Lennox International Inc EL296V01, XP2101 Troubleshooting Tips, During the cooling mode the dis

Page 58

Table 6. Troubleshooting Tips

Bold text indicates a button, or text display on the thermostat.

 

 

 

 

No.

Issue / Problem

Possible Cause

Corrective Action / Comments

 

 

 

 

18

During the cooling mode the dis-

The system may be following

− During the default cooling ramping profile the blower will run for 7.5

 

played air volume on the indoor con-

cooling ramping" profile or may

minutes at 82% of the cooling air volume. If the

 

trol is substantially lower than ex-

be in

profile" is selected, the system will ramp to 100% after 7.5 minutes.

 

pected.

mode".

− The dehumidification mode will run the system at 70% of the cooling

 

 

 

air volume which will be in addition to the air volume reduction pro-

 

 

 

vided during the ramping profile. During the dehumidification mode, a

 

 

 

d" will be displayed on the furnace or air handler control.

 

 

 

 

19

The Indoor unit is not providing the

− Indoor unit air volume settings

− In the installer program select the equipment button and choose the

 

expected air volume according to the

in the icomfort thermostat are

furnace or air handler from the system devices list and press edit.

 

cfm shown on the indoor unit control.

not correct.

Verify/set the correct air volume for heating and cooling modes.

 

 

− System is operating in the cool-

− If in the cooling mode check for cooling ramp mode or dehumidifica-

 

 

ing mode and following the

tion mode as in #18.

 

 

cooling ramping profile or dehu-

 

 

 

midification air volume.

 

 

 

 

 

20

− No second stage cooling is pro-

The red Critical Alert icon and

− Go to the installer program alert button to view all alerts and details

 

vided on a icomfort outdoor unit.

homeowner alert button do not

about those alerts.

 

− Space temperature is above second

display non−critical alerts.

− Look for alert code 401 (Compressor Long On Cycle) which indicates

 

stage differential and has run in first

 

compressor ran more than 18 hours continuous and will lock out 2nd

 

stage a long time.

 

stage compressor.

 

− No red Critical Alert icon or alert is

 

− Cycle indoor power off and back on, alert code 401 will clear within a

 

displayed in the homeowner alert

 

few minutes.

 

button.

 

 

 

 

 

 

21

No weather being displayed.

icomfort Wi-Fit not communicat-

Make sure Wi−Fi is enabled (see Page 24).

 

 

ing with router.

 

 

 

 

 

22

Unable to complete Wi−Fi router / in-

Refer to 507037−01 Wi−Fi Troubleshooting checklist for icomfort Wi−Fit thermostat.

 

ternet connection

 

 

 

 

 

 

506920−01 09/12

Page 58

Image 58
Contents 2P0912**P506920-01 INSTALLER’S SYSTEM SETUP GUIDEicomfortt−Enabled Units CONTROLSTable of Contents Setting up typical icomfortt systemsPage Outdoor Temperature Sensor option SupportsFigure 1. icomfort by Lennoxt system Installation and Setup Dealer Number Change settingsFigure 3. Settings change tools Figure 4. EnteringCirculate fan ON time setting Table 1. System setting defaults and rangeFigure 5. View/edit time and date Set time and date09 39 am Figure 6. Set current time and dateFigure 7. Using the Add or Remove Non−communicating equipment HUMIDITY CONTROL TIPSred settings Add Non−Communicating Outdoor unitFigure 8. Add non−communicating device SystemSystem 5a 5bFigure 9. Add or remove non−communicating device HumidifierDehumidifier Figure 10. Add or remove non−communicating deviceSystem DehumidifierAdjust a setting screen communicating devices Figure 11. Adjust communicating device screensFigure 13. Modify device settings Figure 12. Accessing device to modifyG71MPP or SLP98 Furnace Note Figure 14. Adjust a non−communicating device setting Figure 15. Adjust a non−communicating device setting Figure 16. Adjust dehumidification when not using Humiditrol or an auxiliary dehumidifier HUMIDIFICATION modes Humidification and Dehumidification ModesDEHUMIDIFICATION modes Figure 18. Select tests to run screen Use the Tests / Diagnostics featuresFigure 17. Start testing screen Figure 19. Typical tests results screensFigure 20. Testing finished screen Equipment, Alerts, DiagnosticsSet up Equipment parameters Figure 21. Equipment parameters screenRun Diagnostics Figure 22. Edit equipment detailsFigure 23. Select device and run diagnostics View and clear Installer AlertsFigure 24. Selecting and viewing alerts Figure 25. Cleared alert confirmationView cleared alerts Figure 26. Cleared alerts screenSTART Figure 27. Wi−Fi setupSecure Connection Recommended HERERegistration for online access Registering the icomfort Wi-FitthermostatFigure 28. Change Networks Figure 30. icomfort Wi-FitRegistration screen Figure 31. PC Welcome Screen Welcome homeHow Do I Upload a Skin? Wi-FitTherAccess installer program from Home screen yes noReconfigure a system Figure 34. Re−configuration process2nd Stage Differential where applicable2 Smooth Setback Recovery SSR Rules for SSRLow Balance Point Heat Pump, Dual Fuel and Balance PointsHeat Pump Balance Points High Balance PointShut down HP Figure 36. Variable Capacity Operation Flow Chart Gas Heat Control ModeStaged operation Table 2. Variable Capacity Furnace OperationLoad−tracking Variable Capacity FAQs SLP98V only Table 3. Adjustable Parameters Table Installer Installer entryTable 3. Adjustable Parameters Table Installer Lock in 2nd stage HP by Outdoor TempTable 3. Adjustable Parameters Table Installer AIR HANDLERTable 3. Adjustable Parameters Table Installer Gas Heat Airflow SettingsFURNACE Heat Pump Airflow Settings Cooling Airflow SettingsTable 3. Adjustable Parameters Table Installer Other Parameters Table 3. Adjustable Parameters Table InstallerTable 4. Adjustable Parameters Table User Filter 1 Timer Table 5. Alert Codes and Troubleshooting Table 5. Alert Codes and Troubleshooting AlertTable 5. Alert Codes and Troubleshooting AlertTable 5. Alert Codes and Troubleshooting AlertTable 5. Alert Codes and Troubleshooting AlertTable 5. Alert Codes and Troubleshooting AlertTable 5. Alert Codes and Troubleshooting AlertTable 5. Alert Codes and Troubleshooting AlertTable 5. Alert Codes and Troubleshooting AlertHomeowner Service Alert Codes8 Table 5. Alert Codes and TroubleshootingPossible Cause Table 6. Troubleshooting TipsIssue / Problem Corrective Action / CommentsTable 6. Troubleshooting Tips High Balance Point and Low BalTable 6. Troubleshooting Tips Determine the actual Software verTable 6. Troubleshooting Tips During the cooling mode the disWiring Diagrams icomfortt Communicating System WiringWiring Diagrams icomfort by Lennoxt AIR HANDLER AHCOptional Accessories Wiring for use with any icomfort by Lennoxt systemfor use with any icomfort by Lennoxt system Optional Accessories WiringLVCS Ventilation Control System attached to the PUSHBUTTON Setting up typical systems TIPSTIPS TIPS Setting up typical systemsT PUMP DUAL FUELTIPS Setting up typical systems TIPSTIPS Setting up typical systemsT PUMP UNITS TIPSTIPS icomfortt−Enabled Unit Table 7. Replacement ControlsREVISION HISTORY Replacement Kit Catalog No