Schneider Electric iEM3200 Meter status information, Snvt / Ucpt type Description, Alarm status

Page 67

iEM3100 / iEM3200 / iEM3300 series user manual

Communications via LonWorks

 

 

Meter status information

You can read the following network variables to obtain configuration and status information about the meter. For information on configuring the meter, see the sections on meter configuration properties and the LonWorks plug-in.

Network variable label

SNVT / UCPT type

Description

 

 

 

 

Basic information and meter configuration

 

 

nvoDateTime

SNVT_time_stamp

Meter date and time (DD/MM/YYYY hh:mm:ss)

 

 

 

nvoOpTimer

SNVT_count_32

Meter operation timer: the time in seconds since the meter was last

powered up

 

 

System configuration information

 

 

 

 

Power system configuration:

 

 

0

= 1PH2W L-N

 

 

1

= 1PH2W L-L

nciSystemType

SNVT_count

2

= 1PH3W L-L with N

 

 

3

= 3PH3W

 

 

11 = 3PH4W

 

 

13 = 1PH4 wire multi L-N

nciWireNum

SNVT_count

Number of wires

2, 3, 4

 

 

 

 

 

nciPhaseNum

SNVT_count

Number of phases

1, 3

 

 

 

 

 

 

 

Number of CTs

nciCtNum

SNVT_count

1, 2, 3

 

 

NOTE: only applies to the iEM3275

 

 

Number of VTs

nciVtNum

SNVT_count

0-10

 

 

NOTE: only applies to the iEM3275

nciVtPrimary

SNVT_count_32

VT Primary

NOTE: only applies to the iEM3275

 

 

nciVTSecondary

SNVT_count

VT Secondary

NOTE: only applies to the iEM3275

 

 

nciCtPrimary

SNVT_count

CT Primary

NOTE: only applies to the iEM3275

 

 

nciCtSecondary

SNVT_count

CT Secondary

NOTE: only applies to the iEM3275

 

 

 

 

VT connection type

nciVtConnType

SNVT_count

0

= Direct connection, no VTs

1

= 3PH3W (2VTs)

 

 

 

 

2

= 3PH4W (3VTs)

 

 

 

nciNominalFreq

SNVT_freq_hz

System frequency

50, 60

 

 

 

 

 

Digital input configuration and status information

 

 

Digital input control mode

 

 

0

= Normal (input status)

nciDICtrMode

SNVT_count

2

= Multi Tariff control

 

 

3

= Input metering

 

 

5

= All partial energy reset (configure to reset all partial energy logs)

 

 

 

nciDIPulseConst

SNVT_count_32

Pulse constant (pulses/unit)

 

 

 

 

 

Digital input status (only Bit 1 is used)

 

 

0

= relay open

nvoDIStatus

SNVT_count

1

= relay closed

 

 

NOTE: The information provided by this variable only applies if the

 

 

digital input control mode is set to Input Status.

Alarm status

 

 

 

 

 

Alarm status (only Bit 1 is used)

nvoAlmStatus

SNVT_count

0

= Alarm is inactive

 

 

1

= Alarm is active

 

 

 

 

DOCA0005EN-04

67

Image 67
Contents IEM3100 / iEM3200 / iEM3300 series Page DOCA0005EN-04 Important information Safety informationPlease note FCC Part 15 notice Validity note About the bookRelated documents Document scopeContents Chapter Communications via M-Bus Chapter SpecificationsChapter Troubleshooting 103 Chapter Power, energy and power factor 105Hazard of Electric SHOCK, EXPLOSION, or ARC Flash Safety precautionsSafety precautions DOCA0005EN-04 Overview of meter functions Main characteristicsWhat is in this chapter? Chapter Overview5 a meters Digital outputs Or overload alarm Pulse output onlyFunction Typical applications Typical applicationsIEM31 and iEM33 series IEM32 seriesOverview IEM33 meters Hardware and installationDimensions IEM31 and iEM32 metersAll meters Meter sealing points Hardware overviewIEM3100 / iEM3110 / iEM3115 Direct measurement up to 63 a Digital input IEM3200 / iEM3210 / iEM3215 Measurement with CTs IEM3235 Measurement with CTs and M-Bus communications IEM3300 / iEM3310 Direct measurement up to 125 a IEM3275 Measurement with CTs and LonWorks communicationsDigital input iEM3355 / iEM3365 Mounting the meter on a DIN rail DIN rail mounting and dismountingDismounting the meter from a DIN rail Pulse output wiring iEM3110 / iEM3210 / iEM3310 Input, output and communications wiringDigital input wiring iEM3115 / iEM3215 M-Bus communications connection is polarity-independent Bus communications wiring iEM3135 / iEM3235 / iEM3335Current input protection for 1 a and 5 a meters Power system wiringLonWorks communications wiring iEM3175 / iEM3275 / iEM3375 Voltage input protectionIEM Direct measurement meter wiringFuses and disconnect switch Power systemPower system Wiring Power system WiringSingle-phase systems with CTs 1 a meter wiringMA fuses and disconnect switch Shorting block Three-phase systems with CTs Three-phase systems with CTs and VTs Hardware and installation DOCA0005EN-04 Data display screen overview Front panel display and meter setup1234.5 Data displayData display screens Example navigating the display screensData display screens iEM3150 / iEM3250 / iEM3350 Phase 3 CurrentReset Description ResetsMulti Tariff feature Resetting accumulated energy using the displayDate/time format Clock behavior on power interruptionMeter status information Device clockFront panel display in configuration mode Device configurationSetting the clock initially Entering configuration modeSelecting a value from a list Com. Protection settingExample Configuring a list value Modifying parametersCanceling an entry Configuration mode menusExample configuring a numeric value 1PH2W L-L 1PH3W L-L-N Section Parameter Options DescriptionConfiguration menu for iEM3150 / iEM3350 Com.Protection Contrast Password Reset Config By Internal Clock Configuration menus for iEM3200 / iEM3210 / iEM3215 Configuration menus for iEM3250 Com.Protection 3PH3W 3PH4W Section Parameter Options Description Front panel display and meter setup DOCA0005EN-04 Modbus communication overview Modbus communications settingsCommunications LED indicator for Modbus devices Communications via Modbus RS-485Unit table Modbus functionsFunction list Table formatCommand result Command interfaceCommand interface overview Command requestAction Size Type Unit Range Description Number Command listCommand Action Size Type Unit Range Description Set Date/TimeSet Tariff iEM3155 / iEM3255 / iEM3355 Set Pulse Output iEM3155 / iEM3255 / iEM3355Size Type Unit Range Description Overload Alarm Setup iEM3155 / iEM3255 / iEM3355 Input Metering Setup iEM3155 / iEM3255 / iEM3355Communications Setup Modbus register list Meter Setup and StatusReset Partial Energy Counters Reset Input Metering Counter iEM3155 / iEM3255 / iEM3355Communication Energy Pulse Output Setup iEM3155 / iEM3255 / iEM3355Command Interface Input Metering Setup iEM3155 / iEM3255 / iEM3355Meter Data Current, voltage, power, power factor and frequencyDigital Input iEM3155 / iEM3255 / iEM3355 Digital Output iEM3155 / iEM3255 / iEM3355Energy, energy by tariff and input metering Read Device Identification Overload Alarm iEM3155 / iEM3255 / iEM3355Energy values 32-bit floating point Object ID Name/Description Length Value LonWorks communication implementation LED indicators for LonWorks metersCommunications via LonWorks LonWorks communications overviewGreen communications LED Location of the service pin and Neuron IDGeneral variables System variablesType Description Energy and energy by tariff measurementsInstantaneous RMS measurements Meter status information System configuration informationDigital input configuration and status information Alarm statusNetwork variable label Type Description Action Meter configuration propertiesResets Date/time setupStruct Members Range / options Description Basic setupDigital input setup Input metering setupRange / options Description Overload alarm setupMulti Tariff setup Network propagation rate setupInstalling and registering the LonMaker plug-in Tab name Description Browsing the meter using the LonMaker plug-inLonMaker plug-in interface Plug-in has the following tabsMeter Status Communications via LonWorks DOCA0005EN-04 Key terms Configuring basic communications settingsCommunications via M-Bus Bus communications overviewBus protocol implementation Bus protocol supportFixed data header Variable data structure telegram informationData record header information Description Bin Hex Manufacturer-specific Vife codesPrimary VIF Primary Vife Telegram information for data recordsMeter information Bin HexData format Primary VIF Instantaneous measurementsDate and time information Data formatDigital input and output status information Power system configuration informationData format Primary Vife Action Description Bin Hex Telegram information for meter configurationAlarm status information Supported Vife codes for meter configurationData format Primary VIF Description Date/time setupPower system setup Multi Tariff setupBaud rate Digital input setupDigital output setup Overload alarm setup and acknowledgmentResets Bus tool for data display and meter configurationInstalling the M-Bus tool Accessing the meter using the toolViewing meter data using the M-Bus tool Select Setup Config to switch to configuration mode Configuring the meter using the M-Bus toolSection Description Communications via M-Bus DOCA0005EN-04 Related topics Communications via BACnetBACnet communications overview BACnet protocol supportObject type Configuring basic communication parametersBACnet communications implementation Following standard object types are supportedDevice object Communications LED indicator for BACnet metersBACnet object and property information Change of Value COV subscriptionsAnalog Input objects Object ID Units Default COV Object name / descriptionEnergy and energy by tariff measurements Meter information Instantaneous RMS measurementsDigital input and output setting information Communications settings informationObject ID Object name / description CommandAnalog Value object Binary Input objectsCommunications via BACnet DOCA0005EN-04 Power system inputs iEM33 meters Chapter SpecificationsElectrical characteristics Power system inputs iEM31 metersCharacteristic Value Meters Power system inputs iEM32 metersInputs and outputs Environmental characteristics Mechanical characteristicsMeasurement accuracy Modbus communications Internal clockLonWorks communications BACnet communications Bus communicationsSpecifications 102 DOCA0005EN-04 Diagnosis screen TroubleshootingDo not open the meter. Opening the meter voids the warranty Diagnosis screen lists any current diagnostic codesDescription Possible solution Diagnostic codesPower flow Power, energy and power factorPower PQS Power and the PQ coordinate systemPF lead / lag convention Power factor PFTrue PF and displacement PF Energy delivered imported / energy received exportedPF sign in IEC Power and PF lead / lagPF sign convention PF lead / lag summaryTo +1 +1 to +2 Power factor register formatTo +1 QuadrantPF formula Quadrant PF rangePower, energy and power factor 110 DOCA0005EN-04 Page Schneider Electric 35, rue Joseph Monier CS30323