Schneider Electric iEM3300, iEM3200, iEM3100 user manual 3PH3W 3PH4W

Page 48

Front panel display and meter setup

 

iEM3100 / iEM3200 / iEM3300 series user manual

 

 

 

 

 

 

 

 

 

 

 

Section

Parameter

Options

Description

 

 

 

 

 

 

 

 

3PH3W

 

 

 

 

3PH4W

 

 

 

Type

1PH2W L-N

Select the power system type the meter is wired to.

 

 

1PH2W L-L

 

 

 

 

 

 

 

1PH3W L-L-N

 

 

Wiring

 

1PH4W Multi L-N

 

 

 

 

 

 

 

Direct-NoVT

Select how many voltage transformers (VT) are connected to the electrical power

 

 

 

 

 

VT

Wye(3VTs)

 

 

system.

 

 

 

Delta(2VTs)

 

 

 

 

 

 

 

3CTs on I1, I2, I3

Define how many current transformers (CT) are connected to the meter and which

 

 

CT

1 CT on I1

 

 

terminals they are connected to.

 

 

 

2 CTs on I1, I3

 

 

 

 

 

 

 

 

 

 

 

CT Secondary

1

Select the size of the CT secondary, in Amps.

 

 

5

 

 

 

 

 

 

CT Primary

1 - 32767

Enter the size of the CT primary, in Amps.

 

CT & VT Ratio

 

100

 

 

 

110

 

 

 

VT Secondary

Select the size of the VT secondary, in Volts.

 

 

115

 

 

 

 

 

 

 

120

 

 

 

VT Primary

1 - 1000000

Enter the size of the VT primary, in Volts.

 

Frequency

Frequency

50

Select the frequency of the electrical power system, in Hz.

 

60

 

 

 

 

 

 

 

 

 

 

Date

Date

DD-MMM-YYYY

Set the current date using the specified format.

 

 

 

 

 

 

Time

Time

hh:mm

Set the time using the 24-hour format.

 

 

 

 

 

 

 

 

 

Select the tariff control mode:

 

 

 

 

• Disable: the Multi Tariff function is disabled.

 

 

 

Disable

• by Communication: the active tariff is control by communications. See the chapter

 

 

 

for the applicable protocol for more information.

 

 

 

 

 

Multi Tariffs

Control Mode

by Communication

• by Digital Input: the digital input is associated with the multi-tariff function. A signal to

 

by Digital Input

the digital input changes the active tariff.

 

 

 

• by Internal Clock: the device clock controls the active tariff. If you set the Control

 

 

 

by Internal Clock

 

 

 

Mode to by Internal Clock, you must also configure the schedule. Set the time when

 

 

 

 

each tariff period starts, using the 24 hour clock format (00:00 to 23:59). The start

 

 

 

 

time of the next tariff is the end time of the current tariff. For example, T2 start

 

 

 

 

equals the end of T1.

 

 

 

Disable

Select whether or not the Overload Alarm is enabled:

 

Overload Alarm

Alarm

• Disable: the alarm is disabled.

 

Enable

 

 

 

• Enable: the alarm is enabled. If you enabled the Overload Alarm, you must also

 

 

 

 

configure the Pick Up Value in kW from 1 - 9999999.

 

 

 

 

Select how the digital output functions:

 

 

 

 

• Disable: the digital output is disabled.

 

 

 

Disable

• for Alarm: the digital output is associated with the overload alarm. The meter sends

 

Digital Output

DO Function

for Alarm

a pulse to the digital output port when the alarm is triggered.

 

• for Pulse: The digital output is associated with energy pulsing. When this mode is

 

 

 

for Pulse (kWh)

 

 

 

selected, you must also configure the can select the energy parameter and the set

 

 

 

 

the Pulse Constant (imp/kWh) and the Pulse Width (ms).

 

 

 

 

NOTE: the iEM3275 does not have a digital output.

 

 

 

 

Select how the digital input functions:

 

 

 

Input Status

• Input status: the digital input records the status of the input, for example, OF, SD of

 

 

 

a circuit breaker.

 

 

 

 

 

Digital Input

DI Function

Tariff Control

• Input Metering: the digital input is associated with input metering. The meter counts

 

Input Metering

and records the number of incoming pulses. If you set the DI Function to Input

 

 

 

Metering, you must also configure In. Pulse Constant.

 

 

 

Partial Reset

 

 

 

• Tariff Control: the digital input is associated with the multi-tariff function. A signal to

 

 

 

 

the digital input changes the active tariff.

 

 

 

 

• Partial Reset: a signal to the digital input initiates a partial reset.

 

 

Slave Address

1 - 247

Set the address for this device. The address must be unique for each device in a

 

 

communications loop.

 

 

 

 

 

 

 

19200

Select the speed for data transmission. The baud rate must be the same for all devices

 

 

Baud Rate

38400

 

Communication (iEM3255)

in a communications loop.

 

 

9600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Even

Select None if the parity bit is not used. The parity setting must be the same for all

 

 

Parity

Odd

devices in a communications loop.

 

 

 

None

NOTE: Number of stop bits = 1.

 

 

 

 

 

 

48

DOCA0005EN-04

Image 48
Contents IEM3100 / iEM3200 / iEM3300 series Page DOCA0005EN-04 Safety information Important informationPlease note FCC Part 15 notice About the book Related documentsDocument scope Validity noteContents Chapter Specifications Chapter Troubleshooting 103Chapter Power, energy and power factor 105 Chapter Communications via M-BusSafety precautions Hazard of Electric SHOCK, EXPLOSION, or ARC FlashSafety precautions DOCA0005EN-04 Main characteristics What is in this chapter?Chapter Overview Overview of meter functionsDigital outputs Or overload alarm Pulse output only 5 a metersFunction Typical applications IEM31 and iEM33 seriesIEM32 series Typical applicationsOverview Hardware and installation DimensionsIEM31 and iEM32 meters IEM33 metersHardware overview All meters Meter sealing pointsIEM3100 / iEM3110 / iEM3115 Direct measurement up to 63 a Digital input IEM3200 / iEM3210 / iEM3215 Measurement with CTs IEM3235 Measurement with CTs and M-Bus communications IEM3275 Measurement with CTs and LonWorks communications IEM3300 / iEM3310 Direct measurement up to 125 aDigital input iEM3355 / iEM3365 DIN rail mounting and dismounting Mounting the meter on a DIN railDismounting the meter from a DIN rail Input, output and communications wiring Pulse output wiring iEM3110 / iEM3210 / iEM3310Digital input wiring iEM3115 / iEM3215 Bus communications wiring iEM3135 / iEM3235 / iEM3335 M-Bus communications connection is polarity-independentPower system wiring LonWorks communications wiring iEM3175 / iEM3275 / iEM3375Voltage input protection Current input protection for 1 a and 5 a metersDirect measurement meter wiring Fuses and disconnect switchPower system IEMPower system Wiring Power system Wiring1 a meter wiring Single-phase systems with CTsMA fuses and disconnect switch Shorting block Three-phase systems with CTs Three-phase systems with CTs and VTs Hardware and installation DOCA0005EN-04 Front panel display and meter setup 1234.5Data display Data display screen overviewExample navigating the display screens Data display screensPhase 3 Current Data display screens iEM3150 / iEM3250 / iEM3350Resets Multi Tariff featureResetting accumulated energy using the display Reset DescriptionClock behavior on power interruption Meter status informationDevice clock Date/time formatDevice configuration Setting the clock initiallyEntering configuration mode Front panel display in configuration modeCom. Protection setting Example Configuring a list valueModifying parameters Selecting a value from a listConfiguration mode menus Canceling an entryExample configuring a numeric value Section Parameter Options Description 1PH2W L-L 1PH3W L-L-NConfiguration menu for iEM3150 / iEM3350 Com.Protection Contrast Password Reset Config By Internal Clock Configuration menus for iEM3200 / iEM3210 / iEM3215 Configuration menus for iEM3250 Com.Protection 3PH3W 3PH4W Section Parameter Options Description Front panel display and meter setup DOCA0005EN-04 Modbus communications settings Communications LED indicator for Modbus devicesCommunications via Modbus RS-485 Modbus communication overviewModbus functions Function listTable format Unit tableCommand interface Command interface overviewCommand request Command resultCommand list Command Action Size Type Unit Range DescriptionSet Date/Time Action Size Type Unit Range Description NumberSet Pulse Output iEM3155 / iEM3255 / iEM3355 Set Tariff iEM3155 / iEM3255 / iEM3355Size Type Unit Range Description Input Metering Setup iEM3155 / iEM3255 / iEM3355 Overload Alarm Setup iEM3155 / iEM3255 / iEM3355Communications Setup Meter Setup and Status Reset Partial Energy CountersReset Input Metering Counter iEM3155 / iEM3255 / iEM3355 Modbus register listEnergy Pulse Output Setup iEM3155 / iEM3255 / iEM3355 Command InterfaceInput Metering Setup iEM3155 / iEM3255 / iEM3355 CommunicationCurrent, voltage, power, power factor and frequency Digital Input iEM3155 / iEM3255 / iEM3355Digital Output iEM3155 / iEM3255 / iEM3355 Meter DataEnergy, energy by tariff and input metering Overload Alarm iEM3155 / iEM3255 / iEM3355 Read Device IdentificationEnergy values 32-bit floating point Object ID Name/Description Length Value LED indicators for LonWorks meters Communications via LonWorksLonWorks communications overview LonWorks communication implementationLocation of the service pin and Neuron ID General variablesSystem variables Green communications LEDEnergy and energy by tariff measurements Type DescriptionInstantaneous RMS measurements System configuration information Digital input configuration and status informationAlarm status Meter status informationMeter configuration properties ResetsDate/time setup Network variable label Type Description ActionBasic setup Digital input setupInput metering setup Struct Members Range / options DescriptionOverload alarm setup Multi Tariff setupNetwork propagation rate setup Range / options DescriptionInstalling and registering the LonMaker plug-in Browsing the meter using the LonMaker plug-in LonMaker plug-in interfacePlug-in has the following tabs Tab name DescriptionMeter Status Communications via LonWorks DOCA0005EN-04 Configuring basic communications settings Communications via M-BusBus communications overview Key termsBus protocol support Bus protocol implementationVariable data structure telegram information Fixed data headerData record header information Manufacturer-specific Vife codes Description Bin HexTelegram information for data records Meter informationBin Hex Primary VIF Primary VifeInstantaneous measurements Date and time informationData format Data format Primary VIFPower system configuration information Digital input and output status informationData format Primary Vife Telegram information for meter configuration Alarm status informationSupported Vife codes for meter configuration Action Description Bin HexDate/time setup Power system setupMulti Tariff setup Data format Primary VIF DescriptionDigital input setup Digital output setupOverload alarm setup and acknowledgment Baud rateBus tool for data display and meter configuration Installing the M-Bus toolAccessing the meter using the tool ResetsViewing meter data using the M-Bus tool Configuring the meter using the M-Bus tool Select Setup Config to switch to configuration modeSection Description Communications via M-Bus DOCA0005EN-04 Communications via BACnet BACnet communications overviewBACnet protocol support Related topicsConfiguring basic communication parameters BACnet communications implementationFollowing standard object types are supported Object typeCommunications LED indicator for BACnet meters BACnet object and property informationChange of Value COV subscriptions Device objectObject ID Units Default COV Object name / description Analog Input objectsEnergy and energy by tariff measurements Instantaneous RMS measurements Meter informationCommunications settings information Digital input and output setting informationCommand Analog Value objectBinary Input objects Object ID Object name / descriptionCommunications via BACnet DOCA0005EN-04 Chapter Specifications Electrical characteristicsPower system inputs iEM31 meters Power system inputs iEM33 metersPower system inputs iEM32 meters Characteristic Value MetersInputs and outputs Mechanical characteristics Environmental characteristicsMeasurement accuracy Internal clock Modbus communicationsLonWorks communications Bus communications BACnet communicationsSpecifications 102 DOCA0005EN-04 Troubleshooting Do not open the meter. Opening the meter voids the warrantyDiagnosis screen lists any current diagnostic codes Diagnosis screenDiagnostic codes Description Possible solutionPower, energy and power factor Power PQSPower and the PQ coordinate system Power flowPower factor PF True PF and displacement PFEnergy delivered imported / energy received exported PF lead / lag conventionPower and PF lead / lag PF sign conventionPF lead / lag summary PF sign in IECPower factor register format To +1Quadrant To +1 +1 to +2Quadrant PF range PF formulaPower, energy and power factor 110 DOCA0005EN-04 Page Schneider Electric 35, rue Joseph Monier CS30323