Lennox International Inc Gas Units, G61MP Series Units Heating Sequence of Operation

Page 52

Heating Sequence of Operation

NOTE − The thermostat selection DIP switch on the control board is factory−set in the −STAGE" position.

Applications Using a Two−Stage Thermostat

A − Heating Sequence −− Control Board Thermostat Selection DIP switch in T wo−Stage" Position (Factory Setting)

1 − On a call for heat, thermostat first−stage contacts close sending a signal to the integrated control. The inte- grated control runs a self-diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts.The combustion air inducer is ener- gized at low speed and the humidifier terminal is ener- gized.

2 − Once the control receives a signal that the low−fire pressure switch has closed, the combustion air induc- er begins a 15−second pre−purge in low speed.

3 − After the pre−purge is complete, a 20−second initial ig- nitor warm−up period begins. The combustion air in- ducer continues to operate at low speed.

4 − After the 20−second warm−up period has ended, the gas valve is energized on low fire (first stage) and ignition oc- curs. At the same time, the control module sends a sig- nal to begin an indoor blower 45−second ON−delay. When the delay ends, the indoor blower motor is ener- gized on the low fire heating speed. The furnace will continue this operation as long as the thermostat has a first−stage heating demand.

5 − If second−stage heat is required, the thermostat sec- ond−stage heat contacts close and send a signal to the integrated control. The integrated control initiates a 30−second second−stage recognition delay.

6 − At the end of the recognition delay, the integrated con- trol energizes the combustion air inducer at high speed. The control also checks the high−fire (second stage) pressure switch to make sure it is closed. Once the the control receives a signal that the high−fire pres- sure switch is close, the high−fire (second stage) gas valve is energized and the indoor blower motor is en- ergized for operation at the high−fire heating speed.

7 − When the demand for high−fire (second stage) heat is satisfied, the combustion air inducer is switched to the low−fire heating speed and the high−fire (second stage) gas valve is de−energized. The low−fire (first stage) gas valve continues operation. The indoor blower motor is switched to the low−fire heating speed.

8 − When the thermostat demand for low−fire (first stage) heat is satisfied, the gas valve is de−energized and the field−selected indoor blower off delay begins. The combustion air inducer begins a 5−second post−purge period.

9 − When the combustion air post−purge period is com- plete, the inducer and humidifier terminal are de−ener- gized. The indoor blower is de−energized at the end of the off delay.

Applications Using A Single−Stage Thermostat

B − Heating Sequence −− Control Board Thermostat Selection DIP switch in tage" Position

NOTE − In these applications, two−stage heat will be initi- ated by the integrated control if heating demand has not been satisfied after the field adjustable period (10 or 15 minutes).

1 − On a call for heat, thermostat first−stage contacts close sending a signal to the integrated control. The inte- grated control runs a self-diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts.The combustion air inducer is ener- gized at low speed and the humidifier terminal is ener- gized.

2 − Once the control receives a signal that the low−fire pressure switch has closed, the combustion air induc- er begins a 15−second pre−purge in low speed.

3 − After the pre−purge is complete, a 20−second initial ig- nitor warm−up period begins. The combustion air in- ducer continues to operate at low speed.

4 − After the 20−second warm−up period has ended, the gas valve is energized on low fire (first stage) and ignition oc- curs. At the same time, the control module sends a sig- nal to begin an indoor blower 45−second ON−delay. When the delay ends, the indoor blower motor is ener- gized on the low−fire heating speed. The integrated control also initiates a second−stage on delay (factory− set at 10 minutes; adjustable to 15 minutes).

5 − If the heating demand continues beyond the second− stage on delay, the integrated control energizes the combustion air inducer at high speed. The control also checks the high−fire (second stage) pressure switch to make sure it is closed. Once the control receives a sig- nal the high−fire pressure switch is closed, the high−fire (second stage) gas valve is energized and the indoor blower motor is energized for operation at the high−fire heating speed.

6 − When the thermostat heating demand is satisfied, the- combustion air inducer begins a 5−second post−purge. The field−selected indoor blower off delay begins.

7 − When the combustion air post−purge period is com- plete, the inducer and humidifier terminal are de−ener- gized. The indoor blower is de−energized at the end of the off delay.

Page 52

Image 52
Contents Installation Instructions Table of ContentsTOP View G61MP Unit Dimensions − inches mmFront View Side View Glass Assembly G61MP Parts ArrangementTOP CAP Sight BlowerSafety Information Direct Vent Installation NON−DIRECT VentInstallation G61MP Gas FurnaceUse of Furnace as Construction Heater General Combustion, Dilution & Ventilation AirEquipment in Confined Space − ALL AIR from Inside Equipment operation Installation − Setting EquipmentEquipment in Confined Space − ALL AIR from Outside Setting Equipment Front ViewSide View END ViewUpflow Applications Refer to Engineering Handbook for additional informationFront View Furnace FrontSetting an Upflow Unit Leveling BoltFurnace Locations Bottom Leveling Bolt NON−COMBUSTIBLE Floor Opening SizeAdditive Base Floor Opening Size Side ViewTypical Horizontal Ceiling Application Blower Access PanelINTAKE/EXHAUST Connection Support Frame Drain PAN MIN Raised Platform Condensate Line Service Platform Exhaust Pipe GAS ConnectorIntake Pipe Pipe & Fittings Specifications Piping and Fittings SpecificationsFilters Duct SystemOutdoor Termination Kits and Corresponding Equivalencies Model DIAVent Piping Guidelines Minimum Vent Pipe Lengths Maximum Vent Pipe LengthsJoint Cementing Procedure Plastic strapping or a large wire tie Venting PracticesMAX Plug TrapTypical Exhaust Pipe Connections From indoors and flue gases are discharged outdoors Direct Vent applications where combustion air is takenTransition Sweep ELL Intake Debris Screen Page Inside Corner Detail Inches 305mm or 12 in mmUS Installations1 Canadian Installations2 Exhaust Pipe Termination Size Reduction G61MPDirect Vent Roof Termination KIT TOP View Wall Ring KIT with Straight IntakeFront View Using Existing Chimney ANGLE−CUT in Direction G61MP Direct Vent ApplicationCondensate Piping G61MP NON−DIRECT Vent Application Using Existing ChimneySide View NON−DIRECT Vent Wall Ring Termination Condensate Assembly Coupling CLEAN−OUT Access−RINGS CAP HI/LO Screws Vent Nipple TEEGas Piping Furnace Isolate GAS ValveHorizontal Applications Possible Gas Piping Configerations GAS Pipe Capacity − FT3/HR kL/HRPrecautions and Procedures Interior MAKE−UP BOX InstallationElectrical Electrostatic Discharge ESDTypical G61MP Field Wiring Diagram Heat / 2 Cool Cut Intact OFF Cut IntactDIP Switches Function = Error Code Recall H= 24V Humidifier Output L= do not USETWO−STAGE Integrated Control Board Integrated Control Board DIP Switch Settings and Jumpers Typical G61MP Wiring Diagram Integrated Control Board For Your Safety Read Before OperatingUnit Start−Up White Rodgers 36E Series GAS Valve Honeywell VR8205 Series GAS ValveUrning Off Gas to Unit and call your service techni Gas Pressure AdjustmentIf the appliance will not operate, follow the instructions High Altitude Information Order TWO EachOther Unit Adjustments Carbon Monoxide Poisoning HazardPage Blower Performance Data 270In. w.g High Low Cfm Watts 2840 1450 In. w.g High Low Cfm Watts 2720 1385 In. w.g High Low Cfm Watts 2730 1465 Heating Sequence of Operation Service Electrical SHOCK, Fire Or Explosion HazardPage Planned Service Flash Code Status / Error Description Ignition Control Board Diagnostic Codes+ Y Troubleshooting Heating Sequence of Operation On NextHeating Sequence of Operation Thermostat Calls for Heat Status LED − HeartbeatU1.40 microamps Or Heat Demand is SATISFIED. a Five Troubleshooting Cooling Sequence of Operation Cooling Sequence of OperationRepair Parts List Troubleshooting Continuous Fan Sequence of OperationContinuous LOW Speed FAN Sequence of Operation Heat Anticipator Setting? Thermostat Level? Vent Pipe Sizing WorksheetG61MP Start−Up & Performance Check List − LP/Propane High Fire Manifold PressureRequirements for Commonwealth of Massachusetts LY BELOW. Keep Clear of ALL OBSTRUC- Tions
Related manuals
Manual 8 pages 10.79 Kb

G61MP Series Units, Gas Units specifications

Lennox International Inc. has established itself as a leader in the heating and cooling industry, and its G61MP Series Gas Units stand as a testament to the company's commitment to innovation and energy efficiency. These gas units are specifically designed for residential applications and are recognized for their reliability, performance, and advanced technology.

One of the main features of the G61MP Series is its variable speed motor, which offers significantly enhanced comfort over traditional single-stage gas units. This technology allows for precise temperature control and improved humidity management. By adjusting its speed according to the heating demand, the unit minimizes temperature fluctuations, leading to a more consistent indoor climate.

Another notable characteristic of the G61MP Series is its ECM blower motor, which operates quietly and efficiently. This motor not only reduces energy consumption but also enhances the overall comfort of the home by providing a steady flow of warm air without the disruptive noise often associated with traditional gas units.

The G61MP Series units are designed with a focus on energy efficiency, boasting an impressive Annual Fuel Utilization Efficiency (AFUE) rating. This rating indicates that these units convert a significant portion of the fuel they consume into usable heat, resulting in lower energy bills for homeowners. The units are equipped with a modulating gas valve that further optimizes fuel usage by adjusting the gas flow according to the heating needs of the home.

Safety is a paramount consideration in the design of the G61MP Series. These units are built with advanced safety features, including a self-diagnostic control system that continuously monitors the unit’s performance. This system alerts homeowners to any potential issues, allowing for proactive maintenance and ensuring the longevity of the equipment.

The G61MP Series is also designed for ease of installation and servicing. Its compact design allows for flexible placement in various home environments, while the user-friendly access panels simplify routine maintenance tasks.

In conclusion, Lennox International Inc.'s G61MP Series Gas Units deliver a combination of advanced technology, energy efficiency, and reliability, making them an excellent choice for homeowners looking to enhance their heating systems. With features designed to maximize comfort, minimize energy costs, and ensure safety, these units represent a significant advancement in residential heating solutions.