Raypak 133-4001 manual Flame Roll-Out Safety Switch, Service Burner Tray Removal

Page 31

size, and connections which comply with all applicable codes.

Flame Roll-Out Safety Switch

The boiler is equipped with a cut-off device to prevent flame roll-out in the event the heat exchanger becomes blocked. This is a "manual reset" type roll- out switch, that must be reset by a service technician after any over temperature conditions have been fixed. Excessive restriction in the heat exchanger flue pas- sage may cause the switch to disable the boiler.

Fig. 45: Flame Roll-Out Safety Switch

Service

Burner Tray Removal

COMBUSTION

AIR BLOWER

AIR SHUTTER

ADJUSTMENT

GAS

VALVE

BURNER

BURNER

HOLD-

DOWN

BRACKET

Fig. 46: Low NOx Burner Tray Assembly

1.Shut-off main electrical power switch to heater.

2.Shut-off gas upstream of heater.

3.Remove front door.

4.Disconnect gas line from gas valve.

5.Remove (2) screws that mount burner tray to the base of the unit, and (2) screws that secure gas valve to jacket.

6.Disconnect wires that terminate at gas valve.

7.Unscrew (4) screws that secure the control box.

8.Disconnect pilot wire from the ignition module.

9.Disconnect wire harness from the combustion blower.

10.Carefully slide out the burner tray assembly.

11.Reverse above procedure to re-install.

Gas Valve Adjustment - Robertshaw (Invensys) 7000 Series 2-Stage Gas Valve with Solenoid Valve

NOTE: Attach a manometer and check the manifold pressures –both high fire and low fire– before making any adjustments.

1.Turn the heater off.

2.Remove the 3/8” nut or the #10 Torx screw.

3.Lift solenoid valve up, keeping the wires connect- ed to the solenoid valve.

4.If only low fire adjustment is needed, go to Step 9.

5.Using a 3/8” wrench, carefully remove the alu- minum cap that was under the solenoid valve-count # of turns when removing the cap. Be careful not to drop the cylinder (weight) or the small spring that is under the cap –see Fig. 47.

6.Remove the spring and store in a safe place.

Fig. 47: 2-Stage Gas Valve Adjustment (Invensys)

31

Image 31
Contents Raytherm Heating Boilers Deletions None Contents Are important but not related to personal injury hazards 0 5 1 4 a Model IdentificationBoiler Types InstallationReceiving Equipment CertificationsClearances Installation BaseHigh-Wind Conditions Outdoor Units Only Outdoor BoilersCombustion and Ventilation Air Indoor Units Only Model Sq. Inches Outdoor Installations ModelVenting Models 181-401Models Indoor InstallationsIndoor Installation-Model Indoor Stack InstallationIndoor Installation-Models 181-401 Vent Piping Drafthood Installation-ModelsCommon Venting Models 133 Through 261 Where Required Location Vent Damper InstallationNormal Operation Summary PlumbingGas Supply Connections Vent DamperPump Selection Venting of Diaphragm Gas ComponentsGas Pressure Regulator GeneralFeedwater Regulator Temperature & Pressure GaugeRecommended Purge Manifolds for Typical Hydronic System HookupsSingle Boiler Primary/Secondary Piping-Models Multiple-Boiler- Reverse Return Hook-Up-Models Operating Controls ControlsEconomaster Controls Electronic IgnitionMode H9 4-Stage Firing Mode H2 Motorized ModulationMode H3 2-Stage Firing Mode H4 On/Off Firing100% Pilot Safety Manual-Reset High LimitAuto-Reset High Limit Flow SwitchElectrical Connections High and Low Gas Pressure Switches OptionalLow Water Cut-Off Optional START-UP START-UP For Models with Manual Gas Valves For Your Safety Read Before OperatingLighting Instructions After Start-Up Standing Pilot Checkout ProcedureFor Models with Automatic Gas Valves Intermittent Pilot System Checkout S8600Controls Inspections BurnersSuggested Inspection Schedule Start-Up S8600H Blower AdjustmentModels 181 to OperationService Burner Tray Removal Flame Roll-Out Safety SwitchCombustion Fan Removal Gas Valve RemovalMain Burner and Orifice Removal Pilot RemovalElectrical-Electronic Ignition IID TroubleshootingIntermittent Pilot System Honeywell S8600 Electrical-Standing Pilot Typical ON-OFF Intermittent Ignition Control Wiring Diagram Mechanical Problem Possible Cause Corrective Action Pumps Gas Valve Removal Service Repair SectionTube Cleaning Procedure Burner Tray RemovalHigh Limit or Tankstat Removal Pilot Removal and CleaningHeat Exchanger Removal Combustion Chamber Removal Heat Exchanger Re-AssemblyControl Well Replacement Tube Replacement ProcedureCleaning Flue Gas Passageways Replacement PartsEastman Avenue Oxnard, CA Limited Warranty Raytherm Types H and WH

133-4001 specifications

Raypak 133-4001 is a premier heating solution designed for both residential and commercial applications, known for its efficiency and reliability. This high-performance water heater is specifically engineered to meet the demanding requirements of hot water supply while ensuring energy conservation and user convenience.

One of the standout features of the Raypak 133-4001 is its robust construction. Made from high-quality materials, including a corrosion-resistant heat exchanger and durable casing, this unit is designed to withstand harsh environmental conditions. Its compact design allows for easy installation in various locations, making it an ideal choice for homeowners and businesses alike.

The unit operates on natural gas or LP gas, providing versatility in fuel choice. With a heating capacity of 199,000 BTU/hr, it delivers an impressive flow rate that ensures a steady supply of hot water, even during peak demand periods. This capacity makes it suitable for a wide range of applications, from residential water heating to larger facilities requiring substantial hot water output.

Raypak’s advanced technology set ensures that the 133-4001 operates at maximum efficiency. It utilizes a modulating power burner that adjusts the flame based on demand, optimizing fuel consumption. This feature not only helps in reducing energy bills but also minimizes the carbon footprint, making it an environmentally friendly option.

Another notable characteristic of the Raypak 133-4001 is its digital control system. The intuitive interface allows for precise temperature adjustments and easy monitoring of the heating process. Users can set the desired water temperature, and the system will maintain it consistently, ensuring comfort and reducing the risk of scalding.

Safety is a paramount consideration in the design of the 133-4001. It features a built-in high-limit switch, pressure relief valve, and multiple safety sensors to prevent overheating and potential hazards. These safety features provide peace of mind for homeowners and facility managers, knowing that their hot water system is reliable and secure.

In conclusion, Raypak 133-4001 combines advanced technology, robust construction, and user-friendly features, making it a highly effective water heating solution. Its efficiency and dependability cater to a variety of hot water needs, positioning it as a top choice for both residential and commercial use. Whether for a single-family home or a large facility, the Raypak 133-4001 is built to deliver exceptional performance with every use.