Venting
2. Assemble and Adjust the Sleeve Length
Measure wall thickness through previously drilled 3 1/2 inch (90 mm) hole.
The end of the sleeve should protrude 3/16 - 3/8 inch
In the
In both kits, two parts are threaded for additional adjustment.
Adjust the sleeve length to wall thickness plus 3/16 - 3/8 inch
a b c
Sleeve Parts
For wall thickness plus 3/16 - 3/8 in | Assemble these parts (“A” Vent Kit) | ||||
4 1/3 - 6 1/8 in (110 - 155 mm) |
| a | + | b |
|
6 1/8 - 7 3/4 in (155 - 195 mm) | a | + | b | + | c |
7 3/4 - 9 1/2 in (195 - 240 mm) | a + | b | + | c | + c |
|
|
|
|
|
|
3.Attach the sleeve
Attach to the inside wall using 3 screws arranging the flange so that the marking “TOP” is at the top.
The flange is offset 2° to allow the condensate to drain to the outside.
3 screws
sleeve should extend 3/16 - 3/8 in
4. Install the Terminal
Terminal seal
Check that the terminal seal is in place. For weatherboard or vinyl siding, add the second seal next to the terminal seal to compensate for the angle.
From the outside insert the terminal into the sleeve with the marking “TOP” at the top. The left hand side locking tie should be marked “LEFT”.
Terminal
Locking tie
Rinnai Corporation | 21 |