Lennox International Inc 506510-01 installation instructions Alert Status

Page 36

Outdoor Main Control

 

 

 

 

LEDs

 

 

 

 

 

 

Condition

Possible Cause(s)

 

Solution

DS11

DS14 Red

 

 

 

 

 

Green

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 Fast

Heating Low

 

 

 

OFF

Flash then

 

 

 

Capacity

 

 

 

 

Pause

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 Fast

Heating High

 

 

 

OFF

Flash then

 

 

 

Capacity

 

 

 

 

Pause

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 Fast

 

 

 

 

ON

Flash then

Defrost

 

 

 

 

Pause

 

These are codes that show status of operation whether in low stage or high stage, heating or cooling,

 

 

 

1 Fast

 

Cooling Low

defrost or in the EDA mode.

 

 

 

 

 

 

Flash then

OFF

 

 

 

Capacity

 

 

 

Pause

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 Fast

 

Cooling High

 

 

 

Flash then

OFF

 

 

 

Capacity

 

 

 

Pause

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 Fast

 

Dehumidification

 

 

 

Flash then

ON

 

 

 

Mode

 

 

 

Pause

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALERT STATUS

 

 

 

 

 

 

OFF

SLOW

Low Pressure

1 Restricted air flow over

 

 

Flash

Fault

indoor or outdoor coil.

 

 

 

1 Remove any blockages or restrictions from coils and/or fans. Check

 

 

 

 

 

 

2 Improper refrigerant

 

 

Low Pressure

 

indoor and outdoor fan motor for proper current draws.

OFF

ON

charge in system.

 

 

 

Switch Lockout

2 Check system charge using approach and subcooling temperatures.

 

 

3 Improper metering de-

 

 

 

3

Check system operating pressures and compare to unit charging

SLOW

 

High Pressure

vice installed or incorrect

OFF

 

charts.

operation of metering de-

 

Flash

Fault

 

4

Make sure all pressure switches and sensors have secure connec-

 

vice.

 

 

 

 

 

 

 

tions to system to prevent refrigerant leaks or errors in pressure and

 

 

High Pressure

4 Incorrect or improper

 

 

 

 

temperature measurements.

ON

OFF

Discharge Sensor

sensor location or con-

 

 

 

 

 

Lockout

nection to system.

 

 

 

 

 

 

 

 

SLOW

ON

Discharge Line

This code detects high discharge temperatures. If the discharge line temperature exceeds a temperature

Flash

Temperature Fault

 

 

 

of 279ºF (137ºC) during compressor operation, the control will de−energize the compressor contactor

 

 

Discharge Line

output (and the defrost output if active). The compressor will remain off until the discharge temperature

FAST

 

has dropped below 225ºF (107ºC). See Figure 21 for further details concerning lockouts and reset

ON

Temperature

Flash

procedures.

 

 

 

Lockout

 

 

 

 

 

 

 

 

 

 

 

OFF

Fast Flash

Discharge Sensor

The control detects open or short sensor or out of temperature sensor range. This fault is detected by

Fault

allowing the unit to run for 90 seconds before checking sensor resistance. If the sensor resistance is

 

 

not within range after 90 seconds, the control will raise the alarm.

 

 

 

 

 

 

 

 

 

Fast simultaneous

OEM Mode

Factory Test Mode.

 

 

flashing of DS11, DS13,

 

 

 

 

 

 

DS14 and DS15

 

 

 

 

 

 

 

 

 

 

Page 36

506510−01

Image 36
Contents Table of Contents GeneralShipping and Packing List AIR ConditionerUnit Dimensions − Inches mm and Parts Arrangement Side View Access ViewModel Number Identification Base with Elongated LegsPLUMBING, Switches and Sensor Components Typical Unit Parts ArrangementControl BOX Operating Gauge Set and Service Valves Using Manifold Gauge SETOperating Service Valves Torque RequirementsTo Access Service Port Operating Angle Type Service ValveOperating Ball Type Service Valve Reinstall Stem CapRecovering Recovering Refrigerant from Existing SystemNew Outdoor Unit Placement Clearance on ALL Sides Minimum Clearance Above UnitMinimum Clearance Between TWO Units Positioning ConsiderationsElevating the Unit Stabilizing Unit on Uneven SurfacesRoof Mounting Outside Unit Placement Elevated Slab Mounting using Feet ExtendersSlab Mounting at Ground Level Stabilizing Unit on Uneven SurfacesRemoving and Installing Panels Access Panel RemovalAccess and Louvered Louvered Panel InstallationNew or Replacement Line Set Refrigerant Line SETLine SET Brazing Flushing Flushing the SystemUncased Coil Shown Line SET and Indoor Coil 1Sensing Bulb Installation Equalizer Line InstallationFlushing Line SET and Indoor Coil 2 Leak Testing the System Installing Isolation GrommetsLeak Test Line SET and Indoor CoilEvacuating Evacuating the SystemSize Circuit and Install Disconnect 2INSTALL ThermostatElectrical 24VAC Transformer3ROUTE Control Wires 4ROUTE High Voltage and Ground WiresTypical XC17 Wiring Main Control Jumpers and Terminals Main Control AGEMain Control Jumpers and Terminals FANField Control Wiring Flat metal jumperOn−board link Connections for Testing and Charging Gauge SETServicing Units Delivered Void of Charge Unit Start−UpAirflow Indoor CoilAction Weigh Charge METHOD? Determine byRequirements Calculating System Charge for Outdoor Unit Void of ChargeApproach SubcoolingTest and Charge Method Operating and Temperature Pressures HFC−410A Temperature Fahrenheit PsigSystem Operation Test Pins Function Ambient Sensor Temperature / Resistance Range High Discharge Sensor Temperature / Resistance Range Sensor Temperature / Resistance Range Resetting LED Alert CodesMain Control LED Alert Codes System LED Alert CodesAlert Status Compressor LED Alert Codes Detected in RUN High Pressure Switch Operation Low Pressure Switch Operation High Discharge Temperature Sensor Operation Maintenance Verifying Jumper Settings J2FAN Motor Control and Start UP Verifying LED Status CodesLED Codes and Sequence of Operations Fan Motor Board Unit LED CodesControl Panel Testing for External Power to Fan Control Fan Motor Test FAN Motor Surge Protection Fan Motor Surge Protection DeviceXC17 Start−Up and Performance Checklist Cooling ModeStart UP Checks Subcooling