Lennox International Inc G61MP Series Units Equipment in Confined Space − ALL AIR from Inside

Page 7

Z223.1/NFPA 54). This reprinted material is not the com- plete and official position of the ANSI on the referenced subject, which is represented only by the standard in its entirety.

In Canada, refer to the standard CSA B149 installation codes.

CAUTION

Do not install the furnace in a corrosive or contami- nated atmosphere. Meet all combustion and ventila- tion air requirements, as well as all local codes.

All gas-fired appliances require air for the combustion pro- cess. If sufficient combustion air is not available, the fur- nace or other appliance will operate inefficiently and un- safely. Enough air must be provided to meet the needs of all fuel−burning appliances and appliances such as exhaust fans which force air out of the house. When fireplaces, ex- haust fans, or clothes dryers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a downdraft. Insufficient air causes incomplete combustion which can result in carbon monoxide.

which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space ei- ther from inside the building or from outside.

Air from Inside

If the confined space that houses the furnace adjoins a space categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of total input rating of all gas−fired equipment in the confined space. Each opening must be at least 100 square inches (64516 mm2). One opening shall be within 12 inches (305

mm)of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. See figure 3.

EQUIPMENT IN CONFINED SPACE − ALL AIR FROM INSIDE

In addition to providing combustion air, fresh outdoor air di- lutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace compo- nents.

The requirements for providing air for combustion and ven- tilation depend largely on whether the furnace is installed in an unconfined or a confined space.

Unconfined Space

ROOF TERMINATED

EXHAUST PIPE

SIDE WALL

 

TERMINATED EX-

 

HAUST PIPE (ALTER-

 

NATE LOCATION)

G61MP

OPENINGS

(To Adjacent

Unconfined

Space)

An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com- bined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be un- confined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures in the air from outside section.

Confined Space

A confined space is an area with a volume less than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com− bined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.

When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space con- taining the furnace, the return air must be handled by ducts

NOTE − Each opening shall have a free area of at least one square inch per 1,000 Btu (645mm2 per .29kW) per hour of the total input rating of all equipment in the enclosure, but not less than 100 square inches (64516mm.2).

FIGURE 3

Air from Outside

If air from outside is brought in for combustion and ventila- tion, the confined space shall be provided with two perma- nent openings. One opening shall be within 12" (305mm) of the top of the enclosure and one within 12" (305mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a mini- mum free area of 1 square inch per 4,000 Btu (645mm2 per 1.17kW) per hour of total input rating of all equipment in the enclosure. When communicating with the outdoors through horizontal ducts, each opening shall have a mini- mum free area of 1 square inch per 2,000 Btu (645mm2 per .59kW) per total input rating of all equipment in the en- closure (See figure 4).

Page 7

Image 7
Contents Table of Contents Installation InstructionsTOP View G61MP Unit Dimensions − inches mmFront View Side View Sight Blower Glass AssemblyG61MP Parts Arrangement TOP CAPG61MP Gas Furnace Safety InformationDirect Vent Installation NON−DIRECT Vent InstallationUse of Furnace as Construction Heater Combustion, Dilution & Ventilation Air GeneralEquipment in Confined Space − ALL AIR from Inside Equipment operation Installation − Setting EquipmentEquipment in Confined Space − ALL AIR from Outside END View Setting EquipmentFront View Side ViewRefer to Engineering Handbook for additional information Upflow ApplicationsFurnace Front Front ViewNON−COMBUSTIBLE Floor Opening Size Setting an Upflow UnitLeveling Bolt Furnace Locations Bottom Leveling BoltSide View Additive Base Floor Opening SizeTypical Horizontal Ceiling Application Blower Access PanelINTAKE/EXHAUST Connection Support Frame Drain PAN MIN Raised Platform Condensate Line Service Platform Exhaust Pipe GAS ConnectorIntake Pipe Duct System Pipe & Fittings SpecificationsPiping and Fittings Specifications FiltersModel DIA Outdoor Termination Kits and Corresponding EquivalenciesVent Piping Guidelines Maximum Vent Pipe Lengths Minimum Vent Pipe LengthsJoint Cementing Procedure Trap Plastic strapping or a large wire tieVenting Practices MAX PlugTypical Exhaust Pipe Connections From indoors and flue gases are discharged outdoors Direct Vent applications where combustion air is takenTransition Sweep ELL Intake Debris Screen Page Inches 305mm or 12 in mm Inside Corner DetailUS Installations1 Canadian Installations2 TOP View Wall Ring KIT with Straight Intake Exhaust Pipe Termination Size ReductionG61MP Direct Vent Roof Termination KITFront View G61MP Direct Vent Application Using Existing Chimney ANGLE−CUT in DirectionCondensate Piping G61MP NON−DIRECT Vent Application Using Existing ChimneySide View NON−DIRECT Vent Wall Ring Termination Vent Nipple TEE Condensate AssemblyCoupling CLEAN−OUT Access −RINGS CAP HI/LO ScrewsFurnace Isolate GAS Valve Gas PipingGAS Pipe Capacity − FT3/HR kL/HR Horizontal Applications Possible Gas Piping ConfigerationsElectrostatic Discharge ESD Precautions and ProceduresInterior MAKE−UP BOX Installation ElectricalTypical G61MP Field Wiring Diagram Heat / 2 Cool Cut Intact Cut Intact OFFDIP Switches Function = Error Code Recall H= 24V Humidifier Output L= do not USETWO−STAGE Integrated Control Board Integrated Control Board DIP Switch Settings and Jumpers Typical G61MP Wiring Diagram Integrated Control Board For Your Safety Read Before OperatingUnit Start−Up Honeywell VR8205 Series GAS Valve White Rodgers 36E Series GAS ValveUrning Off Gas to Unit and call your service techni Gas Pressure AdjustmentIf the appliance will not operate, follow the instructions Order TWO Each High Altitude InformationCarbon Monoxide Poisoning Hazard Other Unit AdjustmentsPage 270 Blower Performance DataIn. w.g High Low Cfm Watts 2840 1450 In. w.g High Low Cfm Watts 2720 1385 In. w.g High Low Cfm Watts 2730 1465 Heating Sequence of Operation Electrical SHOCK, Fire Or Explosion Hazard ServicePage Planned Service Flash Code Status / Error Description Ignition Control Board Diagnostic Codes+ Y On Next Troubleshooting Heating Sequence of OperationThermostat Calls for Heat Status LED − Heartbeat Heating Sequence of OperationU1.40 microamps Or Heat Demand is SATISFIED. a Five Cooling Sequence of Operation Troubleshooting Cooling Sequence of OperationRepair Parts List Troubleshooting Continuous Fan Sequence of OperationContinuous LOW Speed FAN Sequence of Operation − LP/Propane High Fire Manifold Pressure Heat Anticipator Setting? Thermostat Level?Vent Pipe Sizing Worksheet G61MP Start−Up & Performance Check ListLY BELOW. Keep Clear of ALL OBSTRUC- Tions Requirements for Commonwealth of Massachusetts
Related manuals
Manual 8 pages 10.79 Kb

G61MP Series Units, Gas Units specifications

Lennox International Inc. has established itself as a leader in the heating and cooling industry, and its G61MP Series Gas Units stand as a testament to the company's commitment to innovation and energy efficiency. These gas units are specifically designed for residential applications and are recognized for their reliability, performance, and advanced technology.

One of the main features of the G61MP Series is its variable speed motor, which offers significantly enhanced comfort over traditional single-stage gas units. This technology allows for precise temperature control and improved humidity management. By adjusting its speed according to the heating demand, the unit minimizes temperature fluctuations, leading to a more consistent indoor climate.

Another notable characteristic of the G61MP Series is its ECM blower motor, which operates quietly and efficiently. This motor not only reduces energy consumption but also enhances the overall comfort of the home by providing a steady flow of warm air without the disruptive noise often associated with traditional gas units.

The G61MP Series units are designed with a focus on energy efficiency, boasting an impressive Annual Fuel Utilization Efficiency (AFUE) rating. This rating indicates that these units convert a significant portion of the fuel they consume into usable heat, resulting in lower energy bills for homeowners. The units are equipped with a modulating gas valve that further optimizes fuel usage by adjusting the gas flow according to the heating needs of the home.

Safety is a paramount consideration in the design of the G61MP Series. These units are built with advanced safety features, including a self-diagnostic control system that continuously monitors the unit’s performance. This system alerts homeowners to any potential issues, allowing for proactive maintenance and ensuring the longevity of the equipment.

The G61MP Series is also designed for ease of installation and servicing. Its compact design allows for flexible placement in various home environments, while the user-friendly access panels simplify routine maintenance tasks.

In conclusion, Lennox International Inc.'s G61MP Series Gas Units deliver a combination of advanced technology, energy efficiency, and reliability, making them an excellent choice for homeowners looking to enhance their heating systems. With features designed to maximize comfort, minimize energy costs, and ensure safety, these units represent a significant advancement in residential heating solutions.