Raypak 1334001 Electrical-Electronic Ignition IID, Intermittent Pilot System Honeywell S8600

Page 36

TROUbLESHOOTING

Electrical—Electronic Ignition IID

Intermittent Pilot System

Honeywell S8600

WARNING—HIGH VOLTAGE: For qualified

technicians ONLY.

NOTE: Some heaters may be equipped with an ignition module that shuts off pilot gas if pilot fails to light. To reset, interrupt power to heater.

START

TURN GAS SUPPLY OFF.

TURN THERMOSTAT

(CONTROLLER) TO CALL

FOR HEAT

POWER TO MODULE

(24 V NOMINAL)?

YES

SPARK ACROSS

IGNITER/SENSOR GAP?

YES

NO

NO

NOTE: Before troubleshooting, familiarize yourself with the start-up and checkout procedure.

Check line voltage power, low voltage transformer, limit controller, thermostat (controller) and wiring.

Pull ignition lead and check spark at module.

If spark is okay:

Check ignition cable, ground wiring, ceramic insulator and gap, and correct.

Check boot of the ignition cable for signs of melting or buckling. Take protective action to shield cable and boot from excessive temperatures.

If not, replace module.

TURN GAS SUPPLY ON PILOT BURNER LIGHTS?

YES

SPARK STOPS WHEN

PILOT IS LIT?

YES

MAIN BURNER LIGHTS?

YES

SYSTEM RUNS UNTIL CALL FOR HEAT ENDS?

YES

NO

 

• Check that all manual gas valves are open, supply tubing and pressures are good,

 

 

 

and pilot burner orifice is not blocked.

 

 

Check electrical connections between module and pilot operator on gas control.

Check for 24 Vac across PV-MV/PV terminals on module. If voltage is okay, replace gas control; if not, replace module.

 

 

NOTE: If S8600H goes into lockout, reset system. Lockout is used on propane

 

 

models.

NO

 

Check continuity of ignition cable and ground wire.

 

 

 

Clean flame rod.

 

 

Check electrical connections between flame rod and module.

 

 

Check for cracked ceramic flame rod insulator.

 

 

Check that pilot flame covers flame rod and is steady and blue.

 

 

Adjust pilot flame.

 

 

If problem persists, replace module.

 

 

 

 

 

 

 

 

 

 

Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace module.

NO

 

 

Check electrical connections between module and gas control. If okay, replace

 

 

 

 

gas valve or gas control operator, i.e. pilot gas valve, flow switch etc.

 

 

 

 

NOTE: IF S8600H goes into lockout, reset system.

NO

• Check continuity of ignition cable and ground wire.

 

NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though operation is normal at the time of checkout.

Check that pilot flame covers flame rod and is steady and blue.

If checks are okay, replace module.

CALL FOR HEAT ENDS SYSTEM SHUTS OFF?

YES

NO

Check for proper thermostat (controller) operation.

Remove MILLIVOLT lead at module; if valve closes, recheck temperature controller and wiring; if not, replace gas valve.

TROUBLESHOOTING ENDS

36

Image 36
Contents Raytherm Hot Water Supply Heaters Page Contents If Propane is Present or Suspected General Safety Temperature limiting valves are available, see manualTemperature Time to Produce Serious Burn Feel water before bathing or show- eringTime/Temperature Relationships in Scalds Receiving EquipmentModel Identification Installation Installation Clearances All Dimensions are in Inches ClearancesModel Part Number Specifications and Dimensions ModelModels 0182-0400 Models MBHMBH GPH Outdoor Water Heaters High Wind Conditions Outdoor Units OnlyOutdoor Installations Vent Terminal Outdoor Stackless Top InstallationVenting Models 0181-0401Indoor Installations Indoor Top Installation Models 0181-0401 Vent Terminal/Indoor Stack Installation Vent Piping Vent PipingVent Damper Installation Models 0133 Through 0180 Where RequiredLocation MountingInstallation Vent DamperPlumbing GeneralGas Supply Connections Gas Pressure Regulator Venting of Diaphragm Gas ComponentsFlow Rates Maximum and Minimum Flow RatesPiping-Domestic Hot Water Supply Heaters Soft Medium HardPiping Diagram-Type WH Unitemp 80 System Pump Time Delay Controls-GeneralRelief Valve Electronic IgnitionFlow Switch Limit ControlsHigh Limit 100% Pilot Safety High and Low Gas Pressure Switches OptionalElectrical Connections Low Water Cut-Off OptionalLocation of Controls 0824 START-UP Procedures Before Start-UpGeneral Initial Start-Up Pump and MotorFor Your Safety Read Before Operating Inspection Procedures BurnersControls After Start-UpInspection Procedures Start-Up Procedures S8610b Ignition ModuleOperation Should be checked monthly. Takes approximately 15 minutesBurner Adjustment High Gas Pressure SwitchVisual Inspection ElectricalMain burner And Orifice Removal Pilot RemovalCombustion Fan Removal Electrical-Electronic Ignition IID Intermittent Pilot System Honeywell S8600Mechanical Problem Possible Cause Corrective Action MechanicalWiring Diagrams Wiring Diagram-W2/WH2Wiring Diagram-WH1 0181/0261 Wiring Diagram-WH1 0331/0401 Wiring Diagram-WH1 Wiring Diagram-WH1 Wiring Diagram-WH1 Wiring Diagram-WH1 Service Maintenance Procedures Troubleshooting-PumpsTube Cleaning Combination Flame SENSOR/ Igniter and Pilot Burner Pilot Removal and Cleaning Heat Exchanger Re-AssemblyHigh Limit or Tankstat Removal Heat Exchanger RemovalReplacement Parts Control Well ReplacementTube Replacement Cleaning Flue Gas PassagewaysScope Page