Raypak 1334001 operating instructions Models, Mbh

Page 10

MODELS 0514-0824

 

Indoor/Outdoor

 

Dimensions (in inches)

 

 

 

 

 

Gas

Flue

 

 

 

 

Width

Conn.

 

Model

Input

Recovery

Diameter

 

Number

MBH

GPH*

A

G

K

L

WH-0514

511.5

508

32-3/4

1

10

25-3/8

WH-0624

627.0

623

37-1/2

1

12

29-1/2

WH-0724

726.0

722

41-5/8

1

12

34-1/4

WH-0824

825.0

820

45-3/4

1

14

38-1/2

 

 

 

 

 

 

 

* Recovery based on manufacturer’s rating.

MODELS 0962-1826

NOTE:

Ratings are shown for elevations up to

2,000 feet. For elevations over 2,000 feet, reduce ratings 4% for each 1,000 feet above sea level.

 

 

 

 

 

 

Dimensions (in inches)

 

 

 

 

 

 

 

Overall

Jacket

Gas

Water

 

Flue

 

Model

Input

Recovery

Width

Height

Height

Conn.

Conns.

 

Diameter

 

A

B

C

G

H

J

K

L

Number

MBH

GPH*

WH-0962

961.7

956

52-3/8

68-3/4

33-1/2

1

2-1/2

18

14

28

WH-1125

1124.7

1118

59-1/4

74-1/2

33-1/2

1

2-1/2

23-5/8

16

32

WH-1223

1222.5

1215

63-5/8

74-1/2

33-1/2

1-1/4

2-1/2

23-5/8

16

32

WH-1336

1336.6

1328

68-5/8

76-1/2

33-1/2

1-1/4

2-1/2

23-5/8

18

36

WH-1468

1467.0

1458

74-7/8

76-1/2

33-1/2

1-1/4

2-1/2

23-5/8

18

36

WH-1631

1630.0

1620

82-1/8

79-1/2

36-1/2

1-1/4

2-1/2

23-5/8

18

36

WH-1826

1825.6

1814

89-3/8

81-1/2

36-1/2

1-1/4

2-1/2

23-5/8

20

40

* Recovery based on manufacturer’s rating.

NOTE:

Ratings are shown for elevations up to 2,000 feet. For elevations over 2,000 feet, reduce ratings

4% for each 1,000 feet above sea level.

10

Image 10
Contents Raytherm Hot Water Supply Heaters Page Contents If Propane is Present or Suspected Temperature Time to Produce Serious Burn General SafetyTemperature limiting valves are available, see manual Feel water before bathing or show- eringReceiving Equipment Time/Temperature Relationships in ScaldsModel Identification Installation Clearances Installation Clearances All Dimensions are in InchesModel Part Number Model Specifications and DimensionsModels 0182-0400 Models MBHMBH GPH Outdoor Water Heaters High Wind Conditions Outdoor Units OnlyVenting Outdoor InstallationsVent Terminal Outdoor Stackless Top Installation Models 0181-0401Indoor Installations Indoor Top Installation Models 0181-0401 Vent Terminal/Indoor Stack Installation Vent Piping Vent PipingLocation Vent Damper InstallationModels 0133 Through 0180 Where Required MountingInstallation Vent DamperGeneral PlumbingGas Supply Connections Gas Pressure Regulator Venting of Diaphragm Gas ComponentsFlow Rates Maximum and Minimum Flow RatesPiping-Domestic Hot Water Supply Heaters Soft Medium HardPiping Diagram-Type WH Unitemp 80 System Relief Valve Pump Time DelayControls-General Electronic IgnitionLimit Controls Flow SwitchHigh Limit Electrical Connections 100% Pilot SafetyHigh and Low Gas Pressure Switches Optional Low Water Cut-Off OptionalLocation of Controls 0824 General START-UP ProceduresBefore Start-Up Initial Start-Up Pump and MotorFor Your Safety Read Before Operating Controls Inspection ProceduresBurners After Start-UpOperation Inspection ProceduresStart-Up Procedures S8610b Ignition Module Should be checked monthly. Takes approximately 15 minutesVisual Inspection Burner AdjustmentHigh Gas Pressure Switch ElectricalPilot Removal Main burner And Orifice RemovalCombustion Fan Removal Electrical-Electronic Ignition IID Intermittent Pilot System Honeywell S8600Mechanical Problem Possible Cause Corrective Action MechanicalWiring Diagrams Wiring Diagram-W2/WH2Wiring Diagram-WH1 0181/0261 Wiring Diagram-WH1 0331/0401 Wiring Diagram-WH1 Wiring Diagram-WH1 Wiring Diagram-WH1 Wiring Diagram-WH1 Troubleshooting-Pumps Service Maintenance ProceduresTube Cleaning Combination Flame SENSOR/ Igniter and Pilot Burner High Limit or Tankstat Removal Pilot Removal and CleaningHeat Exchanger Re-Assembly Heat Exchanger RemovalTube Replacement Replacement PartsControl Well Replacement Cleaning Flue Gas PassagewaysScope Page