Block distinction |
| Operation of diagnosis function |
|
| ||
Check | Block | Check | Cause of operation | Air | Remarks | Judgment and action |
conditioner |
| |||||
code | code |
| ||||
|
| status |
|
| ||
|
|
|
|
|
| |
| Outdoor |
| Inverter | All off | Displayed when | Even if trying operation again, all |
| P.C. board |
| protective circuit |
| error is detected. | operations stop immediately. : Replace |
|
|
| operates. (Short time) |
|
| P.C. board. |
|
|
| All off | Displayed when | 1. Even if connecting lead wire of | |
|
|
| error or |
| error is detected. | compressor is removed, position- |
|
|
| between windings of |
|
| detect circuit error occurred. : |
|
|
| compressor |
|
| Replace P.C. board. |
|
|
|
|
|
| 2. Measure resistance between wires |
|
|
|
|
|
| of compressor, and perform short- |
|
|
|
|
|
| circuit. : Replace compressor. |
|
|
| All off | Displayed when | Even if trying operation again, all | |
|
|
| error |
| error is detected. | operations stop immediately. : |
|
|
|
|
|
| Replace P.C. board. |
|
|
| Being out of place, | All off | Displayed when | 1. Check outdoor temp. sensors |
|
|
| disconnection or short- |
| error is detected. | (TE, TS). |
|
|
| circuit of outdoor temp. |
|
| 2. Check P.C. board. |
|
|
| sensor |
|
|
|
|
|
| Disconnection or short- | All off | Displayed when | 1. Check discharge temp. sensor (TD). |
|
|
| circuit of discharge temp. |
| error is detected. | 2. Check P.C. board |
|
|
| sensor |
|
|
|
|
|
| Outdoor fan drive system | All off | Displayed when | |
|
|
| error |
| error is detected. | protective operation of outdoor fan |
|
|
|
|
|
| drive system, fan lock, etc. : |
|
|
|
|
|
| Replace P.C. board or fan motor. |
| Not |
| Outdoor heat exchanger | Operation |
| 1. Check outdoor heat exchanger temp. |
| displayed |
| temp. sensor error | continues | sensor (TE). | |
|
|
|
|
|
| 2. Check P.C. board. |
| Outdoor |
| Compressor drive output | All off | Displayed when | When 20 seconds passed after start- |
| P.C. board |
| error, Compressor error |
| error is detected. | up, |
|
|
| (lock, missing, etc.), |
|
| occurred. : Replace compressor. |
|
|
| Break down |
|
|
|
| Others |
| Return serial signal has | Operation | Flashes when | 1. Repeat Start and Stop with interval |
| (including |
| been sent when | continues | trouble is detected | of approx. 10 to 40 minutes. (Code is |
| compressor) |
| operation started, but it |
| on Return serial | not displayed during operation.) |
|
|
| is not sent from halfway. |
| signal, and normal | Supply gas. (Check also gas leak). |
|
|
| (1) Compressor thermo. |
| status when signal | 2. Unit operates normally during check. |
|
|
| operation |
| is reset. | If Return serial signal does not stop |
|
|
| Gas shortage |
|
| between indoor terminal block 2 and |
|
|
| Gas leak |
|
| 3, replace inverter P.C. board. |
|
|
| (2) Instantaneous power |
|
| If signal stops between indoor |
|
|
| failure |
|
| terminal block 2 and 3, replace |
|
|
|
|
|
| indoor P.C. board. |
|
|
| Compressor does not | All off | Displayed when | 1. Trouble on compressor |
|
|
| rotate. |
| error is detected. | 2. Trouble on wiring of compressor |
|
|
| (Current protective |
|
| (Missed phase) |
|
|
| circuit does not operate |
|
|
|
|
|
| when a specified time |
|
|
|
|
|
| passed after compressor |
|
|
|
|
|
| had been activated.) |
|
|
|
|
|
| Discharge temp. | All off | Displayed when | 1. Check dischage temp. sensor (TD). |
|
|
| exceeded 117°C |
| error is detected. | 2. Degassing |
|
|
|
|
|
| 3. Trouble on P.M.V. |
|
|
| Break down of | All off | Displayed when | 1. Check power voltage. |
|
|
| compressor |
| error is detected. | |
|
|
|
|
|
| 2. Overload operation of refrigeration |
|
|
|
|
|
| cycle |
|
|
|
|
|
| Check installation condition |
|
|
|
|
|
| |
|
|
| Operation |
| 1. Check | |
|
|
| error | continues |
|
|
|
|
| (TC sensor value |
|
| |
|
|
| lowered during heating |
|
|
|
|
|
| operation.) |
|
|
|