary Auto Operation Temporary Cooling OperationAuto Restart Function How to Set the Auto RestartOperation Motion How to Cancel the Auto Restart Case of Power Failure during the Timer OperationRemote Controller Parts Name of Remote ControllerName of Indications on Remote Controller START/STOP buttonSafety Cautions Installation ProcedureRemark per EMC Directive 89/336/EEC Optional Installation Parts Indoor UnitElectrical Work Outdoor Unit Refrigerant Piping ConnectionHOW to Diagnose the Trouble Confirmation of Power SupplyConfirmation of Power Voltage First ConfirmationOperation Which is not a Trouble Program Operation Primary JudgmentOperation of air conditioner Description Judgment by Flashing LED of Indoor Unit Check Block display Description for self-diagnosis CodeSelf-Diagnosis by Remote Controller Check Code Operation Control by Rated Frequency in Service ModeSelf-Diagnosis ButtonBlock distinction Check outdoor heat exchanger temp Judgment of Trouble by Every Symptom Indoor Unit Including Remote ControllerConfirmation procedure Power is not turned on Does not operate entirelyOnly the indoor fan does not operate YESCause How to examine whether remote controller is good or bad Check procedure Select phenomena described below Wiring Failure Interconnecting and Serial Signal WireOutdoor unit does not operate Check Code 1C Miswiring in indoor/outdoor units and 1E Check procedureSummarized Inner Diagnosis of Inverter Assembly How to Diagnose Trouble in Outdoor UnitDiagnosis/Process flowchart Contents Summary How to Check Simply the Main Parts How to Check the P.C. Board Indoor UnitOperating precautions Inspection proceduresCheck procedures Procedure Check point Symptom Causes10-8-2. P.C. Board Layout Sensor characteristic tableBottom View Part name Checking procedure Indoor Unit Other PartsOutdoor Unit Position Resistance valueChecking Method for Each Part Case that product is goodHow to Simply Judge Whether Outdoor Fan Motor is Good or Bad SymptomHOW to Replace the Main Parts Part name Procedure Remarks11-1 Indoor Unit To assemble the front panelRemoving Louver motor Microcomputer Board layoutDetachment No. Part name Procedure RemarksAttachment Be careful to check the inverter because High-voltage circuit is incorporated in itBundled PartLead wires Propeller Flange nut is loosened by turning clockwise Pulse modulating valve has a room Side and B room side. After mounting itCheck that coil at B room side Red Perform work on a corrugated cardboardPart name Procedure Remarks Parts name Qty RemarksMCC-808 Part Description Exploded Views and Parts ListLocation Part Description 222 43T49023 Holder of Plate of EVA-SEAL 11, 13 12 24, 25 26, 27 12-3. P.C. Board Layout Toshiba Carrier Corporation Turn 208 10YKV-E 221 Cushion, Rubber Valve, 4-way To Sensor Ø6