Schneider Electric iEM3200 Telegram information for meter configuration, Alarm status information

Page 82

Communications via M-Bus

 

 

 

 

iEM3100 / iEM3200 / iEM3300 series user manual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data format

Primary VIFE

Manufacturer-specific VIFE

 

Description

 

 

 

 

 

bin

hex

bin

hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pulse weight of the digital output

05

E010 1110

2E

NOTE: This information only applies if the digital output mode is set to

 

 

 

 

 

energy pulsing.

 

 

 

 

 

Digital output control mode

03

E001 1010

1A

2

= for Alarm

3

= for Pulse (kWh)

 

 

 

 

 

 

 

 

 

 

0xFFFF = Disabled

 

 

 

 

 

 

 

 

 

 

 

Digital output association with energy pulsing:

03

E010 1101

2D

0

= Digital output disabled

 

 

 

 

 

1

= for Pulse (digital output is associated with active energy pulse output)

 

 

 

 

 

 

 

 

 

 

 

Digital output association with overload alarm:

02

E011 0110

36

0x0000 = digital output disabled

 

 

 

 

 

0x0100 = for Alarm (digital output is associated with the overload alarm)

Alarm status information

NOTE: E denotes the extension bit; the hex value assumes E = 0.

Data format

Primary VIF

Manufacturer-specific VIFE

 

Description

 

 

 

 

bin

 

hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm status:

02

E011 0111

37

 

0x0000

= Alarm is inactive

 

 

 

 

 

0x0100

= Alarm is active

 

 

 

 

 

 

 

 

 

 

 

Acknowledgement status:

02

E011 1000

38

 

0x0000

= historic alarm is acknowledged by the user

 

 

 

 

 

0x0100

= historic alarm is unacknowledged by the user

04

ED

E011 1001

39

 

Timestamp of last alarm (DD/MM/YYYY hh:mm:ss)

05

E011 1010

3A

 

Value at last alarm

 

 

 

 

 

Overload alarm configuration:

02

E011 0100

34

 

0x0000

= disabled

 

 

 

 

 

0x0100

= enabled

 

 

 

 

 

 

05

E011 0101

35

 

The pickup setpoint in kW for the overload alarm

 

 

 

 

 

 

 

Telegram information for meter configuration

You can use the information provided in this section to write to the meter using a SND_UD function.

NOTE: If Com. Protection is enabled, you may receive an error response when you try to configure the meter over communications.

You can also configure the meter using the M-Bus tool available from www.schneider-electric.com.

Supported VIFE codes for meter configuration

NOTE: E denotes the extension bit; the hex value assumes E = 0.

VIFE code

 

Action

Description

 

 

 

bin

 

hex

 

 

 

 

 

 

 

 

E000 0000

00

 

Write and replace

Replaces the old value with the new value.

 

 

 

 

 

E000 0111

07

 

Clear

Resets an accumulated value to 0 (zero).

 

 

 

 

 

Related topics

See “Configuration mode menus” on page 40 for information on enabling and disabling Com. Protection.

See “M-Bus tool for data display and meter configuration” on page 85 for information on the M-Bus tool.

82

DOCA0005EN-04

Image 82
Contents IEM3100 / iEM3200 / iEM3300 series Page DOCA0005EN-04 Important information Safety informationPlease note FCC Part 15 notice Document scope About the bookRelated documents Validity noteContents Chapter Power, energy and power factor 105 Chapter SpecificationsChapter Troubleshooting 103 Chapter Communications via M-BusSafety precautions Hazard of Electric SHOCK, EXPLOSION, or ARC FlashSafety precautions DOCA0005EN-04 Chapter Overview Main characteristicsWhat is in this chapter? Overview of meter functions5 a meters Digital outputs Or overload alarm Pulse output onlyFunction IEM32 series Typical applicationsIEM31 and iEM33 series Typical applicationsOverview IEM31 and iEM32 meters Hardware and installationDimensions IEM33 metersAll meters Meter sealing points Hardware overviewIEM3100 / iEM3110 / iEM3115 Direct measurement up to 63 a Digital input IEM3200 / iEM3210 / iEM3215 Measurement with CTs IEM3235 Measurement with CTs and M-Bus communications IEM3275 Measurement with CTs and LonWorks communications IEM3300 / iEM3310 Direct measurement up to 125 aDigital input iEM3355 / iEM3365 DIN rail mounting and dismounting Mounting the meter on a DIN railDismounting the meter from a DIN rail Pulse output wiring iEM3110 / iEM3210 / iEM3310 Input, output and communications wiringDigital input wiring iEM3115 / iEM3215 Bus communications wiring iEM3135 / iEM3235 / iEM3335 M-Bus communications connection is polarity-independentVoltage input protection Power system wiringLonWorks communications wiring iEM3175 / iEM3275 / iEM3375 Current input protection for 1 a and 5 a metersPower system Direct measurement meter wiringFuses and disconnect switch IEMPower system Wiring Power system WiringSingle-phase systems with CTs 1 a meter wiringMA fuses and disconnect switch Shorting block Three-phase systems with CTs Three-phase systems with CTs and VTs Hardware and installation DOCA0005EN-04 Data display Front panel display and meter setup1234.5 Data display screen overviewExample navigating the display screens Data display screensPhase 3 Current Data display screens iEM3150 / iEM3250 / iEM3350Resetting accumulated energy using the display ResetsMulti Tariff feature Reset DescriptionDevice clock Clock behavior on power interruptionMeter status information Date/time formatEntering configuration mode Device configurationSetting the clock initially Front panel display in configuration modeModifying parameters Com. Protection settingExample Configuring a list value Selecting a value from a listCanceling an entry Configuration mode menusExample configuring a numeric value Section Parameter Options Description 1PH2W L-L 1PH3W L-L-NConfiguration menu for iEM3150 / iEM3350 Com.Protection Contrast Password Reset Config By Internal Clock Configuration menus for iEM3200 / iEM3210 / iEM3215 Configuration menus for iEM3250 Com.Protection 3PH3W 3PH4W Section Parameter Options Description Front panel display and meter setup DOCA0005EN-04 Communications via Modbus RS-485 Modbus communications settingsCommunications LED indicator for Modbus devices Modbus communication overviewTable format Modbus functionsFunction list Unit tableCommand request Command interfaceCommand interface overview Command resultSet Date/Time Command listCommand Action Size Type Unit Range Description Action Size Type Unit Range Description NumberSet Tariff iEM3155 / iEM3255 / iEM3355 Set Pulse Output iEM3155 / iEM3255 / iEM3355Size Type Unit Range Description Overload Alarm Setup iEM3155 / iEM3255 / iEM3355 Input Metering Setup iEM3155 / iEM3255 / iEM3355Communications Setup Reset Input Metering Counter iEM3155 / iEM3255 / iEM3355 Meter Setup and StatusReset Partial Energy Counters Modbus register listInput Metering Setup iEM3155 / iEM3255 / iEM3355 Energy Pulse Output Setup iEM3155 / iEM3255 / iEM3355Command Interface CommunicationDigital Output iEM3155 / iEM3255 / iEM3355 Current, voltage, power, power factor and frequencyDigital Input iEM3155 / iEM3255 / iEM3355 Meter DataEnergy, energy by tariff and input metering Read Device Identification Overload Alarm iEM3155 / iEM3255 / iEM3355Energy values 32-bit floating point Object ID Name/Description Length Value LonWorks communications overview LED indicators for LonWorks metersCommunications via LonWorks LonWorks communication implementationSystem variables Location of the service pin and Neuron IDGeneral variables Green communications LEDEnergy and energy by tariff measurements Type DescriptionInstantaneous RMS measurements Alarm status System configuration informationDigital input configuration and status information Meter status informationDate/time setup Meter configuration propertiesResets Network variable label Type Description ActionInput metering setup Basic setupDigital input setup Struct Members Range / options DescriptionNetwork propagation rate setup Overload alarm setupMulti Tariff setup Range / options DescriptionInstalling and registering the LonMaker plug-in Plug-in has the following tabs Browsing the meter using the LonMaker plug-inLonMaker plug-in interface Tab name DescriptionMeter Status Communications via LonWorks DOCA0005EN-04 Bus communications overview Configuring basic communications settingsCommunications via M-Bus Key termsBus protocol support Bus protocol implementationFixed data header Variable data structure telegram informationData record header information Manufacturer-specific Vife codes Description Bin HexBin Hex Telegram information for data recordsMeter information Primary VIF Primary VifeData format Instantaneous measurementsDate and time information Data format Primary VIFDigital input and output status information Power system configuration informationData format Primary Vife Supported Vife codes for meter configuration Telegram information for meter configurationAlarm status information Action Description Bin HexMulti Tariff setup Date/time setupPower system setup Data format Primary VIF DescriptionOverload alarm setup and acknowledgment Digital input setupDigital output setup Baud rateAccessing the meter using the tool Bus tool for data display and meter configurationInstalling the M-Bus tool ResetsViewing meter data using the M-Bus tool Select Setup Config to switch to configuration mode Configuring the meter using the M-Bus toolSection Description Communications via M-Bus DOCA0005EN-04 BACnet protocol support Communications via BACnetBACnet communications overview Related topicsFollowing standard object types are supported Configuring basic communication parametersBACnet communications implementation Object typeChange of Value COV subscriptions Communications LED indicator for BACnet metersBACnet object and property information Device objectAnalog Input objects Object ID Units Default COV Object name / descriptionEnergy and energy by tariff measurements Instantaneous RMS measurements Meter informationCommunications settings information Digital input and output setting informationBinary Input objects CommandAnalog Value object Object ID Object name / descriptionCommunications via BACnet DOCA0005EN-04 Power system inputs iEM31 meters Chapter SpecificationsElectrical characteristics Power system inputs iEM33 metersCharacteristic Value Meters Power system inputs iEM32 metersInputs and outputs Environmental characteristics Mechanical characteristicsMeasurement accuracy Modbus communications Internal clockLonWorks communications Bus communications BACnet communicationsSpecifications 102 DOCA0005EN-04 Diagnosis screen lists any current diagnostic codes TroubleshootingDo not open the meter. Opening the meter voids the warranty Diagnosis screenDiagnostic codes Description Possible solutionPower and the PQ coordinate system Power, energy and power factorPower PQS Power flowEnergy delivered imported / energy received exported Power factor PFTrue PF and displacement PF PF lead / lag conventionPF lead / lag summary Power and PF lead / lagPF sign convention PF sign in IECQuadrant Power factor register formatTo +1 To +1 +1 to +2Quadrant PF range PF formulaPower, energy and power factor 110 DOCA0005EN-04 Page Schneider Electric 35, rue Joseph Monier CS30323