Schneider Electric iEM3200 Internal clock, Modbus communications, LonWorks communications

Page 100

Specifications

 

 

iEM3100 / iEM3200 / iEM3300 series user manual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Characteristic

 

Value

 

Meters

 

 

 

 

 

 

 

 

 

 

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD):

iEM3200 / iEM3210 / iEM3215

 

 

 

Imax=1.2 A, ln=1 A, and Ist=0.002 A

 

 

 

 

 

 

 

Active energy

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx):

iEM3235 / iEM3250 / iEM3255 / iEM3265 /

 

Imax=1.2 A, ln=1 A, and Ist=0.002 A

 

iEM3275

for x/1A current input

 

 

 

 

 

Class B conforming to EN 50470-3: Imax=1.2 A, ln=1 A, Imin=0.01 A, and

iEM32••

 

 

 

 

 

 

Ist=0.002 A

 

 

 

 

Reactive energy

Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx):

iEM3235 / iEM3255 / iEM3265 / iEM3275

 

Imax=1.2 A, ln=1 A, and Ist=0.003 A

 

 

 

 

 

 

 

 

 

Class 0.5S conforming to IEC 62053-22 and IEC 61557-12 (PMD SD):

iEM32••

 

 

 

Imax=6 A, ln=5 A, and Ist=0.005 A

 

 

 

 

 

 

 

Active energy

Class 0.5S conforming to IEC 62053-22 and IEC 61557-12 (PMD Sx):

iEM3235 / iEM3250 / iEM3255 / iEM3265 /

 

Imax=6 A, ln=5 A, and Ist=0.005 A

 

iEM3275

for x/5A current input

 

 

 

 

 

Class C conforming to EN 50470-3: Imax=6 A, ln=5 A, Imin=0.05 A, and

iEM32••

 

 

 

 

 

 

Ist=0.005 A

 

 

 

 

Reactive energy

Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx):

iEM3235 / iEM3255 / iEM3265 / iEM3275

 

Imax=6 A, ln=5 A, and Ist=0.015 A

 

 

 

 

 

 

MID

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Characteristic

Value

 

Meters

 

 

 

 

 

 

 

Electromagnetic environmental class

E2

iEM3110 / iEM3115 / iEM3135 / iEM3155 / iEM3165 / iEM3175 /

 

 

 

 

 

iEM3210 / iEM3215 / iEM3235 / iEM3255 / iEM3265 / iEM3275 /

 

 

Mechanical environmental class

M1

 

 

iEM3310 / iEM3335 / iEM3355 / iEM3365 / iEM3375

Complies with the European Measuring Instruments Directive (MID) 2004/22/CE when installed in a suitable switchboard in accordance with the instructions in DOCA0038EN, available on our website. The CE declaration document is also available; search for ECDiEM3000.

Internal clock

Characteristic

Value

Meters

 

 

 

Type

Quartz crystal based

iEM3115 / iEM3135 / iEM3155 / iEM3165 /

Backup by supercapacitor

 

iEM3175 / iEM3215 / iEM3235 / iEM3255 /

Time error

< 2.5 s/day (30 ppm) at 25°C (77°F)

iEM3265 / iEM3275 / iEM3335 / iEM3355 /

 

 

iEM3365 / iEM3375

Backup time

> 3 days at 25°C (77°F)

 

 

 

 

Modbus communications

Characteristic

 

 

Value

Meters

 

 

 

 

 

Number of ports

1

 

 

 

 

 

 

 

 

Labels

0V, D0/-, D1/+

 

(shield)

 

 

 

 

 

 

 

 

 

 

Parity

Even, Odd, None

 

 

 

 

 

 

Baud rate

9600, 19200, 38400

iEM3150 / iEM3155 / iEM3250 /

Isolation

4.0 kV rms

 

iEM3255 / iEM3350 / iEM3355

 

 

 

 

Wire

2.5 mm2 / 14 AWG shielded twisted pair

 

Wire strip length

7 mm / 0.28 in

 

 

 

 

 

 

 

Torque

0.5 Nm / 4.4 in•lb

 

 

 

 

 

 

 

Related topics

See “Communications via Modbus RS-485” on page 51 for information on Modbus communications.

LonWorks communications

Characteristic

Value

Meters

 

 

 

Number of ports

1

 

Isolation

3.75 kV rms

 

Wire

2.5 mm2 / 14 AWG

iEM3175 / iEM3275 / iEM3375

Wire strip length

7 mm / 0.28 in

 

Torque

0.5 Nm / 4.4 in•lb

 

100

DOCA0005EN-04

Image 100
Contents IEM3100 / iEM3200 / iEM3300 series Page DOCA0005EN-04 Important information Safety informationPlease note FCC Part 15 notice About the book Related documentsDocument scope Validity noteContents Chapter Specifications Chapter Troubleshooting 103Chapter Power, energy and power factor 105 Chapter Communications via M-BusSafety precautions Hazard of Electric SHOCK, EXPLOSION, or ARC FlashSafety precautions DOCA0005EN-04 Main characteristics What is in this chapter?Chapter Overview Overview of meter functions5 a meters Digital outputs Or overload alarm Pulse output onlyFunction Typical applications IEM31 and iEM33 seriesIEM32 series Typical applicationsOverview Hardware and installation DimensionsIEM31 and iEM32 meters IEM33 metersAll meters Meter sealing points Hardware overviewIEM3100 / iEM3110 / iEM3115 Direct measurement up to 63 a Digital input IEM3200 / iEM3210 / iEM3215 Measurement with CTs IEM3235 Measurement with CTs and M-Bus communications IEM3275 Measurement with CTs and LonWorks communications IEM3300 / iEM3310 Direct measurement up to 125 aDigital input iEM3355 / iEM3365 DIN rail mounting and dismounting Mounting the meter on a DIN railDismounting the meter from a DIN rail Pulse output wiring iEM3110 / iEM3210 / iEM3310 Input, output and communications wiringDigital input wiring iEM3115 / iEM3215 Bus communications wiring iEM3135 / iEM3235 / iEM3335 M-Bus communications connection is polarity-independentPower system wiring LonWorks communications wiring iEM3175 / iEM3275 / iEM3375Voltage input protection Current input protection for 1 a and 5 a metersDirect measurement meter wiring Fuses and disconnect switchPower system IEMPower system Wiring Power system WiringSingle-phase systems with CTs 1 a meter wiringMA fuses and disconnect switch Shorting block Three-phase systems with CTs Three-phase systems with CTs and VTs Hardware and installation DOCA0005EN-04 Front panel display and meter setup 1234.5Data display Data display screen overviewExample navigating the display screens Data display screensPhase 3 Current Data display screens iEM3150 / iEM3250 / iEM3350Resets Multi Tariff featureResetting accumulated energy using the display Reset DescriptionClock behavior on power interruption Meter status informationDevice clock Date/time formatDevice configuration Setting the clock initiallyEntering configuration mode Front panel display in configuration modeCom. Protection setting Example Configuring a list valueModifying parameters Selecting a value from a listCanceling an entry Configuration mode menusExample configuring a numeric value Section Parameter Options Description 1PH2W L-L 1PH3W L-L-NConfiguration menu for iEM3150 / iEM3350 Com.Protection Contrast Password Reset Config By Internal Clock Configuration menus for iEM3200 / iEM3210 / iEM3215 Configuration menus for iEM3250 Com.Protection 3PH3W 3PH4W Section Parameter Options Description Front panel display and meter setup DOCA0005EN-04 Modbus communications settings Communications LED indicator for Modbus devicesCommunications via Modbus RS-485 Modbus communication overviewModbus functions Function listTable format Unit tableCommand interface Command interface overviewCommand request Command resultCommand list Command Action Size Type Unit Range DescriptionSet Date/Time Action Size Type Unit Range Description NumberSet Tariff iEM3155 / iEM3255 / iEM3355 Set Pulse Output iEM3155 / iEM3255 / iEM3355Size Type Unit Range Description Overload Alarm Setup iEM3155 / iEM3255 / iEM3355 Input Metering Setup iEM3155 / iEM3255 / iEM3355Communications Setup Meter Setup and Status Reset Partial Energy CountersReset Input Metering Counter iEM3155 / iEM3255 / iEM3355 Modbus register listEnergy Pulse Output Setup iEM3155 / iEM3255 / iEM3355 Command InterfaceInput Metering Setup iEM3155 / iEM3255 / iEM3355 CommunicationCurrent, voltage, power, power factor and frequency Digital Input iEM3155 / iEM3255 / iEM3355Digital Output iEM3155 / iEM3255 / iEM3355 Meter DataEnergy, energy by tariff and input metering Read Device Identification Overload Alarm iEM3155 / iEM3255 / iEM3355Energy values 32-bit floating point Object ID Name/Description Length Value LED indicators for LonWorks meters Communications via LonWorksLonWorks communications overview LonWorks communication implementationLocation of the service pin and Neuron ID General variablesSystem variables Green communications LEDEnergy and energy by tariff measurements Type DescriptionInstantaneous RMS measurements System configuration information Digital input configuration and status informationAlarm status Meter status informationMeter configuration properties ResetsDate/time setup Network variable label Type Description ActionBasic setup Digital input setupInput metering setup Struct Members Range / options DescriptionOverload alarm setup Multi Tariff setupNetwork propagation rate setup Range / options DescriptionInstalling and registering the LonMaker plug-in Browsing the meter using the LonMaker plug-in LonMaker plug-in interfacePlug-in has the following tabs Tab name DescriptionMeter Status Communications via LonWorks DOCA0005EN-04 Configuring basic communications settings Communications via M-BusBus communications overview Key termsBus protocol support Bus protocol implementationFixed data header Variable data structure telegram informationData record header information Manufacturer-specific Vife codes Description Bin HexTelegram information for data records Meter informationBin Hex Primary VIF Primary VifeInstantaneous measurements Date and time informationData format Data format Primary VIFDigital input and output status information Power system configuration informationData format Primary Vife Telegram information for meter configuration Alarm status informationSupported Vife codes for meter configuration Action Description Bin HexDate/time setup Power system setupMulti Tariff setup Data format Primary VIF DescriptionDigital input setup Digital output setupOverload alarm setup and acknowledgment Baud rateBus tool for data display and meter configuration Installing the M-Bus toolAccessing the meter using the tool ResetsViewing meter data using the M-Bus tool Select Setup Config to switch to configuration mode Configuring the meter using the M-Bus toolSection Description Communications via M-Bus DOCA0005EN-04 Communications via BACnet BACnet communications overviewBACnet protocol support Related topicsConfiguring basic communication parameters BACnet communications implementationFollowing standard object types are supported Object typeCommunications LED indicator for BACnet meters BACnet object and property informationChange of Value COV subscriptions Device objectAnalog Input objects Object ID Units Default COV Object name / descriptionEnergy and energy by tariff measurements Instantaneous RMS measurements Meter informationCommunications settings information Digital input and output setting informationCommand Analog Value objectBinary Input objects Object ID Object name / descriptionCommunications via BACnet DOCA0005EN-04 Chapter Specifications Electrical characteristicsPower system inputs iEM31 meters Power system inputs iEM33 metersCharacteristic Value Meters Power system inputs iEM32 metersInputs and outputs Environmental characteristics Mechanical characteristicsMeasurement accuracy Modbus communications Internal clockLonWorks communications Bus communications BACnet communicationsSpecifications 102 DOCA0005EN-04 Troubleshooting Do not open the meter. Opening the meter voids the warrantyDiagnosis screen lists any current diagnostic codes Diagnosis screenDiagnostic codes Description Possible solutionPower, energy and power factor Power PQSPower and the PQ coordinate system Power flowPower factor PF True PF and displacement PFEnergy delivered imported / energy received exported PF lead / lag conventionPower and PF lead / lag PF sign conventionPF lead / lag summary PF sign in IECPower factor register format To +1Quadrant To +1 +1 to +2Quadrant PF range PF formulaPower, energy and power factor 110 DOCA0005EN-04 Page Schneider Electric 35, rue Joseph Monier CS30323