Lennox International Inc G61MP Series Units Service, Electrical SHOCK, Fire Or Explosion Hazard

Page 53

Service

WARNING

ELECTRICAL SHOCK, FIRE,

OR EXPLOSION HAZARD.

Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage.

Improper servicing could result in dangerous opera- tion, serious injury, death, or property damage. Before servicing, disconnect all electrical power to furnace.

When servicing controls, label all wires prior to dis- connecting. Take care to reconnect wires correctly. Verify proper operation after servicing.

At the beginning of each heating season, system should be checked as follows by a qualified service technician: Blower

Check the blower wheel for debris and clean if necessary. The blower motors are prelubricated for extended bearing life. No further lubrication is needed.

WARNING

The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal inju- ry or death.

Filters

All G61MP filters are installed external to the unit. Filters should be inspected monthly. Clean or replace the filters when necessary to ensure proper furnace operation. Table 3 lists recommended filter sizes.

Exhaust and air intake pipes

Check the exhaust and air intake pipes and all connections for tightness and to make sure there is no blockage. NOTE − After any heavy snow, ice or frozen fog event the furnace vent pipes may become restricted. Always check the vent system and remove any snow or ice that may be obstructing the plastic intake or exhaust pipes. Electrical

1 − Check all wiring for loose connections.

2 − Check for the correct voltage at the furnace (furnace operating).

3 − Check amp−draw on the blower motor.

Motor Nameplate__________Actual__________

Winterizing and Condensate Trap Care 1 − Turn off power to the unit.

2 − Have a shallow pan ready to empty condensate water.

3 − Remove the drain plug from the condensate trap and empty water. Inspect the trap then reinstall the drain plug.

Cleaning Heat Exchanger

If cleaning the heat exchanger becomes necessary, follow the below procedures and refer to figure 1 when disassem- bling unit. Use papers or protective covering in front of fur- nace while removing heat exchanger assembly.

1 − Turn off electrical and gas supplies to the furnace.

2 − Remove the upper and lower furnace access panels. 3 − Mark all gas valve wires and disconnect them from

valve.

4 − Remove gas supply line connected to gas valve. Re- move gas valve/manifold assembly.

5 − Remove sensor wire from sensor. Disconnect 2-pin plug from the ignitor.

6 − Disconnect wires from flame roll−out switches.

7 − Remove burner box cover and remove four burner box screws at the vestibule panel and remove burner box. Set burner box assembly aside.

NOTE − G61MP−135 units are secured to the vestibule panel by two additional screws. These screws must be removed for servicing; however it is not necessary to replace the screws.

NOTE − If necessary, clean burners at this time. Follow procedures outlined in Burner Cleaning section.

8 − Loosen three clamps and remove flexible exhaust tee. 9 − Remove 3/8 inch rubber cap from condensate drain

plug and drain. Replace cap after draining.

10 − Disconnect condensate drain line from the conden- sate trap. Remove condensate trap (it may be neces- sary to cut drain pipe). Remove screws that secure condensate collars to either side of the furnace and re- move collars. Remove drain tubes from cold end header collector box.

11 − Disconnect condensate drain tubing from flue collar. Remove screws that secure both flue collars into place. Remove flue collars. It may be necessary to cut the exiting exhaust pipe for removal of the fittings.

12 − Mark and disconnect all combustion air pressure tub- ing from cold end header collector box.

13 − Mark and remove wires from pressure switches. Re- move pressure switches. Keep tubing attached to pressure switches.

14 − Disconnect the 3-pin plug from the combustion air in- ducer. Disconnect the two wires to the backup secon- dary limit, if applicable. Remove four screws which se- cure combustion air inducer to collector box. Remove combustion air inducer assembly. Remove ground wire from vest panel.

15 − Remove electrical junction box from the side of the fur- nace.

16 − Mark and disconnect any remaining wiring to heating compartment components. Disengage strain relief bushing and pull wiring and bushing through the hole in the blower deck.

Page 53

Image 53
Contents Table of Contents Installation InstructionsFront View Side View G61MP Unit Dimensions − inches mmTOP View G61MP Parts Arrangement Glass AssemblyTOP CAP Sight BlowerDirect Vent Installation NON−DIRECT Vent Safety InformationInstallation G61MP Gas FurnaceUse of Furnace as Construction Heater Combustion, Dilution & Ventilation Air GeneralEquipment in Confined Space − ALL AIR from Inside Equipment in Confined Space − ALL AIR from Outside Installation − Setting EquipmentEquipment operation Front View Setting EquipmentSide View END ViewRefer to Engineering Handbook for additional information Upflow ApplicationsFurnace Front Front ViewLeveling Bolt Setting an Upflow UnitFurnace Locations Bottom Leveling Bolt NON−COMBUSTIBLE Floor Opening SizeSide View Additive Base Floor Opening SizeINTAKE/EXHAUST Connection Support Frame Drain PAN Blower Access PanelTypical Horizontal Ceiling Application Intake Pipe Exhaust Pipe GAS ConnectorMIN Raised Platform Condensate Line Service Platform Piping and Fittings Specifications Pipe & Fittings SpecificationsFilters Duct SystemModel DIA Outdoor Termination Kits and Corresponding EquivalenciesVent Piping Guidelines Maximum Vent Pipe Lengths Minimum Vent Pipe LengthsJoint Cementing Procedure Venting Practices Plastic strapping or a large wire tieMAX Plug TrapTypical Exhaust Pipe Connections Transition Direct Vent applications where combustion air is takenFrom indoors and flue gases are discharged outdoors Sweep ELL Intake Debris Screen Page Inches 305mm or 12 in mm Inside Corner DetailUS Installations1 Canadian Installations2 G61MP Exhaust Pipe Termination Size ReductionDirect Vent Roof Termination KIT TOP View Wall Ring KIT with Straight IntakeFront View G61MP Direct Vent Application Using Existing Chimney ANGLE−CUT in DirectionSide View NON−DIRECT Vent Wall Ring Termination G61MP NON−DIRECT Vent Application Using Existing ChimneyCondensate Piping Coupling CLEAN−OUT Access Condensate Assembly−RINGS CAP HI/LO Screws Vent Nipple TEEFurnace Isolate GAS Valve Gas PipingGAS Pipe Capacity − FT3/HR kL/HR Horizontal Applications Possible Gas Piping ConfigerationsInterior MAKE−UP BOX Installation Precautions and ProceduresElectrical Electrostatic Discharge ESDTypical G61MP Field Wiring Diagram Heat / 2 Cool Cut Intact Cut Intact OFFTWO−STAGE Integrated Control Board = Error Code Recall H= 24V Humidifier Output L= do not USEDIP Switches Function Integrated Control Board DIP Switch Settings and Jumpers Typical G61MP Wiring Diagram Unit Start−Up For Your Safety Read Before OperatingIntegrated Control Board Honeywell VR8205 Series GAS Valve White Rodgers 36E Series GAS ValveIf the appliance will not operate, follow the instructions Gas Pressure AdjustmentUrning Off Gas to Unit and call your service techni Order TWO Each High Altitude InformationCarbon Monoxide Poisoning Hazard Other Unit AdjustmentsPage 270 Blower Performance DataIn. w.g High Low Cfm Watts 2840 1450 In. w.g High Low Cfm Watts 2720 1385 In. w.g High Low Cfm Watts 2730 1465 Heating Sequence of Operation Electrical SHOCK, Fire Or Explosion Hazard ServicePage Planned Service + Y Ignition Control Board Diagnostic CodesFlash Code Status / Error Description On Next Troubleshooting Heating Sequence of OperationThermostat Calls for Heat Status LED − Heartbeat Heating Sequence of OperationU1.40 microamps Or Heat Demand is SATISFIED. a Five Cooling Sequence of Operation Troubleshooting Cooling Sequence of OperationContinuous LOW Speed FAN Sequence of Operation Troubleshooting Continuous Fan Sequence of OperationRepair Parts List Vent Pipe Sizing Worksheet Heat Anticipator Setting? Thermostat Level?G61MP Start−Up & Performance Check List − LP/Propane High Fire Manifold PressureLY BELOW. Keep Clear of ALL OBSTRUC- Tions Requirements for Commonwealth of Massachusetts
Related manuals
Manual 8 pages 10.79 Kb

G61MP Series Units, Gas Units specifications

Lennox International Inc. has established itself as a leader in the heating and cooling industry, and its G61MP Series Gas Units stand as a testament to the company's commitment to innovation and energy efficiency. These gas units are specifically designed for residential applications and are recognized for their reliability, performance, and advanced technology.

One of the main features of the G61MP Series is its variable speed motor, which offers significantly enhanced comfort over traditional single-stage gas units. This technology allows for precise temperature control and improved humidity management. By adjusting its speed according to the heating demand, the unit minimizes temperature fluctuations, leading to a more consistent indoor climate.

Another notable characteristic of the G61MP Series is its ECM blower motor, which operates quietly and efficiently. This motor not only reduces energy consumption but also enhances the overall comfort of the home by providing a steady flow of warm air without the disruptive noise often associated with traditional gas units.

The G61MP Series units are designed with a focus on energy efficiency, boasting an impressive Annual Fuel Utilization Efficiency (AFUE) rating. This rating indicates that these units convert a significant portion of the fuel they consume into usable heat, resulting in lower energy bills for homeowners. The units are equipped with a modulating gas valve that further optimizes fuel usage by adjusting the gas flow according to the heating needs of the home.

Safety is a paramount consideration in the design of the G61MP Series. These units are built with advanced safety features, including a self-diagnostic control system that continuously monitors the unit’s performance. This system alerts homeowners to any potential issues, allowing for proactive maintenance and ensuring the longevity of the equipment.

The G61MP Series is also designed for ease of installation and servicing. Its compact design allows for flexible placement in various home environments, while the user-friendly access panels simplify routine maintenance tasks.

In conclusion, Lennox International Inc.'s G61MP Series Gas Units deliver a combination of advanced technology, energy efficiency, and reliability, making them an excellent choice for homeowners looking to enhance their heating systems. With features designed to maximize comfort, minimize energy costs, and ensure safety, these units represent a significant advancement in residential heating solutions.