Lennox International Inc Dave Lennox Signature Collection XC17 Air Conditioner, 506510-01

Page 11

New or Replacement Line Set

REFRIGERANT LINE SET

This section provides information on installation or replacement of existing line set. If new or replacement line set is not being installed then proceed to Brazing Connections on page 13.

IMPORTANT

Lennox highly recommends changing line set when converting the existing system from HCFC−22 to HFC−410A. If that is not possible and the line set is the proper size as reference in Table 2, use the procedure outlined under Flushing the System on page 13.

If refrigerant lines are routed through a wall, then seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds. See Figure 5 for recommended installation practices. Also, consider the following when placing and installing a high−efficiency outdoor unit.

Liquid lines that meter the refrigerant, such as RFC1 liquid lines, must not be used in this application. Existing line set of proper size as listed in Table 2 may be reused. If system was previously charged with HCFC−22 refrigerant, then existing line set must be flushed (see Flushing the System on page 14).

Field refrigerant piping consists of liquid and vapor lines from the outdoor unit to the indoor unit coil (braze connections). Use Lennox L15 (sweat, non−flare) series line set, or field−fabricated refrigerant line sizes as listed in Table 2.

Table 2. Refrigerant Line Set

 

Field

Recommended Line Set

 

Connections

 

 

 

 

Model

 

 

 

 

 

 

 

 

 

L15

Size

Liquid

Vapor

Liquid

Vapor

Line Sets

 

 

Line

Line

Line

Line

 

Feet (Meters)

 

 

 

 

 

 

 

 

 

 

 

−024

3/8

3/4

3/8

3/4

L15−41

 

 

(10)

(19)

(10)

(19)

15 − 50’ (5 − 15)

−030

 

 

 

 

 

 

 

 

 

 

 

−036

3/8

7/8

3/8

7/8

 

(10)

(22)

(10)

(22)

 

 

 

 

 

 

 

 

L15−65

 

 

 

 

 

−042

3/8

7/8

3/8

7/8

15 − 50’ (5 − 15)

 

 

−048

(10)

(22)

(10)

(22)

 

 

 

 

 

 

 

 

 

 

 

 

−060

3/8

1−1/8

3/8

1−1/8

Field Fabricated

(10)

(29)

(10)

(29)

 

 

 

 

 

 

 

 

NOTE

1−1/8" adapter

NOTE When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, CORP. 9351−L9, or contact Lennox Technical Support Product Applications for assistance.

IMPORTANT

Mineral oils are not compatible with HFC−410A. If oil must be added, it must be a Polyol ester oil.

The compressor is charged with sufficient Polyol ester oil for line set lengths up to 50 feet. If line set lengths longer than 50 feet will be required, all one (1) ounce of oil for every additional 10 feet of line set. Do not add any more than seven (7) ounces of oil.

Recommended topping−off POE oils are Mobil EAL ARCTIC 22 CC or ICI EMKARATEt RL32CF.

To obtain the correct information from Lennox, be sure to communicate the following information:

SModel (XC17) and size of unit (e.g. −036).

SLine set diameters for the unit being installed as listed in Table 2 and total length of installation.

SNumber of elbows vertical rise or drop in the piping.

WARNING

Danger of fire. Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubing being pressurized. Application of a brazing torch while pressurized may result in ignition of the refrigerant and oil mixture − check the high and low pressures before unbrazing.

WARNING

When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).

CAUTION

Brazing alloys and flux contain materials which are hazardous to your health.

Avoid breathing vapors or fumes from brazing operations. Perform operations only in well ventilated areas.

Wear gloves and protective goggles or face shield to protect against burns.

Wash hands with soap and water after handling brazing alloys and flux.

Page 11

XC17 SERIES

Image 11
Contents AIR Conditioner Table of ContentsGeneral Shipping and Packing ListBase with Elongated Legs Unit Dimensions − Inches mm and Parts ArrangementSide View Access View Model Number IdentificationControl BOX PLUMBING, Switches and Sensor ComponentsTypical Unit Parts Arrangement Torque Requirements Operating Gauge Set and Service ValvesUsing Manifold Gauge SET Operating Service ValvesReinstall Stem Cap To Access Service PortOperating Angle Type Service Valve Operating Ball Type Service ValveRecovering Refrigerant from Existing System RecoveringPositioning Considerations New Outdoor Unit PlacementClearance on ALL Sides Minimum Clearance Above Unit Minimum Clearance Between TWO UnitsRoof Mounting Elevating the UnitStabilizing Unit on Uneven Surfaces Stabilizing Unit on Uneven Surfaces Outside Unit PlacementElevated Slab Mounting using Feet Extenders Slab Mounting at Ground LevelLouvered Panel Installation Removing and Installing PanelsAccess Panel Removal Access and LouveredRefrigerant Line SET New or Replacement Line SetLine SET Brazing Line SET and Indoor Coil 1 FlushingFlushing the System Uncased Coil ShownFlushing Line SET and Indoor Coil 2 Sensing Bulb InstallationEqualizer Line Installation Installing Isolation Grommets Leak Testing the SystemLine SET and Indoor Coil Leak TestEvacuating the System Evacuating24VAC Transformer Size Circuit and Install Disconnect2INSTALL Thermostat Electrical4ROUTE High Voltage and Ground Wires 3ROUTE Control WiresTypical XC17 Wiring Main Control AGE Main Control Jumpers and TerminalsFAN Main Control Jumpers and TerminalsFlat metal jumper Field Control WiringOn−board link Unit Start−Up Connections for Testing and ChargingGauge SET Servicing Units Delivered Void of ChargeAction AirflowIndoor Coil Calculating System Charge for Outdoor Unit Void of Charge WeighCharge METHOD? Determine by RequirementsTest and Charge Method ApproachSubcooling HFC−410A Temperature Fahrenheit Psig Operating and Temperature PressuresSystem Operation Test Pins Function Ambient Sensor Temperature / Resistance Range High Discharge Sensor Temperature / Resistance Range System LED Alert Codes Sensor Temperature / Resistance RangeResetting LED Alert Codes Main Control LED Alert CodesAlert Status Compressor LED Alert Codes Detected in RUN High Pressure Switch Operation Low Pressure Switch Operation High Discharge Temperature Sensor Operation Verifying LED Status Codes MaintenanceVerifying Jumper Settings J2 FAN Motor Control and Start UPFan Motor Board Unit LED Codes LED Codes and Sequence of OperationsControl Panel Testing for External Power to Fan Control Fan Motor Test Fan Motor Surge Protection Device FAN Motor Surge ProtectionStart UP Checks XC17 Start−Up and Performance ChecklistCooling Mode Subcooling