CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the boiler and void the warranty.

a.All Air From Inside The Building:

Each opening shall have a minimum net free square inches as noted in Table E.

Model

Sq. Inches

Model

Sq. Inches

 

 

 

 

133

136

1125

1125

 

 

 

 

182/181

181

1223

1223

 

 

 

 

260/261

264

1336

1337

 

 

 

 

330/331

334

1468

1467

 

 

 

 

400/401

399

1631

1630

 

 

 

 

514

512

1826

1826

 

 

 

 

624

627

2100

2100

 

 

 

 

724

726

2500

2499

 

 

 

 

824

825

3001

3000

 

 

 

 

962

962

3500

3500

 

 

 

 

 

 

4001

4000

 

 

 

 

Table E: Minimum Net Free Air from Inside Building

b.All Air From Outdoors:

When air is supplied directly from outside of build- ing, each opening shall have a minimum net free square inches as noted in Table F.

Model

Sq. Inches

Model

Sq. Inches

 

 

 

 

133

34

1125

282

 

 

 

 

182/181

46

1223

306

 

 

 

 

260/261

66

1336

335

 

 

 

 

330/331

84

1468

367

 

 

 

 

400/401

100

1631

408

 

 

 

 

514

128

1826

457

 

 

 

 

624

157

2100

525

 

 

 

 

724

182

2500

625

 

 

 

 

824

207

3001

750

 

 

 

 

962

241

3500

875

 

 

 

 

 

 

4001

1000

 

 

 

 

Table F: Minimum Net Free Air from Outside Building

Venting

Outdoor Installations

Model 133

1.Remove the front (4) screws.

2.Line up outdoor top vent opening over heater vent opening.

3.Lower outdoor top onto unit lining up slots in the outdoor top with screw holes in jacket top.

4.Reinstall (5) screws to secure jacket top and out- door top to unit.

Fig. 4: Installing Outdoor Top—Model 133

Models 181-401 & 182-400

Outdoor Top Installation

(Part of heater)

Fig. 5: Installing Outdoor Top—Models 181-401 & 182-

400

9

Image 9
Contents Raytherm Heating Boilers Deletions None Contents Are important but not related to personal injury hazards 0 5 1 4 a Model IdentificationReceiving Equipment InstallationCertifications Boiler TypesClearances Installation BaseOutdoor Boilers High-Wind Conditions Outdoor Units OnlyCombustion and Ventilation Air Indoor Units Only Venting Outdoor Installations ModelModels 181-401 Model Sq. InchesModels Indoor InstallationsIndoor Installation-Model Indoor Stack InstallationIndoor Installation-Models 181-401 Vent Piping Drafthood Installation-ModelsCommon Venting Models 133 Through 261 Where Required Location Vent Damper InstallationGas Supply Connections PlumbingVent Damper Normal Operation SummaryGas Pressure Regulator Venting of Diaphragm Gas ComponentsGeneral Pump SelectionRecommended Purge Manifolds for Temperature & Pressure GaugeTypical Hydronic System Hookups Feedwater RegulatorSingle Boiler Primary/Secondary Piping-Models Multiple-Boiler- Reverse Return Hook-Up-Models Economaster Controls ControlsElectronic Ignition Operating ControlsMode H3 2-Stage Firing Mode H2 Motorized ModulationMode H4 On/Off Firing Mode H9 4-Stage FiringAuto-Reset High Limit Manual-Reset High LimitFlow Switch 100% Pilot SafetyHigh and Low Gas Pressure Switches Optional Electrical ConnectionsLow Water Cut-Off Optional START-UP START-UP For Models with Manual Gas Valves For Your Safety Read Before OperatingFor Models with Automatic Gas Valves After Start-Up Standing Pilot Checkout ProcedureIntermittent Pilot System Checkout S8600 Lighting InstructionsInspections Burners ControlsSuggested Inspection Schedule Models 181 to Blower AdjustmentOperation Start-Up S8600HService Burner Tray Removal Flame Roll-Out Safety SwitchMain Burner and Orifice Removal Gas Valve RemovalPilot Removal Combustion Fan RemovalTroubleshooting Electrical-Electronic Ignition IIDIntermittent Pilot System Honeywell S8600 Electrical-Standing Pilot Typical ON-OFF Intermittent Ignition Control Wiring Diagram Mechanical Problem Possible Cause Corrective Action Pumps Tube Cleaning Procedure Service Repair SectionBurner Tray Removal Gas Valve RemovalPilot Removal and Cleaning High Limit or Tankstat RemovalHeat Exchanger Removal Control Well Replacement Heat Exchanger Re-AssemblyTube Replacement Procedure Combustion Chamber RemovalReplacement Parts Cleaning Flue Gas PassagewaysEastman Avenue Oxnard, CA Limited Warranty Raytherm Types H and WH

133-4001 specifications

Raypak 133-4001 is a premier heating solution designed for both residential and commercial applications, known for its efficiency and reliability. This high-performance water heater is specifically engineered to meet the demanding requirements of hot water supply while ensuring energy conservation and user convenience.

One of the standout features of the Raypak 133-4001 is its robust construction. Made from high-quality materials, including a corrosion-resistant heat exchanger and durable casing, this unit is designed to withstand harsh environmental conditions. Its compact design allows for easy installation in various locations, making it an ideal choice for homeowners and businesses alike.

The unit operates on natural gas or LP gas, providing versatility in fuel choice. With a heating capacity of 199,000 BTU/hr, it delivers an impressive flow rate that ensures a steady supply of hot water, even during peak demand periods. This capacity makes it suitable for a wide range of applications, from residential water heating to larger facilities requiring substantial hot water output.

Raypak’s advanced technology set ensures that the 133-4001 operates at maximum efficiency. It utilizes a modulating power burner that adjusts the flame based on demand, optimizing fuel consumption. This feature not only helps in reducing energy bills but also minimizes the carbon footprint, making it an environmentally friendly option.

Another notable characteristic of the Raypak 133-4001 is its digital control system. The intuitive interface allows for precise temperature adjustments and easy monitoring of the heating process. Users can set the desired water temperature, and the system will maintain it consistently, ensuring comfort and reducing the risk of scalding.

Safety is a paramount consideration in the design of the 133-4001. It features a built-in high-limit switch, pressure relief valve, and multiple safety sensors to prevent overheating and potential hazards. These safety features provide peace of mind for homeowners and facility managers, knowing that their hot water system is reliable and secure.

In conclusion, Raypak 133-4001 combines advanced technology, robust construction, and user-friendly features, making it a highly effective water heating solution. Its efficiency and dependability cater to a variety of hot water needs, positioning it as a top choice for both residential and commercial use. Whether for a single-family home or a large facility, the Raypak 133-4001 is built to deliver exceptional performance with every use.