Lennox International Inc Dave Lennox Signature Collection XC17 Air Conditioner Approach

Page 29

APPROACH

TEST AND CHARGE METHOD

65ºF (18.3ºC) and Above

If refrigerant added or removed, retest to confirm that unit is properly charged

If value is greater than shown (high approach), add refrigerant; if less than shown (liquid temp too close to ambient temp, low approach), remove refrigerant.

APPº (Approach) Values(F:+/−1.0° [C: +/−0.6°])*

 

 

 

Models

 

 

ºF (ºC)*

−024

−030

−036

−042 . . . −048 . . . −060

 

Any

10 (5.6)

10 (5.6)

6 (3.3)

10 (5.6) . 8 (4.4) . . 8 (4.4)

*Temperature of air entering outdoor coil

*These approach values are also listed on the unit charging sticker 580005−01 located on the access panel.

1.Confirm proper airflow across coil using Figure 12.

2.Compare unit pressures with Table 4, Normal Operating Pressures.

3.Use APPROACH to correctly charge unit or to verify the charge is correct.

4.Set thermostat to call for heat (must have a cooling load between 70-80ºF (21−26ºC).

5.Connect gauge set.

6.When heat demand is satisfied, set thermostat to call for cooling.

7.Allow temperatures and pressures to stabilize.

8.Record outdoor ambient temperature: AMBº =_________

9.Record line temperature: LIQº = __________

10.Subtract to determine approach (APPº): LIQº_____ − AMBº _____ = APPº_____

11.Compare results with table to the left.

Figure 15. Using Approach Test and Charge Method

SUBCOOLING

TEST AND CHARGE METHOD

65ºF (18.3ºC) and Above

1.

Confirm proper airflow across coil using Figure 12.

2.

Compare unit pressures with Table 4, Normal Operating Pressures.

CARDBOARD OR PLASTIC SHEET

BLOCK OUTDOOR COIL: [sometimes necessary with lower temperatures] Use cardboard or plastic sheet to restrict the airflow through the outdoor coil to achieve pressures from 325−375 psig (2240−2585 kPa). Higher pressures are needed to check charge. Block equal sections of air intake panels and move coverings sideways until the liquid pressure is in the above noted ranges.

3.

Use SUBCOOLING to correctly charge unit or to verify the charge is

 

correct.

4.

Set thermostat to call for heat (must have a cooling load between 70-80ºF

 

(21−26ºC)

5.

Connect gauge set

6.

Measure outdoor ambient temperature

7.

When heat demand is satisfied, set thermostat to call for cooling

If refrigerant added or removed, verify charge using the approach method

If value is greater than shown, remove refrigerant; if less than shown, add refrigerant

SCº (Subcooling) Values (F:+/−1.0° [C: +/−0.6°])

 

 

 

Models

 

 

ºF (ºC)*

−024

−030

−036

−042 . . . −048 . . . −060

 

Any

4 (2.2)

4 (2.2)

7 (3.9)

5 (2.8) . 6 (3.3) . . 6 (3.3)

*Temperature of air entering outdoor coil

*These subcooling values are also listed on the unit charging sticker 580005−01 located on the access panel.

8.

Allow temperatures and pressures to stabilize.

 

NOTE − If necessary, block outdoor coil to maintain 325 − 375 psig.

9.

Record liquid line temperature:

 

LIQº = ______

10.

Measure liquid line pressure and use the value to determine saturation

 

temperature (see Table 5):

 

SATº = ______

11.

Subtract to determine subcooling (SCº):

 

SATº_____ − LIQº _____ = SCº _____

12.

Compare results with table to the left.

Figure 16. Using Subcooling Test and Charge Method

Page 29

XC17 SERIES

Image 29
Contents General Table of ContentsShipping and Packing List AIR ConditionerSide View Access View Unit Dimensions − Inches mm and Parts ArrangementModel Number Identification Base with Elongated LegsControl BOX PLUMBING, Switches and Sensor ComponentsTypical Unit Parts Arrangement Using Manifold Gauge SET Operating Gauge Set and Service ValvesOperating Service Valves Torque RequirementsOperating Angle Type Service Valve To Access Service PortOperating Ball Type Service Valve Reinstall Stem CapRecovering Refrigerant from Existing System RecoveringClearance on ALL Sides Minimum Clearance Above Unit New Outdoor Unit PlacementMinimum Clearance Between TWO Units Positioning ConsiderationsRoof Mounting Elevating the UnitStabilizing Unit on Uneven Surfaces Elevated Slab Mounting using Feet Extenders Outside Unit PlacementSlab Mounting at Ground Level Stabilizing Unit on Uneven SurfacesAccess Panel Removal Removing and Installing PanelsAccess and Louvered Louvered Panel InstallationRefrigerant Line SET New or Replacement Line SetLine SET Brazing Flushing the System FlushingUncased Coil Shown Line SET and Indoor Coil 1Flushing Line SET and Indoor Coil 2 Sensing Bulb InstallationEqualizer Line Installation Installing Isolation Grommets Leak Testing the SystemLine SET and Indoor Coil Leak TestEvacuating the System Evacuating2INSTALL Thermostat Size Circuit and Install DisconnectElectrical 24VAC Transformer4ROUTE High Voltage and Ground Wires 3ROUTE Control WiresTypical XC17 Wiring Main Control AGE Main Control Jumpers and TerminalsFAN Main Control Jumpers and TerminalsFlat metal jumper Field Control WiringOn−board link Gauge SET Connections for Testing and ChargingServicing Units Delivered Void of Charge Unit Start−UpAction AirflowIndoor Coil Charge METHOD? Determine by WeighRequirements Calculating System Charge for Outdoor Unit Void of ChargeTest and Charge Method ApproachSubcooling HFC−410A Temperature Fahrenheit Psig Operating and Temperature PressuresSystem Operation Test Pins Function Ambient Sensor Temperature / Resistance Range High Discharge Sensor Temperature / Resistance Range Resetting LED Alert Codes Sensor Temperature / Resistance RangeMain Control LED Alert Codes System LED Alert CodesAlert Status Compressor LED Alert Codes Detected in RUN High Pressure Switch Operation Low Pressure Switch Operation High Discharge Temperature Sensor Operation Verifying Jumper Settings J2 MaintenanceFAN Motor Control and Start UP Verifying LED Status CodesFan Motor Board Unit LED Codes LED Codes and Sequence of OperationsControl Panel Testing for External Power to Fan Control Fan Motor Test Fan Motor Surge Protection Device FAN Motor Surge ProtectionStart UP Checks XC17 Start−Up and Performance ChecklistCooling Mode Subcooling