Schneider Electric iEM3100, iEM3300 Energy and energy by tariff measurements, Type Description

Page 65

iEM3100 / iEM3200 / iEM3300 series user manual

 

Communications via LonWorks

 

 

 

 

 

 

 

 

 

Network variable label

Type

Description

 

 

 

 

 

 

 

Device error status

 

 

 

Error bitmap: each bit of the bitmap provides error information about

 

 

 

the device. If value of the bit = 1, that error is active.

 

 

 

Bit0 = Code 101: EEPROM error

 

 

 

Bit1 = Code 102: No calibration table

 

 

 

Bit2 = Code 201: mismatch between frequency settings and

 

 

 

frequency measurements

 

nvoErrors

SNVT_state

Bit3 = Code 202: mismatch between wiring settings and wiring inputs

 

Bit4 = Code 203: phase sequence reversed

 

 

 

 

 

 

Bit5 = Not used

 

 

 

Bit6 = Code 205: Date and time have been reset due to a power

 

 

 

failure

 

 

 

Bit7 = Not used

 

 

 

Bit8 = Code 207: Abnormal internal clock function

 

 

 

Bit9 = Internal data bus communications error

 

 

 

Bit10 - 15: Not used

 

nciMeterModel

SNVT_str_asc

Device model, stored as an ASCII string (for example, iEM3275)

 

(SCPTpartNumber)

 

 

 

 

nciMeterManf

SNVT_str_asc

Manufacturer name (Schneider Electric)

 

(SCPToemType)

 

 

 

 

nciSerialNumber

SNVT_str_asc

Device serial number

 

(SCPTserialNumber)

 

 

 

 

nciManfDateTime

SNVT_time_stamp

Date of manufacture

 

(SCPTmanfDate)

 

 

 

 

 

 

LonWorks firmware major version (for example, 2.xx)

 

nciDevMajVer

SCPTdevMajVer

This variable functions with nciDevMinVer to provide the device’s

 

 

 

LonWorks firmware version

 

 

 

LonWorks firmware minor version (for example, x.34)

 

nciDevMinVer

SCPTdevMinVer

This variable functions with nciDevMajVer to provide the device’s

 

 

 

LonWorks firmware version

 

nciMeterVersion

SNVT_str_asc

Device firmware version, stored as an ASCII text string

 

(UCPTMeterVersion)

 

 

 

Related topics

See “Troubleshooting” on page 103 for more information on the error codes.

See “Network propagation rate setup” on page 70 for information on variables that control the network update rate.

Energy and energy by tariff measurements

Most energy values are available in both signed 32-bit integer and floating point format. The SNVT is appended with _l for 32-bit integer values and _f for floating point values.

For example, the SNVTs for total active energy import are as follows:

32-bit integer: SNVT_elec_kwh_l

Floating point: SNVT_elec_whr_f

The energy and energy by tariff measurements listed below are preserved through power failures.

Network variable label

Type

Description

 

 

 

nvoTotkWhImp

SNVT_elec_kwh_l

Total active energy import

nvoTotkWhExp

SNVT_elec_kwh_l

Total active energy export

nvoTotkVARhImp

SNVT_elec_kwh_l

Total reactive energy import

nvoTotkVARhExp

SNVT_elec_kwh_l

Total reactive energy export

nvoTotWhImp

SNVT_elec_whr_f

Total active energy import

nvoTotWhExp

SNVT_elec_whr_f

Total active energy export

nvoTotVARhImp

SNVT_elec_whr_f

Total reactive energy import

nvoTotVARhExp

SNVT_elec_whr_f

Total reactive energy export

nvoPartialkWh

SNVT_elec_kwh_l

Partial active energy import

nvoPartialkVARh

SNVT_elec_kwh_l

Partial reactive energy import

nvoPartialWh

SNVT_elec_whr_f

Partial active energy import

nvoPartialVARh

SNVT_elec_whr_f

Partial reactive energy import

DOCA0005EN-04

65

Image 65
Contents IEM3100 / iEM3200 / iEM3300 series Page DOCA0005EN-04 Please note Safety informationImportant information FCC Part 15 notice Related documents About the bookDocument scope Validity noteContents Chapter Troubleshooting 103 Chapter SpecificationsChapter Power, energy and power factor 105 Chapter Communications via M-BusHazard of Electric SHOCK, EXPLOSION, or ARC Flash Safety precautionsSafety precautions DOCA0005EN-04 What is in this chapter? Main characteristicsChapter Overview Overview of meter functionsFunction Digital outputs Or overload alarm Pulse output only5 a meters IEM31 and iEM33 series Typical applicationsIEM32 series Typical applicationsOverview Dimensions Hardware and installationIEM31 and iEM32 meters IEM33 metersIEM3100 / iEM3110 / iEM3115 Direct measurement up to 63 a Hardware overviewAll meters Meter sealing points Digital input IEM3200 / iEM3210 / iEM3215 Measurement with CTs IEM3235 Measurement with CTs and M-Bus communications IEM3300 / iEM3310 Direct measurement up to 125 a IEM3275 Measurement with CTs and LonWorks communicationsDigital input iEM3355 / iEM3365 Mounting the meter on a DIN rail DIN rail mounting and dismountingDismounting the meter from a DIN rail Digital input wiring iEM3115 / iEM3215 Input, output and communications wiringPulse output wiring iEM3110 / iEM3210 / iEM3310 M-Bus communications connection is polarity-independent Bus communications wiring iEM3135 / iEM3235 / iEM3335LonWorks communications wiring iEM3175 / iEM3275 / iEM3375 Power system wiringVoltage input protection Current input protection for 1 a and 5 a metersFuses and disconnect switch Direct measurement meter wiringPower system IEMPower system Wiring Power system WiringMA fuses and disconnect switch Shorting block 1 a meter wiringSingle-phase systems with CTs Three-phase systems with CTs Three-phase systems with CTs and VTs Hardware and installation DOCA0005EN-04 1234.5 Front panel display and meter setupData display Data display screen overviewData display screens Example navigating the display screensData display screens iEM3150 / iEM3250 / iEM3350 Phase 3 CurrentMulti Tariff feature ResetsResetting accumulated energy using the display Reset DescriptionMeter status information Clock behavior on power interruptionDevice clock Date/time formatSetting the clock initially Device configurationEntering configuration mode Front panel display in configuration modeExample Configuring a list value Com. Protection settingModifying parameters Selecting a value from a listExample configuring a numeric value Configuration mode menusCanceling an entry 1PH2W L-L 1PH3W L-L-N Section Parameter Options DescriptionConfiguration menu for iEM3150 / iEM3350 Com.Protection Contrast Password Reset Config By Internal Clock Configuration menus for iEM3200 / iEM3210 / iEM3215 Configuration menus for iEM3250 Com.Protection 3PH3W 3PH4W Section Parameter Options Description Front panel display and meter setup DOCA0005EN-04 Communications LED indicator for Modbus devices Modbus communications settingsCommunications via Modbus RS-485 Modbus communication overviewFunction list Modbus functionsTable format Unit tableCommand interface overview Command interfaceCommand request Command resultCommand Action Size Type Unit Range Description Command listSet Date/Time Action Size Type Unit Range Description NumberSize Type Unit Range Description Set Pulse Output iEM3155 / iEM3255 / iEM3355Set Tariff iEM3155 / iEM3255 / iEM3355 Communications Setup Input Metering Setup iEM3155 / iEM3255 / iEM3355Overload Alarm Setup iEM3155 / iEM3255 / iEM3355 Reset Partial Energy Counters Meter Setup and StatusReset Input Metering Counter iEM3155 / iEM3255 / iEM3355 Modbus register listCommand Interface Energy Pulse Output Setup iEM3155 / iEM3255 / iEM3355Input Metering Setup iEM3155 / iEM3255 / iEM3355 CommunicationDigital Input iEM3155 / iEM3255 / iEM3355 Current, voltage, power, power factor and frequencyDigital Output iEM3155 / iEM3255 / iEM3355 Meter DataEnergy, energy by tariff and input metering Energy values 32-bit floating point Overload Alarm iEM3155 / iEM3255 / iEM3355Read Device Identification Object ID Name/Description Length Value Communications via LonWorks LED indicators for LonWorks metersLonWorks communications overview LonWorks communication implementationGeneral variables Location of the service pin and Neuron IDSystem variables Green communications LEDType Description Energy and energy by tariff measurementsInstantaneous RMS measurements Digital input configuration and status information System configuration informationAlarm status Meter status informationResets Meter configuration propertiesDate/time setup Network variable label Type Description ActionDigital input setup Basic setupInput metering setup Struct Members Range / options DescriptionMulti Tariff setup Overload alarm setupNetwork propagation rate setup Range / options DescriptionInstalling and registering the LonMaker plug-in LonMaker plug-in interface Browsing the meter using the LonMaker plug-inPlug-in has the following tabs Tab name DescriptionMeter Status Communications via LonWorks DOCA0005EN-04 Communications via M-Bus Configuring basic communications settingsBus communications overview Key termsBus protocol implementation Bus protocol supportData record header information Variable data structure telegram informationFixed data header Description Bin Hex Manufacturer-specific Vife codesMeter information Telegram information for data recordsBin Hex Primary VIF Primary VifeDate and time information Instantaneous measurementsData format Data format Primary VIFData format Primary Vife Power system configuration informationDigital input and output status information Alarm status information Telegram information for meter configurationSupported Vife codes for meter configuration Action Description Bin HexPower system setup Date/time setupMulti Tariff setup Data format Primary VIF DescriptionDigital output setup Digital input setupOverload alarm setup and acknowledgment Baud rateInstalling the M-Bus tool Bus tool for data display and meter configurationAccessing the meter using the tool ResetsViewing meter data using the M-Bus tool Section Description Configuring the meter using the M-Bus toolSelect Setup Config to switch to configuration mode Communications via M-Bus DOCA0005EN-04 BACnet communications overview Communications via BACnetBACnet protocol support Related topicsBACnet communications implementation Configuring basic communication parametersFollowing standard object types are supported Object typeBACnet object and property information Communications LED indicator for BACnet metersChange of Value COV subscriptions Device objectEnergy and energy by tariff measurements Object ID Units Default COV Object name / descriptionAnalog Input objects Meter information Instantaneous RMS measurementsDigital input and output setting information Communications settings informationAnalog Value object CommandBinary Input objects Object ID Object name / descriptionCommunications via BACnet DOCA0005EN-04 Electrical characteristics Chapter SpecificationsPower system inputs iEM31 meters Power system inputs iEM33 metersInputs and outputs Power system inputs iEM32 metersCharacteristic Value Meters Measurement accuracy Mechanical characteristicsEnvironmental characteristics LonWorks communications Internal clockModbus communications BACnet communications Bus communicationsSpecifications 102 DOCA0005EN-04 Do not open the meter. Opening the meter voids the warranty TroubleshootingDiagnosis screen lists any current diagnostic codes Diagnosis screenDescription Possible solution Diagnostic codesPower PQS Power, energy and power factorPower and the PQ coordinate system Power flowTrue PF and displacement PF Power factor PFEnergy delivered imported / energy received exported PF lead / lag conventionPF sign convention Power and PF lead / lagPF lead / lag summary PF sign in IECTo +1 Power factor register formatQuadrant To +1 +1 to +2PF formula Quadrant PF rangePower, energy and power factor 110 DOCA0005EN-04 Page Schneider Electric 35, rue Joseph Monier CS30323