Schneider Electric iEM3300, iEM3200, iEM3100 Manufacturer-specific Vife codes, Description Bin Hex

Page 78

Communications via M-Bus

 

 

iEM3100 / iEM3200 / iEM3300 series user manual

 

 

 

 

 

 

 

 

 

 

 

Primary VIFE codes

bin

hex

Additional information

 

 

 

 

 

 

Cumulation counter

E110 0001

x1

Input metering accumulation

 

Error flag

E001 0111

x7

Manufacturer-specific VIFE codes

The manufacturer-specific VIFE codes in the table below are used by the meter when the VIF equals FF hex (1111 1111 bin).

NOTE: E denotes the extension bit; the hex value assumes E = 0.

Description

bin

hex

 

 

 

L1 value

E000 0001

01

 

 

 

L2 value

E000 0010

02

 

 

 

L3 value

E000 0011

03

 

 

 

Export energy value

E000 1001

09

 

 

 

Partial energy value

E000 1101

0D

 

 

 

Average current

E000 0000

00

 

 

 

L-N Avg

E000 0100

04

 

 

 

L1-L2

E000 0101

05

 

 

 

L2-L3

E000 0110

06

 

 

 

L3-L1

E000 0111

07

 

 

 

L-L Avg

E000 1000

08

 

 

 

Power Factor

E000 1010

0A

 

 

 

Frequency

E000 1011

0B

 

 

 

Energy reset date and time

E000 1100

0C

 

 

 

Input metering reset date and time

E000 1110

0E

 

 

 

Input metering accumulation

E000 1111

0F

 

 

 

Active tariff (Energy active rate)

E001 0000

10

 

 

 

Tariff control mode

E001 0001

11

 

 

 

Meter operation timer

E010 0000

20

 

 

 

Number of phases

E010 0001

21

 

 

 

Number of wires

E010 0010

22

 

 

 

Power system configuration

E010 0011

23

 

 

 

Nominal frequency

E010 0100

24

 

 

 

Number of VTs

E010 0101

25

 

 

 

VT primary

E010 0110

26

 

 

 

VT secondary

E010 0111

27

 

 

 

Number of CTs

E010 1000

28

 

 

 

CT Primary

E010 1001

29

 

 

 

CT Secondary

E010 1010

2A

 

 

 

VT connection type

E010 1011

2B

 

 

 

Energy pulse duration

E010 1100

2C

 

 

 

Digital output association with active energy pulsing

E010 1101

2D

 

 

 

Pulse weight

E010 1110

2E

 

 

 

Pulse constant

E010 1111

2F

 

 

 

Digital input association

E011 0000

30

 

 

 

Digital input status

E011 0010

32

 

 

 

Overload alarm setup

E011 0100

34

 

 

 

Pickup setpoint

E011 0101

35

 

 

 

Digital output association with overload alarm

E011 0110

36

 

 

 

Activated status

E011 0111

37

 

 

 

Acknowledgement

E011 1000

38

 

 

 

Date and time of last alarm

E011 1001

39

 

 

 

Value at last alarm

E011 1010

3A

 

 

 

78

DOCA0005EN-04

Image 78
Contents IEM3100 / iEM3200 / iEM3300 series Page DOCA0005EN-04 Safety information Important informationPlease note FCC Part 15 notice Document scope About the bookRelated documents Validity noteContents Chapter Power, energy and power factor 105 Chapter SpecificationsChapter Troubleshooting 103 Chapter Communications via M-BusSafety precautions Hazard of Electric SHOCK, EXPLOSION, or ARC FlashSafety precautions DOCA0005EN-04 Chapter Overview Main characteristicsWhat is in this chapter? Overview of meter functionsDigital outputs Or overload alarm Pulse output only 5 a metersFunction IEM32 series Typical applicationsIEM31 and iEM33 series Typical applicationsOverview IEM31 and iEM32 meters Hardware and installationDimensions IEM33 metersHardware overview All meters Meter sealing pointsIEM3100 / iEM3110 / iEM3115 Direct measurement up to 63 a Digital input IEM3200 / iEM3210 / iEM3215 Measurement with CTs IEM3235 Measurement with CTs and M-Bus communications IEM3275 Measurement with CTs and LonWorks communications IEM3300 / iEM3310 Direct measurement up to 125 aDigital input iEM3355 / iEM3365 DIN rail mounting and dismounting Mounting the meter on a DIN railDismounting the meter from a DIN rail Input, output and communications wiring Pulse output wiring iEM3110 / iEM3210 / iEM3310Digital input wiring iEM3115 / iEM3215 Bus communications wiring iEM3135 / iEM3235 / iEM3335 M-Bus communications connection is polarity-independentVoltage input protection Power system wiringLonWorks communications wiring iEM3175 / iEM3275 / iEM3375 Current input protection for 1 a and 5 a metersPower system Direct measurement meter wiringFuses and disconnect switch IEMPower system Wiring Power system Wiring1 a meter wiring Single-phase systems with CTsMA fuses and disconnect switch Shorting block Three-phase systems with CTs Three-phase systems with CTs and VTs Hardware and installation DOCA0005EN-04 Data display Front panel display and meter setup1234.5 Data display screen overviewExample navigating the display screens Data display screensPhase 3 Current Data display screens iEM3150 / iEM3250 / iEM3350Resetting accumulated energy using the display ResetsMulti Tariff feature Reset DescriptionDevice clock Clock behavior on power interruptionMeter status information Date/time formatEntering configuration mode Device configurationSetting the clock initially Front panel display in configuration modeModifying parameters Com. Protection settingExample Configuring a list value Selecting a value from a listConfiguration mode menus Canceling an entryExample configuring a numeric value Section Parameter Options Description 1PH2W L-L 1PH3W L-L-NConfiguration menu for iEM3150 / iEM3350 Com.Protection Contrast Password Reset Config By Internal Clock Configuration menus for iEM3200 / iEM3210 / iEM3215 Configuration menus for iEM3250 Com.Protection 3PH3W 3PH4W Section Parameter Options Description Front panel display and meter setup DOCA0005EN-04 Communications via Modbus RS-485 Modbus communications settingsCommunications LED indicator for Modbus devices Modbus communication overviewTable format Modbus functionsFunction list Unit tableCommand request Command interfaceCommand interface overview Command resultSet Date/Time Command listCommand Action Size Type Unit Range Description Action Size Type Unit Range Description NumberSet Pulse Output iEM3155 / iEM3255 / iEM3355 Set Tariff iEM3155 / iEM3255 / iEM3355Size Type Unit Range Description Input Metering Setup iEM3155 / iEM3255 / iEM3355 Overload Alarm Setup iEM3155 / iEM3255 / iEM3355Communications Setup Reset Input Metering Counter iEM3155 / iEM3255 / iEM3355 Meter Setup and StatusReset Partial Energy Counters Modbus register listInput Metering Setup iEM3155 / iEM3255 / iEM3355 Energy Pulse Output Setup iEM3155 / iEM3255 / iEM3355Command Interface CommunicationDigital Output iEM3155 / iEM3255 / iEM3355 Current, voltage, power, power factor and frequencyDigital Input iEM3155 / iEM3255 / iEM3355 Meter DataEnergy, energy by tariff and input metering Overload Alarm iEM3155 / iEM3255 / iEM3355 Read Device IdentificationEnergy values 32-bit floating point Object ID Name/Description Length Value LonWorks communications overview LED indicators for LonWorks metersCommunications via LonWorks LonWorks communication implementationSystem variables Location of the service pin and Neuron IDGeneral variables Green communications LEDEnergy and energy by tariff measurements Type DescriptionInstantaneous RMS measurements Alarm status System configuration informationDigital input configuration and status information Meter status informationDate/time setup Meter configuration propertiesResets Network variable label Type Description ActionInput metering setup Basic setupDigital input setup Struct Members Range / options DescriptionNetwork propagation rate setup Overload alarm setupMulti Tariff setup Range / options DescriptionInstalling and registering the LonMaker plug-in Plug-in has the following tabs Browsing the meter using the LonMaker plug-inLonMaker plug-in interface Tab name DescriptionMeter Status Communications via LonWorks DOCA0005EN-04 Bus communications overview Configuring basic communications settingsCommunications via M-Bus Key termsBus protocol support Bus protocol implementationVariable data structure telegram information Fixed data headerData record header information Manufacturer-specific Vife codes Description Bin HexBin Hex Telegram information for data recordsMeter information Primary VIF Primary VifeData format Instantaneous measurementsDate and time information Data format Primary VIFPower system configuration information Digital input and output status informationData format Primary Vife Supported Vife codes for meter configuration Telegram information for meter configurationAlarm status information Action Description Bin HexMulti Tariff setup Date/time setupPower system setup Data format Primary VIF DescriptionOverload alarm setup and acknowledgment Digital input setupDigital output setup Baud rateAccessing the meter using the tool Bus tool for data display and meter configurationInstalling the M-Bus tool ResetsViewing meter data using the M-Bus tool Configuring the meter using the M-Bus tool Select Setup Config to switch to configuration modeSection Description Communications via M-Bus DOCA0005EN-04 BACnet protocol support Communications via BACnetBACnet communications overview Related topicsFollowing standard object types are supported Configuring basic communication parametersBACnet communications implementation Object typeChange of Value COV subscriptions Communications LED indicator for BACnet metersBACnet object and property information Device objectObject ID Units Default COV Object name / description Analog Input objectsEnergy and energy by tariff measurements Instantaneous RMS measurements Meter informationCommunications settings information Digital input and output setting informationBinary Input objects CommandAnalog Value object Object ID Object name / descriptionCommunications via BACnet DOCA0005EN-04 Power system inputs iEM31 meters Chapter SpecificationsElectrical characteristics Power system inputs iEM33 metersPower system inputs iEM32 meters Characteristic Value MetersInputs and outputs Mechanical characteristics Environmental characteristicsMeasurement accuracy Internal clock Modbus communicationsLonWorks communications Bus communications BACnet communicationsSpecifications 102 DOCA0005EN-04 Diagnosis screen lists any current diagnostic codes TroubleshootingDo not open the meter. Opening the meter voids the warranty Diagnosis screenDiagnostic codes Description Possible solutionPower and the PQ coordinate system Power, energy and power factorPower PQS Power flowEnergy delivered imported / energy received exported Power factor PFTrue PF and displacement PF PF lead / lag conventionPF lead / lag summary Power and PF lead / lagPF sign convention PF sign in IECQuadrant Power factor register formatTo +1 To +1 +1 to +2Quadrant PF range PF formulaPower, energy and power factor 110 DOCA0005EN-04 Page Schneider Electric 35, rue Joseph Monier CS30323