Lennox International Inc Gas Units, G61MP Series Units Vent Piping Guidelines

Page 18

Vent Piping Guidelines

The G61MP can be installed as either a Non−Direct Vent or a Direct Vent gas central furnace.

NOTE − In Non-Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors. In Direct Vent installations, combustion air is taken from out- doors and flue gases are discharged outdoors.

Intake and exhaust pipe sizing in Direct Vent applications and exhaust pipe sizing in Non-Direct Vent applications −− Size pipe according to tables 6 and 7. Table 6 lists the mini- mum equivalent vent pipe lengths permitted. Table 7 lists the maximum equivalent pipe lengths permitted.

Maximum vent length is defined as:

Total length (linear feet) of pipe,

Plus Equivalent length (feet) of fittings,

Plus Equivalent length (feet) of termination.

NOTE − Include ALL pipe and ALL fittings, both in doors and outdoors.

Regardless of the diameter of pipe used, the standard roof and wall terminations described in section Exhaust Piping Terminations should be used. Exhaust vent termination pipe is sized to optimize the velocity of the exhaust gas as it exits the termination. Refer to table 8.

*NOTE − The exhaust pipe should be offset a minimum of 12 inches to avoid the possibility of water droplets being re-

leased from the exhaust termination. The minimum ex- haust vent length is 15 ft. Shorter exhaust vent lengths may result in the discharge of water droplets from the exhaust termination, in spite of the 12−inch vertical offset. See fig- ure 21.

Each 90° elbow (including those provided with the furnace) of any diameter is equivalent to 5 feet (1.52m) of vent pipe of the same diameter. Two 45° elbows are equivalent to one 90° elbow of the same diameter. One 45° elbow is equal to 2.5 feet (.76m) of vent pipe of the same diameter. In some applications which permit the use of several differ- ent sizes of vent pipe, a combination vent pipe may be used. Contact the Application Department for assistance in sizing vent pipe in these applications.

NOTE − The flue collar on all models is sized to accommo- date 2" Schedule 40 flue pipe. When vent pipe which is larger than 2" must be used in an upflow application, a 2" elbow must be applied at the flue collar in order to proper- ly transition to the larger diameter flue pipe. This elbow must be added to the elbow count used to determine ac- ceptable vent lengths. Assign an equivalent feet value to this elbow according to the larger size pipe being used. Contact Lennox’ Application Department for more infor- mation concerning sizing of vent systems which include multiple pipe sizes.

 

Exhaust Pipe Offset

 

12" Min.

*12" Min.

 

Upflow and Downflow Application

Upflow and Downflow Application

Rooftop Termination

Side Wall Termination

*12" Min.

*12" Min.

 

Horizontal Application Rooftop Termination

Horizontal Application Side Wall Termination

*A minimum of 1/4" (6mm) drop for each 12" (305mm) of horizontal run is mandatory for drainage

FIGURE 21

Page 18

Image 18
Contents Installation Instructions Table of ContentsG61MP Unit Dimensions − inches mm TOP ViewFront View Side View TOP CAP Glass AssemblyG61MP Parts Arrangement Sight BlowerInstallation Safety InformationDirect Vent Installation NON−DIRECT Vent G61MP Gas FurnaceUse of Furnace as Construction Heater General Combustion, Dilution & Ventilation AirEquipment in Confined Space − ALL AIR from Inside Installation − Setting Equipment Equipment operationEquipment in Confined Space − ALL AIR from Outside Side View Setting EquipmentFront View END ViewUpflow Applications Refer to Engineering Handbook for additional informationFront View Furnace FrontFurnace Locations Bottom Leveling Bolt Setting an Upflow UnitLeveling Bolt NON−COMBUSTIBLE Floor Opening SizeAdditive Base Floor Opening Size Side ViewBlower Access Panel Typical Horizontal Ceiling ApplicationINTAKE/EXHAUST Connection Support Frame Drain PAN Exhaust Pipe GAS Connector MIN Raised Platform Condensate Line Service PlatformIntake Pipe Filters Pipe & Fittings SpecificationsPiping and Fittings Specifications Duct SystemOutdoor Termination Kits and Corresponding Equivalencies Model DIAVent Piping Guidelines Minimum Vent Pipe Lengths Maximum Vent Pipe LengthsJoint Cementing Procedure MAX Plug Plastic strapping or a large wire tieVenting Practices TrapTypical Exhaust Pipe Connections Direct Vent applications where combustion air is taken From indoors and flue gases are discharged outdoorsTransition Sweep ELL Intake Debris Screen Page Inside Corner Detail Inches 305mm or 12 in mmUS Installations1 Canadian Installations2 Direct Vent Roof Termination KIT Exhaust Pipe Termination Size ReductionG61MP TOP View Wall Ring KIT with Straight IntakeFront View Using Existing Chimney ANGLE−CUT in Direction G61MP Direct Vent ApplicationG61MP NON−DIRECT Vent Application Using Existing Chimney Condensate PipingSide View NON−DIRECT Vent Wall Ring Termination −RINGS CAP HI/LO Screws Condensate AssemblyCoupling CLEAN−OUT Access Vent Nipple TEEGas Piping Furnace Isolate GAS ValveHorizontal Applications Possible Gas Piping Configerations GAS Pipe Capacity − FT3/HR kL/HRElectrical Precautions and ProceduresInterior MAKE−UP BOX Installation Electrostatic Discharge ESDTypical G61MP Field Wiring Diagram Heat / 2 Cool Cut Intact OFF Cut Intact= Error Code Recall H= 24V Humidifier Output L= do not USE DIP Switches FunctionTWO−STAGE Integrated Control Board Integrated Control Board DIP Switch Settings and Jumpers Typical G61MP Wiring Diagram For Your Safety Read Before Operating Integrated Control BoardUnit Start−Up White Rodgers 36E Series GAS Valve Honeywell VR8205 Series GAS ValveGas Pressure Adjustment Urning Off Gas to Unit and call your service techniIf the appliance will not operate, follow the instructions High Altitude Information Order TWO EachOther Unit Adjustments Carbon Monoxide Poisoning HazardPage Blower Performance Data 270In. w.g High Low Cfm Watts 2840 1450 In. w.g High Low Cfm Watts 2720 1385 In. w.g High Low Cfm Watts 2730 1465 Heating Sequence of Operation Service Electrical SHOCK, Fire Or Explosion HazardPage Planned Service Ignition Control Board Diagnostic Codes Flash Code Status / Error Description+ Y Troubleshooting Heating Sequence of Operation On NextHeating Sequence of Operation Thermostat Calls for Heat Status LED − HeartbeatU1.40 microamps Or Heat Demand is SATISFIED. a Five Troubleshooting Cooling Sequence of Operation Cooling Sequence of OperationTroubleshooting Continuous Fan Sequence of Operation Repair Parts ListContinuous LOW Speed FAN Sequence of Operation G61MP Start−Up & Performance Check List Heat Anticipator Setting? Thermostat Level?Vent Pipe Sizing Worksheet − LP/Propane High Fire Manifold PressureRequirements for Commonwealth of Massachusetts LY BELOW. Keep Clear of ALL OBSTRUC- Tions
Related manuals
Manual 8 pages 10.79 Kb

G61MP Series Units, Gas Units specifications

Lennox International Inc. has established itself as a leader in the heating and cooling industry, and its G61MP Series Gas Units stand as a testament to the company's commitment to innovation and energy efficiency. These gas units are specifically designed for residential applications and are recognized for their reliability, performance, and advanced technology.

One of the main features of the G61MP Series is its variable speed motor, which offers significantly enhanced comfort over traditional single-stage gas units. This technology allows for precise temperature control and improved humidity management. By adjusting its speed according to the heating demand, the unit minimizes temperature fluctuations, leading to a more consistent indoor climate.

Another notable characteristic of the G61MP Series is its ECM blower motor, which operates quietly and efficiently. This motor not only reduces energy consumption but also enhances the overall comfort of the home by providing a steady flow of warm air without the disruptive noise often associated with traditional gas units.

The G61MP Series units are designed with a focus on energy efficiency, boasting an impressive Annual Fuel Utilization Efficiency (AFUE) rating. This rating indicates that these units convert a significant portion of the fuel they consume into usable heat, resulting in lower energy bills for homeowners. The units are equipped with a modulating gas valve that further optimizes fuel usage by adjusting the gas flow according to the heating needs of the home.

Safety is a paramount consideration in the design of the G61MP Series. These units are built with advanced safety features, including a self-diagnostic control system that continuously monitors the unit’s performance. This system alerts homeowners to any potential issues, allowing for proactive maintenance and ensuring the longevity of the equipment.

The G61MP Series is also designed for ease of installation and servicing. Its compact design allows for flexible placement in various home environments, while the user-friendly access panels simplify routine maintenance tasks.

In conclusion, Lennox International Inc.'s G61MP Series Gas Units deliver a combination of advanced technology, energy efficiency, and reliability, making them an excellent choice for homeowners looking to enhance their heating systems. With features designed to maximize comfort, minimize energy costs, and ensure safety, these units represent a significant advancement in residential heating solutions.