Lennox International Inc EL296V01, XP2101, XC2105 Setting up typical systemsT PUMP UNITS, Tips

Page 70
Setting up typical systemsT PUMP UNITS

Setting up typical systemsT PUMP UNITS

icomfortt−enabled Air Handler & icomfortt−enabled Heat Pump unit

An icomfort air handler (CBX32MV or CBX40UHV) with an icomfort−enabled heat pump (XP17 or XP21 only) unit.

NOTE − IMPORTANT! Be sure to set up the air handler control for heat strips (if used) prior to powering up the system and thermostat.

1. Configure air handler control (AHC) for auxiliary heat strips if used.

2. Wiring Communicating System Wiring diagram on Page 59

and Optional Accessories Wiring (Page 61) for any accessories be- ing installed with the system.

D4−conductor thermostat wire from the icomfort Wi-Fit thermostat to the air handler (R, i+, i−, C)

D4−conductor thermostat wire from the air handler terminal strip to the icomfort−enabled HP (R, i+, i−, C)

DWiring as required for accessories

3.DO NOT cut any option link on air handler control.

4.After the entire system is wired, power up the system; the icomfort Wi- Fit thermostat will check the system for installed communication de- vices.

5.On the thermostat, go past the

vices" to the o adjust a setting" screen. Select the

device list using the up/down arrows and press the edit button

6.Select Balance Point Control and press edit. Use the down arrow to select Enabled and press save. High and Low Balance Points will ap- pear in red.

7.Complete Balance Point Control by editing the High and Low Balance Points. It is not necessary to change the defaults, but you must save each setting. The red settings will go away after pressing save. Press the back button to return to the adjust screen.

8.Use the arrows to select Air Handler from system devices list. Press edit. From this Air Handler screen you will have access to the various airflow settings. Set the system air volumes according the needs of the home. When all CFM settings are complete, press the back button. Address any red settings as described in steps 6 and 7. Press next step to advance to the tests button.

9.Test the system operation and confirm the system is electrically ener- gized and operational. Particularly, test the heat strips (when used) to ensure the auxiliary stages operate as designed. Press done.

10.Exit the installer setup mode by selecting the EXIT button.

TIPS

SIf the thermostat fer a choice for

heat" and or the electric heat will not function; the electric heat has not been configured. Configure the electric heat as described on Page 64, or for complete detail, see the Air Handler installation instructions. Re- configure the icomfort system by entering the installer program and se- lecting the setup button and following the prompts.

SHigh & low balance points are enabled and adjusted under the installer section of the thermostat. In the equipment button select

press edit. Scroll down to

Point Control" and press edit and

select Enabled and then save.

 

SAn outdoor temperature sensor is provided in an icomfort enabled heat pump unit. To display the outdoor temperature on the home screen of the thermostat, you must turn on (or off) the emp Display".

From the Home screen, press press for more area and select the HELP icon. Press the user preferences box and scroll down to door Temp Display". Press the modify button and use the up/down ar- rows to select On (or Off) and then press the save button. Press done to return to the Home screen.

506920−01 09/12

Page 70

Image 70
Contents 2P0912**P506920-01 INSTALLER’S SYSTEM SETUP GUIDEicomfortt−Enabled Units CONTROLSTable of Contents Setting up typical icomfortt systemsPage Outdoor Temperature Sensor option SupportsFigure 1. icomfort by Lennoxt system Installation and Setup Dealer Number Change settingsFigure 3. Settings change tools Figure 4. EnteringCirculate fan ON time setting Table 1. System setting defaults and rangeFigure 5. View/edit time and date Set time and date09 39 am Figure 6. Set current time and dateFigure 7. Using the Add or Remove Non−communicating equipment HUMIDITY CONTROL TIPSred settings Add Non−Communicating Outdoor unitFigure 8. Add non−communicating device SystemSystem 5a 5bFigure 9. Add or remove non−communicating device HumidifierDehumidifier Figure 10. Add or remove non−communicating deviceSystem DehumidifierAdjust a setting screen communicating devices Figure 11. Adjust communicating device screensFigure 13. Modify device settings Figure 12. Accessing device to modifyG71MPP or SLP98 Furnace Note Figure 14. Adjust a non−communicating device setting Figure 15. Adjust a non−communicating device setting Figure 16. Adjust dehumidification when not using Humiditrol or an auxiliary dehumidifier HUMIDIFICATION modes Humidification and Dehumidification ModesDEHUMIDIFICATION modes Figure 18. Select tests to run screen Use the Tests / Diagnostics featuresFigure 17. Start testing screen Figure 19. Typical tests results screensFigure 20. Testing finished screen Equipment, Alerts, DiagnosticsSet up Equipment parameters Figure 21. Equipment parameters screenRun Diagnostics Figure 22. Edit equipment detailsFigure 23. Select device and run diagnostics View and clear Installer AlertsFigure 24. Selecting and viewing alerts Figure 25. Cleared alert confirmationView cleared alerts Figure 26. Cleared alerts screenSTART Figure 27. Wi−Fi setupSecure Connection Recommended HERERegistration for online access Registering the icomfort Wi-FitthermostatFigure 28. Change Networks Figure 30. icomfort Wi-FitRegistration screen Figure 31. PC Welcome Screen Welcome homeHow Do I Upload a Skin? Wi-FitTherAccess installer program from Home screen yes noReconfigure a system Figure 34. Re−configuration process2nd Stage Differential where applicable2 Smooth Setback Recovery SSR Rules for SSRLow Balance Point Heat Pump, Dual Fuel and Balance PointsHeat Pump Balance Points High Balance PointShut down HP Figure 36. Variable Capacity Operation Flow Chart Gas Heat Control ModeStaged operation Table 2. Variable Capacity Furnace OperationLoad−tracking Variable Capacity FAQs SLP98V only Table 3. Adjustable Parameters Table Installer Installer entryTable 3. Adjustable Parameters Table Installer Lock in 2nd stage HP by Outdoor TempTable 3. Adjustable Parameters Table Installer AIR HANDLERTable 3. Adjustable Parameters Table Installer Gas Heat Airflow SettingsFURNACE Heat Pump Airflow Settings Cooling Airflow SettingsTable 3. Adjustable Parameters Table Installer Other Parameters Table 3. Adjustable Parameters Table InstallerTable 4. Adjustable Parameters Table User Filter 1 Timer Table 5. Alert Codes and Troubleshooting Table 5. Alert Codes and Troubleshooting AlertTable 5. Alert Codes and Troubleshooting AlertTable 5. Alert Codes and Troubleshooting AlertTable 5. Alert Codes and Troubleshooting AlertTable 5. Alert Codes and Troubleshooting AlertTable 5. Alert Codes and Troubleshooting AlertTable 5. Alert Codes and Troubleshooting AlertTable 5. Alert Codes and Troubleshooting AlertHomeowner Service Alert Codes8 Table 5. Alert Codes and TroubleshootingPossible Cause Table 6. Troubleshooting TipsIssue / Problem Corrective Action / CommentsTable 6. Troubleshooting Tips High Balance Point and Low BalTable 6. Troubleshooting Tips Determine the actual Software verTable 6. Troubleshooting Tips During the cooling mode the disWiring Diagrams icomfortt Communicating System WiringWiring Diagrams icomfort by Lennoxt AIR HANDLER AHCOptional Accessories Wiring for use with any icomfort by Lennoxt systemfor use with any icomfort by Lennoxt system Optional Accessories WiringLVCS Ventilation Control System attached to the PUSHBUTTON Setting up typical systems TIPSTIPS TIPS Setting up typical systemsT PUMP DUAL FUELTIPS Setting up typical systems TIPSTIPS Setting up typical systemsT PUMP UNITS TIPSTIPS icomfortt−Enabled Unit Table 7. Replacement ControlsREVISION HISTORY Replacement Kit Catalog No