8-2-4. Automatic Operation

(1)As shown in Fig. 8-2-9, the operation mode (COOL, DRY, HEAT) is selected according to the outside temperature and room temperature when the operation has started.

The operation in Fan mode continues until an operation mode is selected.

If the room temperature is 20°C or higher when “AUTO” operation started within 2 hours after “HEAT” operation had stopped, select an opera- tion mode after Fan operation of ultra low fan.

In AUTO operation, the set temperature of each operation can be corrected by the remote controller in the range of 17 to 30°C.

(2)After selecting the operation mode (COOL, DRY, HEAT), select an operation mode again when a status that the compressor was turned off by the room temperature or outside air temperature continues for 15 minutes.

(3)Powerful Cool mode control

When the outside temperature is above 32°C and indoor temperature is above 28°C, select Cool mode control. In Cool mode, the air flow louver directs downward. When the room tem- perature gains access to the set temperature, it becomes cool memory position.

TA

28

26

24

23

20

Heating with setting on remote controller Ts = 25˚C

Powerful Cooling/Drying with setting on remote controller Ts = 25˚C

Cooling/Drying with setting on remote controller Ts = 25˚C

Monitoring

(Follow to the Fan control in previous mode when being selected again.)

Ts correction by outside temperature (To)

5

15 18

24

32

To

–2

 

–1

 

 

0

 

+1

Fig. 8-2-9

8-3. Temporary Operation

8-3-1. Temporary Auto Operation

Temporary Auto operation, existence of Auto Restart, and Temporary Cooling operation can be set by the TEMPORARY button of the indoor controller.

 

 

 

 

 

 

 

 

 

 

TEMPORARY

 

 

 

 

 

 

 

 

 

 

button

 

 

 

 

 

 

 

 

 

 

 

 

 

TEMPORARY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 8-3-1

 

 

 

 

 

 

 

 

 

 

 

TEMPORARY button

 

 

 

 

 

 

 

 

 

Control

 

 

OFF ON

Temporary Auto operation start

After pushing button

 

Auto Restart control select

for 3 seconds

 

 

 

 

 

 

 

 

 

 

 

After pushing button

 

 

 

 

 

 

 

 

Temporary Cooling

for 10 seconds

 

 

 

 

 

 

 

 

 

operation start

 

 

 

 

 

 

 

 

 

 

 

When the TEMPORARY button is pushed, the Auto operation with set temperature fixed at 25°C starts. Controlling is same as that of Auto opera- tion by the remote controller.

When the TEMPORARY button is pushed again, the operation stops.

During Temporary Auto operation, operation by the remote controller is accepted.

Using the Auto Restart function, the Temporary Auto operation starts when power failure is reset.

8-3-2. Temporary Cooling Operation

When the TEMPORARY operation button keeps pushed for 10 seconds, Cooling operation of which compressor motor speed and the indoor fan speed are fixed starts.

Compressor motor speed : 10 : 30 rps

13 : 30 rps

Indoor fan speed : Low

When the TEMPORARY operation button is pushed again, the operation stops.

Auto Restart function is unavailable.

– 32 –

Image 32
Contents AIR-CONDITIONER Contents RAS-10YKV-E/RAS-10YAV-E SpecificationsSpecifications RAS-13YKV-E/RAS-13YAV-E RAS-13YKV-EOperation Characteristic Curve Capacity Variation Ratio According to TemperatureCooling Heating CoolingSafety During Installation/Servicing Refrigerant Piping InstallationRefrigerant R410A Piping Materials and Joints UsedProcessing of Piping Materials 1 Thicknesses of annealed copper pipes Thickness mmOuter diameter mm R410A R22 Nominal diameter3 Dimensions related to flare processing for R410A Outer 4 Dimensions related to flare processing for R22 Outer5 Flare and flare nut dimensions for R410A Outer Thickness Dimension mmNm kgfcm Wrenches available on the marketR410A air conditioner Conventional air Installation ToolsRequired Tools General tools Conventional tools can be used1 Configuration of refrigerant charging Recharging of RefrigerantFlux Brazing of PipesMaterials for Brazing Brazing Never use gas other than Nitrogen gasRAS-10YKV-E, RAS-13YKV-E Construction ViewsIndoor Unit Outdoor Unit RAS-10YAV-E RAS-13YAV-ECheck items Diagnosis result Wiring Diagram1 Simple check points for diagnosing faults RAS-10YAV-E, RAS-13YAV-E V. Pulse Modulating ValveParts name Model name Rating Specifications of Electrical PartsParts name Type Specifications RAS-10YKV-E/RAS-10YAV-E RAS-13YKV-E/RAS-13YAV-E Refrigerant Cycle DiagramRefrigerant Cycle Diagram Heating Operation DataCooling Control Block Diagram Remote ControllerMCC808 P.C.B AssemblyRAS Operation Description Outline of Air Conditioner ControlPower Factor Improvement Control Capacity ControlCurrent Release Control 1 Compressor revolution rangePrevent-Freezing Control 5. P. M. V. Pulse Modulating ValveLouver Control Indoor Fan Control DC Fan MotorDescription of Operation Circuit Outdoor Fan Control DC Fan MotorCOOL, DRY HeatCurrent release control Outdoor temperature release controlPrevent-freezing control Rps Louver control5 Setting of air flow ECONO. operation controlHeating Operation Basic controlStarting and in stability Cold draft preventing controlDefrost control Temporary Operation Automatic OperationTemporary Auto Operation Temporary Cooling OperationOperation Motion How to Set the Auto RestartAuto Restart Function How to Cancel the Auto Restart Case of Power Failure during the Timer OperationRemote Controller Parts Name of Remote ControllerName of Indications on Remote Controller START/STOP buttonRemark per EMC Directive 89/336/EEC Installation ProcedureSafety Cautions Optional Installation Parts Indoor UnitElectrical Work Outdoor Unit Refrigerant Piping ConnectionHOW to Diagnose the Trouble Confirmation of Power SupplyConfirmation of Power Voltage First ConfirmationOperation of air conditioner Description Primary JudgmentOperation Which is not a Trouble Program Operation Judgment by Flashing LED of Indoor Unit Check Block display Description for self-diagnosis CodeSelf-Diagnosis by Remote Controller Check Code Operation Control by Rated Frequency in Service ModeSelf-Diagnosis ButtonBlock distinction Check outdoor heat exchanger temp Judgment of Trouble by Every Symptom Indoor Unit Including Remote ControllerConfirmation procedure Power is not turned on Does not operate entirelyOnly the indoor fan does not operate YESCause How to examine whether remote controller is good or bad Outdoor unit does not operate Wiring Failure Interconnecting and Serial Signal WireCheck procedure Select phenomena described below Check Code 1C Miswiring in indoor/outdoor units and 1E Check procedureDiagnosis/Process flowchart Contents Summary How to Diagnose Trouble in Outdoor UnitSummarized Inner Diagnosis of Inverter Assembly How to Check Simply the Main Parts How to Check the P.C. Board Indoor UnitOperating precautions Inspection proceduresCheck procedures Procedure Check point Symptom CausesBottom View Sensor characteristic table10-8-2. P.C. Board Layout Part name Checking procedure Indoor Unit Other PartsOutdoor Unit Position Resistance valueChecking Method for Each Part Case that product is goodHow to Simply Judge Whether Outdoor Fan Motor is Good or Bad SymptomHOW to Replace the Main Parts Part name Procedure Remarks11-1 Indoor Unit To assemble the front panelRemoving Louver motor Microcomputer Board layoutAttachment No. Part name Procedure RemarksDetachment Be careful to check the inverter because High-voltage circuit is incorporated in itBundled PartLead wires Propeller Flange nut is loosened by turning clockwise Pulse modulating valve has a room Side and B room side. After mounting itCheck that coil at B room side Red Perform work on a corrugated cardboardPart name Procedure Remarks Parts name Qty RemarksMCC-808 Location Exploded Views and Parts ListPart Description Part Description 222 43T49023 Holder of Plate of EVA-SEAL 11, 13 12 24, 25 26, 27 12-3. P.C. Board Layout Toshiba Carrier Corporation Turn 208 10YKV-E 221 Cushion, Rubber Valve, 4-way To Sensor Ø6