Lennox International Inc Gas Units Exhaust Pipe Termination Size Reduction, G61MP

Page 28

Details of Intake and Exhaust Piping Terminations for Direct Vent Installations

NOTE − In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged to outdoors.

Intake and exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In at- tic or closet installations, vertical termination through the roof is preferred. Figures 31 through 39 show typical ter-

TABLE 8

EXHAUST PIPE TERMINATION SIZE REDUCTION

G61MP

Exhaust Pipe Size

Termination Pipe Size

MODEL

 

 

 

 

 

045, 070, −071

2", 2−1/2", 3" or 4"

1−1/2"

090, −091

2", 2−1/2", 3" or 4"

2"

110, −111

2−1/2", 3" or 4"

*2"

135

3" or 4"

*2"

*Approved 3" concentric termination kit terminates with 2−5/8" ID pipe.

minations.

1 − Exhaust and intake exits must be in same pressure zone. Do not exit one through the roof and one on the

Inches(mm)

3(76) MAX.

SIZE TERMINATION PIPE PER TABLE 8.

UNCONDITIONED

side. Also, do not exit the intake on one side and the exhaust on another side of the house or structure.

2 − Intake and exhaust pipes should be placed as close together as possible at termination end (refer to il- lustrations). Maximum separation is 3" (76mm) on roof terminations and 6" (152mm) on side wall termina- tions.

3 − If necessary, install a field−provided reducer to adapt larger vent pipe size to termination pipe size.

4 − On roof terminations, the intake piping should termi- nate straight down using two 90° elbows (See figure

8" (203) MIN

12" (305) ABOVE AVERAGE SNOW ACCUMULATION

3" (76) OR 2" (51) PVC

PROVIDE SUPPORT

FOR INTAKE AND EXHAUST LINES

ATTIC SPACE

1/2" (13) FOAM INSULATION IN UNCONDITIONED SPACE

31).

5 − Exhaust piping must terminate straight out or up as shown. In rooftop applications, a reducer may be re- quired on the exhaust piping at the point where it exits the structure to improve the velocity of exhaust away from the intake piping. See table 8.

NOTE − Care must be taken to avoid recirculation of exhaust back into intake pipe.

6 − On field supplied terminations for side wall exits, ex- haust piping should extend a minimum of 12 inches (305mm) beyond the outside wall. Intake piping should be as short as possible. See figure 32.

7 − On field supplied terminations, a minimum separation distance between the end of the exhaust pipe and the end of the intake pipe is 8 inches (203mm).

8 − If intake and exhaust piping must be run up a side wall to position above snow accumulation or other obstruc- tions, piping must be supported every 3 ft. (.9m) as shown in figure 22. Refer to figure 35 for proper piping method. In addition, WTK wall termination kit must be extended for use in this application. See figure 38. When exhaust and intake piping must be run up an outside wall, the exhaust piping is reduced to 1−1/2" (38mm) after the final elbow. The intake piping may be equipped with a 90° elbow turndown. Using turndown will add 5 feet (1.5m) to the equivalent length of the pipe.

9 − Based on the recommendation of the manufacturer, a multiple furnace installation may use a group of up to four termination kits WTK assembled together hori- zontally, as shown in figure 37.

DIRECT VENT ROOF TERMINATION KIT

(15F75 or 44J41)

FIGURE 31

 

12" (305) MAX.

 

 

1/2" (13) ARMAFLEX

(unless supported)

 

 

 

 

INSULATION IN

 

 

1/2" (13)

UNCONDITIONED SPACE

 

 

 

 

ARMAFLEX

 

 

INSULATION

FIELD−

 

 

SIZE

PROVIDED

 

 

 

 

TERMINA-

REDUCER MAY

6" (152)

TION PIPE

BE REQUIRED

MAXI-

PER TABLE

TO ADAPT

MUM

 

 

8.

LARGER VENT

 

 

 

 

 

PIPE SIZE TO

 

 

 

TERMINATION

 

 

 

OUTSIDE

8" (203)

 

Inches (mm)

WALL

 

 

 

MINIMUM

 

 

2" (51)

 

 

 

 

 

PVC

 

 

 

COUPLING

 

 

 

TOP VIEW WALL RING KIT WITH STRAIGHT INTAKE

 

(15F74)

 

 

1/2 (13) ARMAFLEX

12 (305) MAX.

 

 

INSULATION IN

 

 

 

 

 

UNCONDITIONED

 

 

1/2" (13)

SPACE

 

 

ARMAFLEX

 

 

 

INSULATION

FIELD−

 

 

 

PROVIDED

 

 

 

REDUCER MAY

 

 

 

BE REQUIRED

 

 

 

TO ADAPT

 

 

SIZE

LARGER VENT

6 (152)

TERMINATION PIPE

PIPE SIZE TO

MAXIMUM

 

PER TABLE 8.

TERMINATION

 

 

 

 

4 (102)

 

 

Inches (mm) OUTSIDE

MINIMUM

 

 

 

 

 

WALL

 

 

 

TOP VIEW WALL RING KIT WITH 90° ELBOW ON INTAKE

 

(15F74)

 

 

FIGURE 32

Page 28

Image 28
Contents Installation Instructions Table of ContentsTOP View G61MP Unit Dimensions − inches mmFront View Side View Glass Assembly G61MP Parts ArrangementTOP CAP Sight BlowerSafety Information Direct Vent Installation NON−DIRECT VentInstallation G61MP Gas FurnaceUse of Furnace as Construction Heater General Combustion, Dilution & Ventilation AirEquipment in Confined Space − ALL AIR from Inside Equipment operation Installation − Setting EquipmentEquipment in Confined Space − ALL AIR from Outside Setting Equipment Front ViewSide View END ViewUpflow Applications Refer to Engineering Handbook for additional informationFront View Furnace FrontSetting an Upflow Unit Leveling BoltFurnace Locations Bottom Leveling Bolt NON−COMBUSTIBLE Floor Opening SizeAdditive Base Floor Opening Size Side ViewTypical Horizontal Ceiling Application Blower Access PanelINTAKE/EXHAUST Connection Support Frame Drain PAN MIN Raised Platform Condensate Line Service Platform Exhaust Pipe GAS ConnectorIntake Pipe Pipe & Fittings Specifications Piping and Fittings SpecificationsFilters Duct SystemOutdoor Termination Kits and Corresponding Equivalencies Model DIAVent Piping Guidelines Minimum Vent Pipe Lengths Maximum Vent Pipe LengthsJoint Cementing Procedure Plastic strapping or a large wire tie Venting PracticesMAX Plug TrapTypical Exhaust Pipe Connections From indoors and flue gases are discharged outdoors Direct Vent applications where combustion air is takenTransition Sweep ELL Intake Debris Screen Page Inside Corner Detail Inches 305mm or 12 in mmUS Installations1 Canadian Installations2 Exhaust Pipe Termination Size Reduction G61MPDirect Vent Roof Termination KIT TOP View Wall Ring KIT with Straight IntakeFront View Using Existing Chimney ANGLE−CUT in Direction G61MP Direct Vent ApplicationCondensate Piping G61MP NON−DIRECT Vent Application Using Existing ChimneySide View NON−DIRECT Vent Wall Ring Termination Condensate Assembly Coupling CLEAN−OUT Access−RINGS CAP HI/LO Screws Vent Nipple TEEGas Piping Furnace Isolate GAS ValveHorizontal Applications Possible Gas Piping Configerations GAS Pipe Capacity − FT3/HR kL/HRPrecautions and Procedures Interior MAKE−UP BOX InstallationElectrical Electrostatic Discharge ESDTypical G61MP Field Wiring Diagram Heat / 2 Cool Cut Intact OFF Cut IntactDIP Switches Function = Error Code Recall H= 24V Humidifier Output L= do not USETWO−STAGE Integrated Control Board Integrated Control Board DIP Switch Settings and Jumpers Typical G61MP Wiring Diagram Integrated Control Board For Your Safety Read Before OperatingUnit Start−Up White Rodgers 36E Series GAS Valve Honeywell VR8205 Series GAS ValveUrning Off Gas to Unit and call your service techni Gas Pressure AdjustmentIf the appliance will not operate, follow the instructions High Altitude Information Order TWO EachOther Unit Adjustments Carbon Monoxide Poisoning HazardPage Blower Performance Data 270In. w.g High Low Cfm Watts 2840 1450 In. w.g High Low Cfm Watts 2720 1385 In. w.g High Low Cfm Watts 2730 1465 Heating Sequence of Operation Service Electrical SHOCK, Fire Or Explosion HazardPage Planned Service Flash Code Status / Error Description Ignition Control Board Diagnostic Codes+ Y Troubleshooting Heating Sequence of Operation On NextHeating Sequence of Operation Thermostat Calls for Heat Status LED − HeartbeatU1.40 microamps Or Heat Demand is SATISFIED. a Five Troubleshooting Cooling Sequence of Operation Cooling Sequence of OperationRepair Parts List Troubleshooting Continuous Fan Sequence of OperationContinuous LOW Speed FAN Sequence of Operation Heat Anticipator Setting? Thermostat Level? Vent Pipe Sizing WorksheetG61MP Start−Up & Performance Check List − LP/Propane High Fire Manifold PressureRequirements for Commonwealth of Massachusetts LY BELOW. Keep Clear of ALL OBSTRUC- Tions
Related manuals
Manual 8 pages 10.79 Kb

G61MP Series Units, Gas Units specifications

Lennox International Inc. has established itself as a leader in the heating and cooling industry, and its G61MP Series Gas Units stand as a testament to the company's commitment to innovation and energy efficiency. These gas units are specifically designed for residential applications and are recognized for their reliability, performance, and advanced technology.

One of the main features of the G61MP Series is its variable speed motor, which offers significantly enhanced comfort over traditional single-stage gas units. This technology allows for precise temperature control and improved humidity management. By adjusting its speed according to the heating demand, the unit minimizes temperature fluctuations, leading to a more consistent indoor climate.

Another notable characteristic of the G61MP Series is its ECM blower motor, which operates quietly and efficiently. This motor not only reduces energy consumption but also enhances the overall comfort of the home by providing a steady flow of warm air without the disruptive noise often associated with traditional gas units.

The G61MP Series units are designed with a focus on energy efficiency, boasting an impressive Annual Fuel Utilization Efficiency (AFUE) rating. This rating indicates that these units convert a significant portion of the fuel they consume into usable heat, resulting in lower energy bills for homeowners. The units are equipped with a modulating gas valve that further optimizes fuel usage by adjusting the gas flow according to the heating needs of the home.

Safety is a paramount consideration in the design of the G61MP Series. These units are built with advanced safety features, including a self-diagnostic control system that continuously monitors the unit’s performance. This system alerts homeowners to any potential issues, allowing for proactive maintenance and ensuring the longevity of the equipment.

The G61MP Series is also designed for ease of installation and servicing. Its compact design allows for flexible placement in various home environments, while the user-friendly access panels simplify routine maintenance tasks.

In conclusion, Lennox International Inc.'s G61MP Series Gas Units deliver a combination of advanced technology, energy efficiency, and reliability, making them an excellent choice for homeowners looking to enhance their heating systems. With features designed to maximize comfort, minimize energy costs, and ensure safety, these units represent a significant advancement in residential heating solutions.