Raypak 133-4001 manual Installation Base, Clearances

Page 7

Installation Base

The boiler should be mounted on a level, non-com- bustible surface. Boiler must not be installed on carpeting. The boiler can be installed on a combustible surface only when a suitable floor shield base is pro- vided. Raypak offers an optional floor shield base which can be factory installed on all indoor models except Model 133; the Model 133 floor shield base is shipped loose and must be installed by the contractor. Do NOT use the shipping crate base as an installation base.

NOTE: For Models 2100-4001, a factory-installed floor shield is standard. Table B provides the floor shield ordering information for other models.

NOTE: The boiler should be located in an area where water leakage will not result in damage to the area adjacent to the appliance or to the structure. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance. The pan must not restrict air flow.

In addition, the boiler shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replacement, etc.).

Boiler Model No.

Base Part No.

Boiler Model No.

Base Part No.

 

 

 

 

133

001749

926*

054597

182/181

058313

1083*

054598

260/261

058314

1178*

054599

330/331

058315

1287*

054600

400/401

058316

1414*

054601

 

 

1571*

058378

 

 

1758*

058379

 

 

 

 

514

056199

962

059233

624

056200

1125

059234

724

056201

1223

059235

824

056202

1336

059236

 

 

1468

059237

 

 

1631

059238

 

 

1826

059239

 

 

 

 

*Models with factory-installed floor shield as standard. BOLD type indicates Low NOx models.

Table B: Combustible Floor Shield Ordering

Information

Fig. 2: Alternate Method for Providing a Non-

Combustible Base

Clearances

MODEL

 

 

 

 

181 to

 

514 to

 

 

 

2100 to

 

 

 

133

 

 

926 to

 

 

 

 

401

 

824

 

1826

 

4001

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

All dimensions are in inches.

Derived from National Fuel Gas Code, Table 6.2.3(a)

*Vent includes factory-supplied drafthood and does not include field- supplied vent systems above the drafthood. On Models 2100-4001 drafthood is built into boiler.

Table C: Clearances from Combustible Surfaces

NOTE 1: Combustible floor shield is required when boiler is to be installed on a combustible surface. (See ordering information in Table B.)

NOTE 2: Servicing Clearances: Provide at least 24" (Models 133-1826), 48" (Models 2100-4001) in front of unit for removal and servicing of the Controls & Burner Tray. Provide at least 18" on side opposite water connections for deliming of Heat Exchanger Tubes.

7

Image 7
Contents Raytherm Heating Boilers Deletions None Contents Are important but not related to personal injury hazards 0 5 1 4 a Model IdentificationBoiler Types InstallationReceiving Equipment CertificationsClearances Installation BaseHigh-Wind Conditions Outdoor Units Only Outdoor BoilersCombustion and Ventilation Air Indoor Units Only Model Sq. Inches Outdoor Installations ModelVenting Models 181-401Models Indoor InstallationsIndoor Installation-Model Indoor Stack InstallationIndoor Installation-Models 181-401 Vent Piping Drafthood Installation-ModelsCommon Venting Models 133 Through 261 Where Required Location Vent Damper InstallationNormal Operation Summary PlumbingGas Supply Connections Vent DamperPump Selection Venting of Diaphragm Gas ComponentsGas Pressure Regulator GeneralFeedwater Regulator Temperature & Pressure GaugeRecommended Purge Manifolds for Typical Hydronic System HookupsSingle Boiler Primary/Secondary Piping-Models Multiple-Boiler- Reverse Return Hook-Up-Models Operating Controls ControlsEconomaster Controls Electronic IgnitionMode H9 4-Stage Firing Mode H2 Motorized ModulationMode H3 2-Stage Firing Mode H4 On/Off Firing100% Pilot Safety Manual-Reset High LimitAuto-Reset High Limit Flow SwitchElectrical Connections High and Low Gas Pressure Switches OptionalLow Water Cut-Off Optional START-UP START-UP For Models with Manual Gas Valves For Your Safety Read Before OperatingLighting Instructions After Start-Up Standing Pilot Checkout ProcedureFor Models with Automatic Gas Valves Intermittent Pilot System Checkout S8600Controls Inspections BurnersSuggested Inspection Schedule Start-Up S8600H Blower AdjustmentModels 181 to OperationService Burner Tray Removal Flame Roll-Out Safety SwitchCombustion Fan Removal Gas Valve RemovalMain Burner and Orifice Removal Pilot RemovalElectrical-Electronic Ignition IID TroubleshootingIntermittent Pilot System Honeywell S8600 Electrical-Standing Pilot Typical ON-OFF Intermittent Ignition Control Wiring Diagram Mechanical Problem Possible Cause Corrective Action Pumps Gas Valve Removal Service Repair SectionTube Cleaning Procedure Burner Tray RemovalHigh Limit or Tankstat Removal Pilot Removal and CleaningHeat Exchanger Removal Combustion Chamber Removal Heat Exchanger Re-AssemblyControl Well Replacement Tube Replacement ProcedureCleaning Flue Gas Passageways Replacement PartsEastman Avenue Oxnard, CA Limited Warranty Raytherm Types H and WH

133-4001 specifications

Raypak 133-4001 is a premier heating solution designed for both residential and commercial applications, known for its efficiency and reliability. This high-performance water heater is specifically engineered to meet the demanding requirements of hot water supply while ensuring energy conservation and user convenience.

One of the standout features of the Raypak 133-4001 is its robust construction. Made from high-quality materials, including a corrosion-resistant heat exchanger and durable casing, this unit is designed to withstand harsh environmental conditions. Its compact design allows for easy installation in various locations, making it an ideal choice for homeowners and businesses alike.

The unit operates on natural gas or LP gas, providing versatility in fuel choice. With a heating capacity of 199,000 BTU/hr, it delivers an impressive flow rate that ensures a steady supply of hot water, even during peak demand periods. This capacity makes it suitable for a wide range of applications, from residential water heating to larger facilities requiring substantial hot water output.

Raypak’s advanced technology set ensures that the 133-4001 operates at maximum efficiency. It utilizes a modulating power burner that adjusts the flame based on demand, optimizing fuel consumption. This feature not only helps in reducing energy bills but also minimizes the carbon footprint, making it an environmentally friendly option.

Another notable characteristic of the Raypak 133-4001 is its digital control system. The intuitive interface allows for precise temperature adjustments and easy monitoring of the heating process. Users can set the desired water temperature, and the system will maintain it consistently, ensuring comfort and reducing the risk of scalding.

Safety is a paramount consideration in the design of the 133-4001. It features a built-in high-limit switch, pressure relief valve, and multiple safety sensors to prevent overheating and potential hazards. These safety features provide peace of mind for homeowners and facility managers, knowing that their hot water system is reliable and secure.

In conclusion, Raypak 133-4001 combines advanced technology, robust construction, and user-friendly features, making it a highly effective water heating solution. Its efficiency and dependability cater to a variety of hot water needs, positioning it as a top choice for both residential and commercial use. Whether for a single-family home or a large facility, the Raypak 133-4001 is built to deliver exceptional performance with every use.