Raypak 1334001 operating instructions Inspection Procedures, Burners, Controls, After Start-Up

Page 32

FOR MODELS WITH AUTOMATIC GAS VALVES

1.Close all gas valves. Turn off electric power supply. Wait five (5) minutes.

2.Open manual pilot valve. Turn on electric power. Pilot is automatically lighted.

3.Open main gas valve.

4.Set temperature controls to desired temperature.

TO SHUT DOWN

Close all manual gas valves. Turn off electric power.

PILOT SHUT-OFF VALVE CONTROL SHOWN IN "ON"

POSITION

GAS INLET

TO PILOT

MAIN GAS

SHUT-OFF

VALVE

SHOWN IN

THE "ON"

POSITION

Intermittent Pilot System Checkout Procedure (S8600)

After Start-Up

1.Turn on power to the ignition systems and turn gas supply off.

2.Check ignition module as follows:

a.Set the tankstat to call for heat.

b.Watch for continuous spark at the pilot burner.

c.Time the spark operation. Time must be within the lockout timing period (15 or 90 seconds).

d.Turn tankstat down to end call for heat and wait 60 seconds on lockout models before beginning step 3.

3.Turn on gas supply.

4.Set tankstat to call for heat.

5.Systems should start as follows:

a.Spark will turn on and pilot gas valve will open at once. Pilot burner should ignite after gas reach- es the pilot burner.

b.Spark ignition should cut-off when pilot flame is established.

c.Main gas valve should open and main burner should ignite after gas reaches the burner port.

INSPECTION

PROCEDURES

burners

Clean main burners and air louvers free of dust, lint and debris. Keep heater area clear and free from com- bustibles and flammable liquids. Do not obstruct the flow of combustion and ventilation air. Make visual check of burner and pilot flame. Yellow flame indicates clogging of air openings. Lifting or blowing flame indi-

cates excessively high gas pressure. Low flame indi- cates low gas pressure.

Fig. 31: Typical Main Burner Flame (Atmospheric

Models)

Controls

Check all controls to see that they are operational. To check electronic safety (IID models), turn off main burner. Observe pilot burner when shutting off pilot gas. Ignition spark should go on. Main gas valve will also drop out.

High Limit Switch - to check high limit switch, turn dial setting down to a point slightly below the temperature of the water leaving the heater. The reset button should snap out and the burner should shut-off. Reset dial to 30°F to 40°F above desired operating tempera- ture and push reset button. Burner should light.

32

Image 32
Contents Raytherm Hot Water Supply Heaters Page Contents If Propane is Present or Suspected General Safety Temperature limiting valves are available, see manualTemperature Time to Produce Serious Burn Feel water before bathing or show- eringModel Identification Time/Temperature Relationships in ScaldsReceiving Equipment Installation Model Part Number Installation Clearances All Dimensions are in InchesClearances Models 0182-0400 Specifications and DimensionsModel Models MBHMBH GPH Outdoor Water Heaters High Wind Conditions Outdoor Units OnlyOutdoor Installations Vent Terminal Outdoor Stackless Top InstallationVenting Models 0181-0401Indoor Installations Indoor Top Installation Models 0181-0401 Vent Terminal/Indoor Stack Installation Vent Piping Vent PipingVent Damper Installation Models 0133 Through 0180 Where RequiredLocation MountingInstallation Vent DamperGas Supply Connections PlumbingGeneral Gas Pressure Regulator Venting of Diaphragm Gas ComponentsFlow Rates Maximum and Minimum Flow RatesPiping-Domestic Hot Water Supply Heaters Soft Medium HardPiping Diagram-Type WH Unitemp 80 System Pump Time Delay Controls-GeneralRelief Valve Electronic IgnitionHigh Limit Flow SwitchLimit Controls 100% Pilot Safety High and Low Gas Pressure Switches OptionalElectrical Connections Low Water Cut-Off OptionalLocation of Controls 0824 START-UP Procedures Before Start-UpGeneral Initial Start-Up Pump and MotorFor Your Safety Read Before Operating Inspection Procedures BurnersControls After Start-UpInspection Procedures Start-Up Procedures S8610b Ignition ModuleOperation Should be checked monthly. Takes approximately 15 minutesBurner Adjustment High Gas Pressure SwitchVisual Inspection ElectricalCombustion Fan Removal Main burner And Orifice RemovalPilot Removal Electrical-Electronic Ignition IID Intermittent Pilot System Honeywell S8600Mechanical Problem Possible Cause Corrective Action MechanicalWiring Diagrams Wiring Diagram-W2/WH2Wiring Diagram-WH1 0181/0261 Wiring Diagram-WH1 0331/0401 Wiring Diagram-WH1 Wiring Diagram-WH1 Wiring Diagram-WH1 Wiring Diagram-WH1 Tube Cleaning Service Maintenance ProceduresTroubleshooting-Pumps Combination Flame SENSOR/ Igniter and Pilot Burner Pilot Removal and Cleaning Heat Exchanger Re-AssemblyHigh Limit or Tankstat Removal Heat Exchanger RemovalReplacement Parts Control Well ReplacementTube Replacement Cleaning Flue Gas PassagewaysScope Page