Lennox International Inc XP1906, XP2101, XC2105 Adjustable Parameters Table Installer, Air Handler

Page 39
AIR HANDLER

Table 3. Adjustable Parameters Table (Installer)

Parameter Name:

Default

Parameter Value Setting

Increment

Installer entry

 

 

AIR HANDLER

Equipment Name

Air Handler

(keyboard input screen)

 

 

 

 

 

 

 

Electric Heating Airflow

nnnn CFM

 

5CFM

 

 

NOTE: CFM Default and Values Settings are depen-

 

 

Low Cooling Airflow

(See Note 3 at

5CFM

 

dent on the tonnage of the unit

 

 

end of table)

 

 

High Cooling Airflow

 

5CFM

 

 

 

 

 

 

 

 

 

 

 

1: No Delays,

 

 

Cooling Airflow Profile

1

2: ON: No delays; OFF: 45 sec delay

 

 

3: ON: 82%/7.5min; OFF: No delays

 

 

 

 

 

 

 

 

4: ON: 50%/30s,82%/7.5min; OFF:50%/30s

 

 

 

 

 

 

 

Low Heating Airflow

 

 

5CFM

 

 

nnnn CFM

 

 

 

High Heating Airflow

NOTE: CFM Default and Values Settings are depen-

5CFM

 

(See Note 3 at

 

 

 

 

Continuous Indoor Blower Airflow

dent on the tonnage of the unit

10CFM

 

end of table)

 

 

 

 

 

Humidification Airflow

 

 

10CFM

 

 

 

 

 

 

Dehumidification Airflow

70%

60 to 80% (percentage of reduction of High Cooling

1%

 

Airflow)

 

 

 

 

 

 

 

 

 

 

Delays:

 

 

 

 

Heating Indoor Blower OFF

10 sec

0 to 10 Seconds

1 sec

 

Heating Indoor Blower ON

0 sec

0 to 5 Seconds

1 sec

 

 

 

 

 

 

Cooling Indoor Blower OFF

0 sec

0 to 30 Seconds

2 sec

 

 

 

 

 

 

Cooling Indoor Blower ON

2 sec

0 to 10 Seconds

1 sec

 

 

 

 

 

 

HP Indoor Blower OFF

45 sec

0 to 60 Seconds

5 sec

 

 

 

 

 

 

HP Indoor Blower ON

0 sec

0 to 30 Seconds

5 sec

 

 

 

 

 

 

Page 39

icomfort Wi-Fit 7−Day Programmable Communicating Thermostat

Image 39
Contents CONTROLS INSTALLER’S SYSTEM SETUP GUIDEicomfortt−Enabled Units 2P0912**P506920-01Setting up typical icomfortt systems Table of ContentsPage Supports Outdoor Temperature Sensor optionFigure 1. icomfort by Lennoxt system Installation and Setup Figure 4. Entering Change settingsFigure 3. Settings change tools Dealer NumberTable 1. System setting defaults and range Circulate fan ON time settingFigure 6. Set current time and date Set time and date09 39 am Figure 5. View/edit time and dateFigure 7. Using the HUMIDITY CONTROL TIPS Add or Remove Non−communicating equipmentSystem Add Non−Communicating Outdoor unitFigure 8. Add non−communicating device red settingsHumidifier 5a 5bFigure 9. Add or remove non−communicating device SystemDehumidifier Figure 10. Add or remove non−communicating deviceSystem DehumidifierFigure 11. Adjust communicating device screens Adjust a setting screen communicating devicesFigure 12. Accessing device to modify Figure 13. Modify device settingsG71MPP or SLP98 Furnace Note Figure 14. Adjust a non−communicating device setting Figure 15. Adjust a non−communicating device setting Figure 16. Adjust dehumidification when not using Humiditrol or an auxiliary dehumidifier Humidification and Dehumidification Modes HUMIDIFICATION modesDEHUMIDIFICATION modes Figure 19. Typical tests results screens Use the Tests / Diagnostics featuresFigure 17. Start testing screen Figure 18. Select tests to run screenFigure 21. Equipment parameters screen Equipment, Alerts, DiagnosticsSet up Equipment parameters Figure 20. Testing finished screenFigure 22. Edit equipment details Run DiagnosticsView and clear Installer Alerts Figure 23. Select device and run diagnosticsFigure 26. Cleared alerts screen Figure 25. Cleared alert confirmationView cleared alerts Figure 24. Selecting and viewing alertsHERE Figure 27. Wi−Fi setupSecure Connection Recommended STARTRegistering the icomfort Wi-Fitthermostat Registration for online accessFigure 28. Change Networks Figure 30. icomfort Wi-FitRegistration screen Wi-FitTher Welcome homeHow Do I Upload a Skin? Figure 31. PC Welcome Screenyes no Access installer program from Home screenFigure 34. Re−configuration process Reconfigure a system2nd Stage Differential where applicable2 Rules for SSR Smooth Setback Recovery SSRHigh Balance Point Heat Pump, Dual Fuel and Balance PointsHeat Pump Balance Points Low Balance PointShut down HP Gas Heat Control Mode Figure 36. Variable Capacity Operation Flow ChartTable 2. Variable Capacity Furnace Operation Staged operationLoad−tracking Variable Capacity FAQs SLP98V only Installer entry Table 3. Adjustable Parameters Table InstallerLock in 2nd stage HP by Outdoor Temp Table 3. Adjustable Parameters Table InstallerAIR HANDLER Table 3. Adjustable Parameters Table InstallerGas Heat Airflow Settings Table 3. Adjustable Parameters Table InstallerFURNACE Cooling Airflow Settings Heat Pump Airflow SettingsTable 3. Adjustable Parameters Table Installer Table 3. Adjustable Parameters Table Installer Other ParametersTable 4. Adjustable Parameters Table User Filter 1 Timer Table 5. Alert Codes and Troubleshooting Alert Table 5. Alert Codes and TroubleshootingAlert Table 5. Alert Codes and TroubleshootingAlert Table 5. Alert Codes and TroubleshootingAlert Table 5. Alert Codes and TroubleshootingAlert Table 5. Alert Codes and TroubleshootingAlert Table 5. Alert Codes and TroubleshootingAlert Table 5. Alert Codes and TroubleshootingAlert Table 5. Alert Codes and TroubleshootingTable 5. Alert Codes and Troubleshooting Homeowner Service Alert Codes8Corrective Action / Comments Table 6. Troubleshooting TipsIssue / Problem Possible CauseHigh Balance Point and Low Bal Table 6. Troubleshooting TipsDetermine the actual Software ver Table 6. Troubleshooting TipsDuring the cooling mode the dis Table 6. Troubleshooting Tipsicomfortt Communicating System Wiring Wiring Diagramsicomfort by Lennoxt AIR HANDLER AHC Wiring Diagramsfor use with any icomfort by Lennoxt system Optional Accessories WiringOptional Accessories Wiring for use with any icomfort by Lennoxt systemLVCS Ventilation Control System attached to the PUSHBUTTON TIPS Setting up typical systemsTIPS Setting up typical systemsT PUMP DUAL FUEL TIPSTIPS TIPS Setting up typical systemsTIPS TIPS Setting up typical systemsT PUMP UNITSTIPS Replacement Kit Catalog No Table 7. Replacement ControlsREVISION HISTORY icomfortt−Enabled Unit