Lennox International Inc G61MP Series Units, Gas Units installation instructions Planned Service

Page 55

Planned Service

A service technician should check the following items dur- ing an annual inspection. Power to the unit must be shut off for safety.

Fresh air grilles and louvers (on the unit and in the room where the furnace is installed) − Must be open and unob- structed to provide combustion air.

Burners − Must be inspected for rust, dirt, or signs of water.

Vent pipe − Must be inspected for signs of water, damaged, cracked or sagging pipe, or disconnected joints.

Unit appearance − Must be inspected for rust, dirt, signs of water, burnt or damaged wires, or components.

Blower access door − Must be properly in place and pro- vide a seal between the return air and the room where the furnace is installed.

Return air duct − Must be properly attached and provide an air seal to the unit.

Operating performance − Unit must be observed during operation to monitor proper performance of the unit and the vent system.

Combustion gases − Flue products must be analyzed and compared to the unit specifications.

Problems detected during the inspection may make it nec- essary to temporarily shut down the furnace until the items can be repaired or replaced.

Instruct the homeowners to pay attention to their furnace. Situations can arise between annual furnace in- spections that may result in unsafe operation. For instance, items innocently stored next to the furnace may obstruct the combustion air supply. This could cause incomplete combustion and the production of carbon monoxide gas.

Page 55

Image 55
Contents Table of Contents Installation InstructionsTOP View G61MP Unit Dimensions − inches mmFront View Side View Sight Blower Glass AssemblyG61MP Parts Arrangement TOP CAPG61MP Gas Furnace Safety InformationDirect Vent Installation NON−DIRECT Vent InstallationUse of Furnace as Construction Heater Combustion, Dilution & Ventilation Air GeneralEquipment in Confined Space − ALL AIR from Inside Equipment operation Installation − Setting EquipmentEquipment in Confined Space − ALL AIR from Outside END View Setting EquipmentFront View Side ViewRefer to Engineering Handbook for additional information Upflow ApplicationsFurnace Front Front ViewNON−COMBUSTIBLE Floor Opening Size Setting an Upflow UnitLeveling Bolt Furnace Locations Bottom Leveling BoltSide View Additive Base Floor Opening SizeTypical Horizontal Ceiling Application Blower Access PanelINTAKE/EXHAUST Connection Support Frame Drain PAN MIN Raised Platform Condensate Line Service Platform Exhaust Pipe GAS ConnectorIntake Pipe Duct System Pipe & Fittings SpecificationsPiping and Fittings Specifications FiltersModel DIA Outdoor Termination Kits and Corresponding EquivalenciesVent Piping Guidelines Maximum Vent Pipe Lengths Minimum Vent Pipe LengthsJoint Cementing Procedure Trap Plastic strapping or a large wire tieVenting Practices MAX PlugTypical Exhaust Pipe Connections From indoors and flue gases are discharged outdoors Direct Vent applications where combustion air is takenTransition Sweep ELL Intake Debris Screen Page Inches 305mm or 12 in mm Inside Corner DetailUS Installations1 Canadian Installations2 TOP View Wall Ring KIT with Straight Intake Exhaust Pipe Termination Size ReductionG61MP Direct Vent Roof Termination KITFront View G61MP Direct Vent Application Using Existing Chimney ANGLE−CUT in DirectionCondensate Piping G61MP NON−DIRECT Vent Application Using Existing ChimneySide View NON−DIRECT Vent Wall Ring Termination Vent Nipple TEE Condensate AssemblyCoupling CLEAN−OUT Access −RINGS CAP HI/LO ScrewsFurnace Isolate GAS Valve Gas PipingGAS Pipe Capacity − FT3/HR kL/HR Horizontal Applications Possible Gas Piping ConfigerationsElectrostatic Discharge ESD Precautions and ProceduresInterior MAKE−UP BOX Installation ElectricalTypical G61MP Field Wiring Diagram Heat / 2 Cool Cut Intact Cut Intact OFFDIP Switches Function = Error Code Recall H= 24V Humidifier Output L= do not USETWO−STAGE Integrated Control Board Integrated Control Board DIP Switch Settings and Jumpers Typical G61MP Wiring Diagram Integrated Control Board For Your Safety Read Before OperatingUnit Start−Up Honeywell VR8205 Series GAS Valve White Rodgers 36E Series GAS ValveUrning Off Gas to Unit and call your service techni Gas Pressure AdjustmentIf the appliance will not operate, follow the instructions Order TWO Each High Altitude InformationCarbon Monoxide Poisoning Hazard Other Unit AdjustmentsPage 270 Blower Performance DataIn. w.g High Low Cfm Watts 2840 1450 In. w.g High Low Cfm Watts 2720 1385 In. w.g High Low Cfm Watts 2730 1465 Heating Sequence of Operation Electrical SHOCK, Fire Or Explosion Hazard ServicePage Planned Service Flash Code Status / Error Description Ignition Control Board Diagnostic Codes+ Y On Next Troubleshooting Heating Sequence of OperationThermostat Calls for Heat Status LED − Heartbeat Heating Sequence of OperationU1.40 microamps Or Heat Demand is SATISFIED. a Five Cooling Sequence of Operation Troubleshooting Cooling Sequence of OperationRepair Parts List Troubleshooting Continuous Fan Sequence of OperationContinuous LOW Speed FAN Sequence of Operation − LP/Propane High Fire Manifold Pressure Heat Anticipator Setting? Thermostat Level?Vent Pipe Sizing Worksheet G61MP Start−Up & Performance Check ListLY BELOW. Keep Clear of ALL OBSTRUC- Tions Requirements for Commonwealth of Massachusetts
Related manuals
Manual 8 pages 10.79 Kb

G61MP Series Units, Gas Units specifications

Lennox International Inc. has established itself as a leader in the heating and cooling industry, and its G61MP Series Gas Units stand as a testament to the company's commitment to innovation and energy efficiency. These gas units are specifically designed for residential applications and are recognized for their reliability, performance, and advanced technology.

One of the main features of the G61MP Series is its variable speed motor, which offers significantly enhanced comfort over traditional single-stage gas units. This technology allows for precise temperature control and improved humidity management. By adjusting its speed according to the heating demand, the unit minimizes temperature fluctuations, leading to a more consistent indoor climate.

Another notable characteristic of the G61MP Series is its ECM blower motor, which operates quietly and efficiently. This motor not only reduces energy consumption but also enhances the overall comfort of the home by providing a steady flow of warm air without the disruptive noise often associated with traditional gas units.

The G61MP Series units are designed with a focus on energy efficiency, boasting an impressive Annual Fuel Utilization Efficiency (AFUE) rating. This rating indicates that these units convert a significant portion of the fuel they consume into usable heat, resulting in lower energy bills for homeowners. The units are equipped with a modulating gas valve that further optimizes fuel usage by adjusting the gas flow according to the heating needs of the home.

Safety is a paramount consideration in the design of the G61MP Series. These units are built with advanced safety features, including a self-diagnostic control system that continuously monitors the unit’s performance. This system alerts homeowners to any potential issues, allowing for proactive maintenance and ensuring the longevity of the equipment.

The G61MP Series is also designed for ease of installation and servicing. Its compact design allows for flexible placement in various home environments, while the user-friendly access panels simplify routine maintenance tasks.

In conclusion, Lennox International Inc.'s G61MP Series Gas Units deliver a combination of advanced technology, energy efficiency, and reliability, making them an excellent choice for homeowners looking to enhance their heating systems. With features designed to maximize comfort, minimize energy costs, and ensure safety, these units represent a significant advancement in residential heating solutions.