Lennox International Inc Dave Lennox Signature Collection XC17 Air Conditioner Electrical

Page 19
MAIN FUSE BOX/
BREAKER PANEL

IMPORTANT

Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns.

WARNING

Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.

Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are defined as any gas that will not condense under

temperatures and pressures present during operation of an air conditioning system. Non−condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts.

Electrical

In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).

Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.

24VAC TRANSFORMER

Use the transformer provided with the furnace or air handler for low-voltage control power (24VAC − 40 VA minimum)

SIZE CIRCUIT AND INSTALL DISCONNECT

1ReferSWITCHto the unit nameplate for minimum circuit ampacity, and maximum fuse or circuit breaker (HACR per NEC). Install power wiring and properly sized disconnect switch.

SERVICE

DISCONNECT

SWITCH

2INSTALL THERMOSTAT

Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight or drafts.

THERMOSTAT

5FEET (1.5M)

NOTE Units are approved for use only with copper conductors. Ground unit at disconnect switch or to an earth ground.

NOTE 24VAC, Class II circuit connections are made in the control panel.

WARNING

Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.

Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.

CAUTION

ELECTROSTATIC DISCHARGE

(ESD)

Precautions and Procedures

Electrostatic discharge can affect electronic components. Take precautions during unit installation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an unpainted unit surface before performing any service procedure

Page 19

XC17 SERIES

Image 19
Contents AIR Conditioner Table of ContentsGeneral Shipping and Packing ListBase with Elongated Legs Unit Dimensions − Inches mm and Parts ArrangementSide View Access View Model Number IdentificationTypical Unit Parts Arrangement PLUMBING, Switches and Sensor ComponentsControl BOX Torque Requirements Operating Gauge Set and Service ValvesUsing Manifold Gauge SET Operating Service ValvesReinstall Stem Cap To Access Service PortOperating Angle Type Service Valve Operating Ball Type Service ValveRecovering Refrigerant from Existing System RecoveringPositioning Considerations New Outdoor Unit PlacementClearance on ALL Sides Minimum Clearance Above Unit Minimum Clearance Between TWO UnitsStabilizing Unit on Uneven Surfaces Elevating the UnitRoof Mounting Stabilizing Unit on Uneven Surfaces Outside Unit PlacementElevated Slab Mounting using Feet Extenders Slab Mounting at Ground LevelLouvered Panel Installation Removing and Installing PanelsAccess Panel Removal Access and LouveredRefrigerant Line SET New or Replacement Line SetLine SET Brazing Line SET and Indoor Coil 1 FlushingFlushing the System Uncased Coil ShownEqualizer Line Installation Sensing Bulb InstallationFlushing Line SET and Indoor Coil 2 Installing Isolation Grommets Leak Testing the SystemLine SET and Indoor Coil Leak TestEvacuating the System Evacuating24VAC Transformer Size Circuit and Install Disconnect2INSTALL Thermostat Electrical4ROUTE High Voltage and Ground Wires 3ROUTE Control WiresTypical XC17 Wiring Main Control AGE Main Control Jumpers and TerminalsFAN Main Control Jumpers and TerminalsFlat metal jumper Field Control WiringOn−board link Unit Start−Up Connections for Testing and ChargingGauge SET Servicing Units Delivered Void of ChargeIndoor Coil AirflowAction Calculating System Charge for Outdoor Unit Void of Charge WeighCharge METHOD? Determine by RequirementsSubcooling ApproachTest and Charge Method HFC−410A Temperature Fahrenheit Psig Operating and Temperature PressuresSystem Operation Test Pins Function Ambient Sensor Temperature / Resistance Range High Discharge Sensor Temperature / Resistance Range System LED Alert Codes Sensor Temperature / Resistance RangeResetting LED Alert Codes Main Control LED Alert CodesAlert Status Compressor LED Alert Codes Detected in RUN High Pressure Switch Operation Low Pressure Switch Operation High Discharge Temperature Sensor Operation Verifying LED Status Codes MaintenanceVerifying Jumper Settings J2 FAN Motor Control and Start UPFan Motor Board Unit LED Codes LED Codes and Sequence of OperationsControl Panel Testing for External Power to Fan Control Fan Motor Test Fan Motor Surge Protection Device FAN Motor Surge ProtectionCooling Mode XC17 Start−Up and Performance ChecklistStart UP Checks Subcooling