Table 3. Adjustable Parameters Table (Installer)
Parameter Name: | Default | Parameter Value Setting | Increment | Installer entry |
|
|
|
|
|
Lock in 2nd stage HP by Outdoor Temp | Off | Off, 40ºF (4ºC), 45ºF (7ºC), 50ºF (10ºC), 55ºF (13ºC) |
|
|
|
|
|
|
|
Balance Point Control | Disabled | Enabled, Disabled |
|
|
|
|
|
|
|
Humiditrol Comfort Adjust | Maximum | Maximum, Midpoint, Minimum Overcooling |
|
|
|
|
|
|
|
High Balance Point | 50ºF | −17ºF to 75ºF | 1ºF |
|
|
|
|
|
|
Low Balance Point Control | 25ºF | −20ºF to 72ºF | 1ºF |
|
|
|
|
|
|
Defrost Target Discharge Temp | 55ºF | 50ºF to 60ºF | 1ºF |
|
|
|
|
|
|
Dehumidification Control Mode | Display Only | Display Only, Basic, Precision (only available when |
|
|
NO dehumidifier is installed) |
|
| ||
|
|
|
| |
|
|
|
|
|
Humidification Control Mode | Display Only | Display Only, Basic, Precision, Basic Dew Point Con- |
|
|
trol, Precision Dew Point Control |
|
| ||
|
|
|
| |
|
|
|
|
|
Autochangeover Humidification Deadband | 5% | 5% to 10% | 1% |
|
|
|
|
|
|
Max Humidification Setpoint | 45% | 15% to 45% | 1% |
|
|
|
|
|
|
Min Dehumidification Setpoint | 40% | 40% to 60% | 1% |
|
|
|
|
|
|
Max Dehumidification Setpoint | 40% | 40% to 60% | 1% |
|
|
|
|
|
|
OK/Humid Boundary | 50% | 45% to 60% | 1% |
|
|
|
|
|
|
Outdoor Temperature Reading Calibration | 0 | −10ºF to 10ºF | 1% |
|
|
|
|
|
|
OUTDOOR EQUIPMENT (Go to EQUIPMENT button and scroll to HEAT PUMP or AIR CONDITIONER.)
Equipment Name (HP & AC) | Outdoor Unit | (keyboard input screen = up to 35 characters in string) |
|
|
|
|
|
|
|
Compressor Short Cycle Delay (HP and AC) | 300 Seconds | 60 to 300 Seconds | 60 Sec |
|
|
|
|
|
|
Compressor Shift Delay On/Off (HP only) | On | On, Off |
|
|
|
|
|
|
|
Defrost Termination Temp (HP only) | 50ºF | 50ºF to 100ºF | 10ºF |
|
|
|
|
|
|
|
|
| table continued on next page |
506920−01 09/12 | Page 38 |